Plan Review Details - Permit 04080325
Plan Review Stops For Permit 04080325
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-05-23 Cont ID  
Sent By shill Date 2005-05-23 Time 10:01 Rev Time 0.50
Received By shill Date 2005-05-23 Time 10:01 Sent To PC
Notes
2005-05-23 00:00:00SHUTTER INSTALLATION PLAN - SAME AS ON
 FILE FOR CONDOS; OK PER BS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-02-03 Cont ID  
Sent By shill Date 2005-02-03 Time 09:14 Rev Time 0.50
Received By shill Date 2005-02-03 Time 09:14 Sent To PC
Notes
2005-02-03 00:00:00****CORRECTIONS****
 HURRICANE SHUTTER INSTALLATION PLAN
 NOT A PLAN REVIEW
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE CONTRACT WITH KLEAN K. SERVICES
 IS TO BE AN ORIGINAL, SIGNED AND
 NOTARIZED CONTRACT.THE LANGUAGE IN THE
 CONTRACT IS TO BE CONSISTENT WITH THE
 CITY'S POLICY IN REGARDS TO THE TIME
 FRAME (HURRICANE WATCH, NOT WARNING).
 THE LANGUAGE STATES "PRIOR TO A
 HURRICANE WARNING"; PLEASE INCLUDE
 LANGUAGE CONSISTENT WITH YOUR PLAN.
  
 2.)THE "CONTRACT" WITH KLEAN K.
 SERVICES PROVIDED WAS AN INVOICE, NOT A
 CONTRACT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-01-21 Cont ID  
Sent By shill Date 2005-01-21 Time 14:02 Rev Time 2.00
Received By shill Date 2005-01-21 Time 13:11 Sent To PC
Notes
2005-01-21 00:00:00PROVISO - APPROVED SHUTTER INSTALLATION
 PLAN REQUIRED BEFORE FRAMING
  
  
 ***HOLD ON C.O. - CONTRACTOR'S
 RESPONSIBILITY TO HAVE HOLD REMOVED
 AFTER APPROVAL OF PLAN***
  
 SAMANTHA HILL, 561-805-6724

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-12-13 Cont ID  
Sent By shill Date 2004-12-13 Time 11:16 Rev Time 2.00
Received By shill Date 2004-12-13 Time 08:12 Sent To  
Notes
2004-12-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE WINDOWS ON THE SECOND FLOOR
 MUST BE IMPACT GLASS.PLEASE NOTE THAT
 THE PRODUCT APPROVAL SUBMITTED IS FOR A
 FIXED WINDOW, PLAN SHOWS OPERABLE
 (CASEMENT)
  
 2.)REGARDING THE INSTALLATION PLAN
 FOR
 HURRICANE PROTECTION, PLEASE SUBMIT AN
 ORIGINAL CONTRACT WITH KLEAN K.
 SERVICES.SERVICES ARE TO BE PERFORMED
 BY INDIVIDUALS WITHIN PALM BEACH COUNTY
 AS PER THE POLICY; PLEASE NOTE IN THE
 PROPOSED PLAN.
  
 3.)SEE THE SOILS REPORT; CONTINUOUS
 FOOTINGS ARE TO BE MIN 18" BELOW GRADE.
 F1 APPEARS TO BE BETWEEN 12-14" BELOW
 GRADE.ALSO SEE 6.3.2 OF THE ORIGINAL
 SOILS REPORT; WAS DESIGNER OF RECORD
 AWARE OF THE RECOMMENDATION IN REGARDS
 TO MONOLITHIC SLABS?PLEASE ASK DOR TO
 READ BOTH SOILS REPORTS BEFORE
 RESUBMITTAL.
  
 4.)SOILS REPORTS ARE TO BE SEALED.
  
