Plan Review Details - Permit 04080160
Plan Review Stops For Permit 04080160
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2005-08-04 Cont ID  
Sent By shill Date 2005-08-04 Time 15:06 Rev Time 0.50
Received By shill Date 2005-08-04 Time 15:06 Sent To PC
Notes
2005-08-04 00:00:00****CORRECTIONS****
 FIREPROOFING SUBMITTAL PREPARED BY
 ARDAMAN & ASSOC
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SUBMITTAL APPEARS CODE COMPLIANT.
 PLEASE HAVE REVIEWED BY DOR AND
 RESUBMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-07-21 Cont ID  
Sent By shill Date 2005-07-21 Time 09:18 Rev Time 0.50
Received By shill Date 2005-07-21 Time 09:18 Sent To PC
Notes
2005-07-21 00:00:00SUBMITTAL DATED 7/19

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-07-19 Cont ID  
Sent By shill Date 2005-07-19 Time 13:54 Rev Time 0.50
Received By shill Date 2005-07-19 Time 13:54 Sent To PC
Notes
2005-07-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 REVISION 7/3
  
 1.)PLEASE RESUBMIT PREVIOUS REVISION.
 IMPACT FEES WERE REQUIRED BUT PLANS WERE
 OTHERWISE APPEARED CODE COMPLIANT.
  
 2.)EACH SHEET IS TO BE SIGNED AND
 SEALED UNLESS AN INDEX SHEET IS USED,
 FAC61G1-16.003.A TITLE BLOCK IS ALSO
 REQUIRED ON EACH SHEET.
  
 3.)THE 1 HOUR CEILING DETAIL APPEARS
 CODE COMPLIANT BUT IS DIFFICULT TO
 DETERMINE AS PARTS ARE ILLEGIBLE.
 PLEASE PROVIDE A LEGIBLE COPY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-06-29 Cont ID  
Sent By shill Date 2005-06-29 Time 18:18 Rev Time 0.50
Received By shill Date 2005-06-29 Time 18:18 Sent To FIRE
Notes
2005-06-29 00:00:00****CORRECTIONS****
  
 1.)ADDITIONAL SQUARE FOOTAGE ON SECOND
 FLOOR.IMPACT FEES REQUIRED, 233-5025.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-05-13 Cont ID  
Sent By shill Date 2005-05-13 Time 16:54 Rev Time 2.00
Received By shill Date 2005-05-13 Time 16:54 Sent To  
Notes
2005-05-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IMPACT FEES MAY BE DUE.CALL
 561-233-5025 (ADDITIONAL SQUARE FOOTAGE
 SECOND FLOOR).
  
 2.)FUTURE TENANT SPACE LS1 SHOWS
 EXITING TO A WINDOW.APPROVED PLAN HAD
 A DOOR.
  
 3.)SHEET A4 IS MISSING REV 3 DATED
 12/9/04, SO HAS DETAILS WHICH WERE
 PREVIOUSLY DENIED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-12-13 Cont ID  
Sent By shill Date 2004-12-13 Time 15:09 Rev Time 1.00
Received By shill Date 2004-12-13 Time 15:09 Sent To PC
Notes
2004-12-13 00:00:00REVISED A2, A4, A6, A7 AS PER PROVISO
 DATED 12/10/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-11-19 Cont ID  
Sent By shill Date 2004-11-19 Time 13:19 Rev Time 1.00
Received By shill Date 2004-11-19 Time 13:17 Sent To  
Notes
2004-11-19 00:00:00PROVISO - REVISE A2, A4, A6, A7

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-08 Cont ID  
Sent By shill Date 2004-11-08 Time 08:38 Rev Time 3.00
Received By shill Date 2004-11-08 Time 08:38 Sent To  
Notes
2004-11-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE THE PREVIOUS LIST, ITEM #14.
 PROVIDE TWO ORIGINAL SOILS
 INVESTIGATION
 REPORTS.SIGNED, SEALED ORIGINALS
 REQUIRED FAC61G15-23.002.
  
 2.)SEE ATTACHED MISSILE IMPACT
 PROTECTION STANDARD, ITEM #14.
 REMOVABLE HURRICANE SHUTTERS ARE NOT
 ALLOWED.AS PER CONVERSATION WITH JOE
 COLOME, THE ALTERNATE #2 (SHEET A4) OF
 A SOLID WALL WILL BE USED IN LIEU OF
 WINDOWS.THIS HAS BEEN REDLINED ON THE
 PLAN; REVISION TO BE SUBMITTED BEFORE
 CONCRETE POUR.REVISE SHEETS A2, A4,
 A6, A7.
  
 3.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED FS714 (OVER 90 DAYS WITHOUT
 COMMENCING WORK).PLEASE NOTE THAT THE
 SAME CERTIFIED DOCUMENT CAN BE REFILED
 WITH THE CLERK OF COURTS FOR A NEW
 FILING DATE.
  
 4.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-19 Cont ID  
Sent By shill Date 2004-08-18 Time 10:07 Rev Time 8.00
Received By shill Date 2004-08-18 Time 10:07 Sent To  
Notes
2004-08-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE A COPY OF A RECORDED UNITY
 OF TITLE COMBINING THE TWO LOTS.
 OTHERWISE THE TWO LOTS MUST COMPLY WITH
 FBC TABLE 600 REQUIREMENTS.
  
 2.)PROVIDE DOCUMENTATION SHOWING THE
 ABANDONMENT OF THE EASEMENTS, OR
 PROVIDE EASEMENT RELEASES.
  
 3.)THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS TO BE ON
 EACH SHEET, FAC61G1-23.003,004.
  
 4.)SEPARATE PERMITS REQUIRED.
  
 5.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 6.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 7.)ENERGY CALCS REQUIRED FOR SHELL
 BUILDINGS, FBC13-101.1.6.
  
 8.)THE PLANS SHOW AN OPENING BETWEEN
 THE FIRST FLOOR EXISTING TENANT SPACE
 (107) AND THE FUTURE TENANT SPACE (108).
 IT IS UNCLEAR HOW ENERGY (A/C) NEEDS
 WILL BE ADDRESSED WITH AN OPENING
 BETWEEN CONDITIONED AND UNCONDITIONED
 SPACE.IF THIS OPENING IS CLOSED, IT
 APPEARS THAT TWO EXITS MAY BE REQUIRED
 FOR THE FUTURE TENANT SPACE (108)
 FBC1020.1(4).PLEASE ADDRESS (LS