 5.)SEE THE PREVIOUS LIST, ITEM #11.
 RECEIPT OF AN UNSEALED LETTER
 ADDRESSING
 THIS MATTER FROM SHAWN STAMBAUGH, PE IS
 ACKNOWLEDGED.IF THE FASTENING
 CONFLICTS WITH THE TECHNICAL BULLETIN
 FROM
 THE MANUFACTURER, LOCAL PRODUCT
 APPROVAL
 (WITH CALCULATIONS) IS REQUIRED
 FAC9B-72.PLEASE FEEL FREE TO CONTACT
 ME TO DISCUSS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-12-01 Cont ID  
Sent By shill Date 2004-12-01 Time 15:05 Rev Time 0.00
Received By shill Date 2004-12-01 Time 15:05 Sent To  
Notes
2004-12-01 00:00:00***SUBMITTAL***
 OR BK 14613/1560
 DEED (ORCHID RESERVE HOA)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-23 Cont ID  
Sent By shill Date 2004-08-23 Time 09:24 Rev Time 4.00
Received By shill Date 2004-08-20 Time 16:43 Sent To  
Notes
2004-08-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE OWNER ON THE APPLICATION DOES
 NOT MATCH THE OWNER IN OUR RECORDS.
 PLEASE ADDRESS.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 3.)PLEASE PROVIDE A SECOND COPY OF
 THE ENERGY CALCS.
  
 4.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 5.)ADDITIONAL FEES DUE (VALUE
 INCREASE, RADON).
  
 6.)SITE PLAN, S1 DIFFERS FROM THE
 SITE PLAN PREPARED BY THE SURVEYOR.
  
 7.)SHEET C1, CALCULATIONS, GROUND
 FLOOR LIVE LOAD IS TO COMPLY WITH
 FBC TABLE 1604.1.YOU DECLARE AN
 OCCUPANCY OF 7 PER SF WHICH WOULD BE
 CONSISTENT WITH ASSEMBLY WITHOUT FIXED
 SEATS FBC TABLE 1003.4.SHEET C1 GIVE
 A LIVE LOAD FOR FLOORS OF 40.ASSEMBLY
 WITHOUT FIXED SEATS REQUIRES 100, FBC
 TABLE 1604.1.PLEASE REVISE.
  
 8.)PROVIDE A SOILS INVESTIGATION
 REPORT FBC1804.2.2.
  
 9.)PLEASE PROVIDE A DIMENSION FOR
 'A' (ZONE 3 EDGE STRIP), ROOF ZONE
 DIAGRAM A7.
  
 10.) 6-A6 SHOWS FLOOR TRUSSES.C1
 REFERS TO 2ND FLOOR LIVE LOAD DESIGN
 CRITERIA.6-A6 IS USED IN AN AREA
 WHICH DOES NOT APPEAR TO HAVE A 2ND
 FLOOR, AND A 2ND FLOOR PLAN HAS NOT
 BEEN PROVIDED.AREA CALCS ARE FOR A
 FIRST FLOOR ONLY.PLEASE CLARIFY.
  
 11.)12-A6, THE FASTENING AND
 ALLOWABLE LOADS CONFLICT WITH THE
 TECHNICAL BULLETIN.PLEASE CLARIFY.
 CHECK ALL CONNECTORS.
  
 12.)THE PRE STORM PREPARATION PLAN
 SUBMITTED IS FOR THE CONDOMINIUM
 BUILDINGS. SUBMIT A PLAN FOR THE
 CLUBHOUSE.
  
 13.)THE PRODUCT APPROVAL FOR THE
 BENCHMARK DOOR IS FOR AN OPAQUE DOOR
 WITH SIDELITES; PRODUCT APPROVALS FOR
 SLIDING GLASS DOORS AND HORIZONTAL
 SLIDER WINDOWS WERE SUBMITTED; NONE ON
 THE PLAN.PLEASE SUBMIT PRODUCT
 APPROVALS FOR THE MULLIONS, FRENCH
 DOORS, SINGLE HUNG WINDOWS, 3080 SOLID
 DOORS, AND ROOF.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2005-10-09 Cont ID  
Sent By dpalmer Date 2005-10-09 Time 13:36 Rev Time 0.25
Received By dpalmer Date 2005-10-09 Time 13:36 Sent To FIRE
Notes
2005-10-09 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE REVISON FOR LIFE
 SAFETY PLAN FOR CLUBHOUSE SUBMITTED,
 HOWEVER REVSIONS SUBMITTED CONTAIN ONLY
 ONE SET, THE SECOND SET IS A SHEET FROM
 BLDG #5??
  
 PLANS SENT TO FIRE FOR REVIEW OF LS
 PLANS.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 PLEASE SEE FIRE REVIEW COMMENTS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-08-09 Cont ID  
Sent By dpalmer Date 2005-08-09 Time 19:24 Rev Time 0.40
Received By dpalmer Date 2005-08-09 Time 19:24 Sent To  
Notes
2005-08-09 00:00:00210.8B3

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-08-04 Cont ID  
Sent By dpalmer Date 2005-08-04 Time 08:25 Rev Time 0.33
Received By dpalmer Date 2005-08-04 Time 07:45 Sent To  
Notes
2005-08-04 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE SEE PREVIOUS PLANS WERE
 NOTED ABOUT CONTINUOUS LOADS, PLEASE SEE
 CONTINUOUS LOADS (PUMP/VAL PAK AND HEAT
 PUMP) ON POOL SUB PANEL ARE TO BE SHOWN
 AT 125% ON SUB PANEL. THIS LOAD WOULD
 JUST BE CARRIED OVER TO THE LOAD ON MAIN
 PANEL. IT IT SHOWN AT 125% ON MAIN
 PANEL, JUST NOT SUB PANEL.
 215.3,680.9,230.42 ETC
  
 2)NOTE: PLEASE SEE A SINK? APPEARS TO BE
 SHOWN DIRECTLY INFRON OF PANEL "A"?
 110.26
  
 3)NOTE: PLEASE SEE PLANS ARE NOT SEALED
 BY ARCHITECT OF RECORD.
 PLEASE SEE FS 481.221
  
 PLEASE ADDRESS NOTES ONE AND TWO SINCE
 PLANS ARE COMING BACK FOR NOTE #3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-07-18 Cont ID  
Sent By dpalmer Date 2005-07-18 Time 09:56 Rev Time 0.50
Received By dpalmer Date 2005-07-18 Time 09:56 Sent To  
Notes
2005-07-18 00:00:00LOAD CALCS?

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-07-08 Cont ID  
Sent By dpalmer Date 2005-07-08 Time 13:06 Rev Time 0.50
Received By dpalmer Date 2005-07-08 Time 13:06 Sent To  
Notes
2005-07-08 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE 250.66 ,310.16 FOR
 SIZING OF MIN GROUNDING ELECTRODE
 CONDUCTOR. #2 MIN.
 PREVIOUS REVIEW.
  
 2)NOTE:PLEASE SEE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%.
 PLEASE SEE ONLY CONTINUOUS ARE TO BE
 INDICATED AS "CONTINUOUS LOADS".
 PLEASE SEE ART 100 NEC FOR DEFINITION OF
 CONT LOADS.
 CONTINUOUS LOAD. A LOAD WHERE THE
 MAXIMUM CURRENT IS EXPECTED TO CONTINUE
 FOR 3 HOURS OR MORE.
  
 PLEASE SEE SERVICE ETC IS BEING SHOWN AS
 ALL BEING CONT???
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-01-03 Cont ID  
Sent By dpalmer Date 2005-01-03 Time 07:40 Rev Time 0.33
Received By dpalmer Date 2005-01-03 Time 07:34 Sent To  
Notes
2005-01-03 00:00:00******** PROVISO/REVISION ***********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEWS.
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAINS TO
 PANELS.
 EQUIPMENT GRNDS REQUIRED AFTER THE FIRST
 MEANS OF DISC. 250.24, 250.110, SIZE PER
 250.122
  
 2)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR PER 250.66 1/0.
  
 3)NOTE: PLEASE SEE CIRCUITING FOR EM
 LTS
 PER 700.12E WITH LOCAL LIGHTING BRANCH
 CIRCUIT.
  
 PLEASE REVISE THE ABOVE ALONG WITH ANY
 OTHER REVISIONS BEFORE ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-18 Cont ID  
Sent By dpalmer Date 2004-11-18 Time 13:41 Rev Time 0.50
Received By dpalmer Date 2004-11-18 Time 13:24 Sent To  
Notes
2004-11-18 00:00:00***** UNSAT 2ND REVIEW *****
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 OK
  
 2)NOTE: NOTE #2 OK
  
 3)NOTE: NOTE #3 OK
  
 4)NOTE: NOTE #4 OK
  
 5)NOTE: NOTE #5 NO.
 PLEASE SEE 250.24, 250.110 FOR EQUIPMENT
 GROUNDING AFTER THE FRIST MEANS OF
 DISCONNECT. SIZED PER 250.122
  
 6)NOTE: NOTE #6 NO.
 PLEASE SHOW LOAD CALCULATIONS, PLEASE
 SHOW PER 220.3,220.10,220.11,220.13
 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 7)NOTE: NOTE #7 NO.
 PLEASE SEE EM/EXT LTS ARE NOW SHOWN ON A
 SEPARATE CIRCUIT. PLEASE SEE 700.12E FOR
 CIRCUITING TO LOCAL AREA LIGHTING.
  
 *NEW NOTE DUE TO CHANGES IN PLANS.
  
 1)NOTE: PLEASE SEE GROUNDING ELECTRODE
 DETAIL HAS NOW ADDED PARALLEL #6'S FOR
 GROUNDING ELECTRODE CONDUCTOR.
  
  
 2)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
 THIS IS ONLY GIVEN AS A NOTICE AT THIS
 TIME.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
  
  
 THIS IS NOT PERMITTED, MAY ONLY USE THE
 #2 AS ALSO SHOWN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-18 Cont ID  
Sent By dpalmer Date 2004-08-18 Time 10:55 Rev Time 0.75
Received By dpalmer Date 2004-08-18 Time 10:52 Sent To  
Notes
2004-08-18 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE CORRELATE ELECTRICAL
 PLANS W/ MECHANICAL PLANS.
 MECH PLANS SHOW TWO A/C SYSTEMS.
 PLEASE ALSO SEE OCP FOR A/C SYSTEMS
 ALONG WITH LOAD CALCULATIONS.
  
 3)NOTE: PLEASE CORRELATE RISER WITH
 PLANS. PLANS SHOW TWO NEW PANELS? A&B
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 MAIN.
  
 5 )NOTE: PLEASE SHOW /CLARIFY METHOD
 OF THE EQUIPMENT GROUNDING BETWEEN
 MAIN MEANS OF DISC AND PANELS/GUTTERS.
 250.110,250.24
 PLEASE SIZE ALL EQUIPMENT GROUNDING
 CONDUCTORS PER 250.122
  
 6)NOTE: PLEASE SEE THIS IS CONSIDERED
 A COMMERCIAL BLDG.
 PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 NEEDS TO REFLECT.
  
 7)NOTE: PLEASE SEE 700.12E FOR CIRCUIT--
 -ING OF EM/EXT LTS.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-08-13 Cont ID  
Sent By mamini Date 2004-08-13 Time 09:06 Rev Time 0.50
Received By mamini Date 2004-08-13 Time 09:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2005-10-11 Cont ID  
Sent By nmccray Date 2005-10-11 Time 10:59 Rev Time 0.00
Received By nmccray Date 2005-10-11 Time 10:34 Sent To  
Notes
2005-10-11 00:00:00DENIED:
  
 1) THERE ARE TWO DIFFERENT SET OF PLANS
 IN PACKET. ONE SET OF LIFE SAFETY PLAN
 FOR THE CLUBHOUSE (PORTOFINO SHORES ST.
 LUCIE COUNTY) THE OTHER SET IS
 ELECTRICAL PLAN FOR COACH HOMES 1 IN
 BUILDING 5.
  
 2) PLEASE IDENTIFY WHAT REVISION THAT
 YOU WANT AND RESUBMIT TO CONSTRUCTION
 SERVICES.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-01-18 Cont ID  
Sent By nmccray Date 2005-01-18 Time 14:55 Rev Time 0.00
Received By nmccray Date 2005-01-18 Time 14:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-15 Cont ID  
Sent By mcarsill Date 2004-12-15 Time 07:57 Rev Time 0.00
Received By mcarsill Date 2004-12-15 Time 07:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-09-16 Cont ID  
Sent By mcarsill Date 2004-09-16 Time 09:49 Rev Time 0.00
Received By mcarsill Date 2004-09-16 Time 09:49 Sent To  
Notes
2004-09-16 00:00:001) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND
 CEILINGS.
  
 2) BUILDING ADDRESS NOPT SHOWN ON
 ELEVATION DRAWINGS. A MINIMUM OF AT
 LEAST 6" HIGH NUMBERS ARE REQUIRED.
  
 3) THERE APPEARS TO BE FIRE ALARM NOTES
 ON PAGE A-8 WHICH MAY NOT BE APPLICABLE
 TO THIS PROJECT. PLEASE ADVISE.
  
 4) ALL NEW STAIRS AND RAMPS SHALL BE
 PROVIDED WITH HANDRAILS ON BOTH SIDES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 12:09 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 12:09 Sent To E
Notes
2005-10-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 15:14 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 15:14 Sent To E
Notes
2005-08-08 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 16:16 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 16:16 Sent To E
Notes
2005-08-03 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-07-15 Cont ID  
Sent By adarroug Date 2005-07-15 Time 16:13 Rev Time 0.00
Received By adarroug Date 2005-07-15 Time 16:13 Sent To E
Notes
2005-07-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 10:28 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 10:28 Sent To E
Notes
2005-07-06 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-19 Cont ID  
Sent By adarroug Date 2005-05-19 Time 14:39 Rev Time 0.00
Received By adarroug Date 2005-05-19 Time 14:39 Sent To B
Notes
2005-05-19 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-30 Cont ID  
Sent By mjacobs Date 2004-12-30 Time 15:24 Rev Time 0.00
Received By mjacobs Date 2004-12-30 Time 15:24 Sent To  
Notes
2004-12-30 00:00:00TO "COMM BD#8

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2004-12-30 Cont ID  
Sent By mjacobs Date 2004-11-17 Time 14:57 Rev Time 0.00
Received By mjacobs Date 2004-11-17 Time 13:03 Sent To  
Notes
2004-11-17 00:00:00SENT TO COMM BD#26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 16:56 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 16:56 Sent To B
Notes
2004-11-12 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-10 Cont ID  
Sent By shill Date 2004-09-16 Time 09:30 Rev Time 0.00
Received By shill Date 2004-08-10 Time 11:42 Sent To  
Notes
2004-08-10 00:00:00TO COMM BD#11

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-09-16 Cont ID  
Sent By pkrauss Date 2004-09-16 Time 14:46 Rev Time 0.25
Received By pkrauss Date 2004-08-30 Time 07:53 Sent To  
Notes
2004-09-16 00:00:00APPROVED 8-30-04

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-11 Cont ID  
Sent By kstevens Date 2004-12-11 Time 16:55 Rev Time 0.80
Received By kstevens Date 2004-12-11 Time 16:55 Sent To  
Notes
2004-12-11 00:00:00PASSED/PROVISO - 606.1(4) VALVES
 REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-09-15 Cont ID  
Sent By kstevens Date 2004-09-15 Time 15:09 Rev Time 1.00
Received By kstevens Date 2004-09-15 Time 15:09 Sent To  
Notes
2004-09-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 PER TABLE 403.1 A SERVICE
 SINK IS REQUIRED.
 2) SUBMIT A DETAIL FOR THE URINAL TO
 SHOW COMPLIANCE WITH SECTION 11-4.18 AND
 ALL SUBSECTIONS.
 3) A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1
 4) SHT A-5 THE SANT. RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN.
 A) THE W/C'S AND LAVS IN THE HANDCAP
 STALLS ARE REVERSED. SHOULD HAVE THE LAV
 ON THE LEFT SIDE OF THE W/C. SECTION
 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-30 Cont ID  
Sent By gjoyce Date 2004-08-30 Time 09:41 Rev Time 0.50
Received By gjoyce Date 2004-08-30 Time 09:40 Sent To  
Notes
***NONE***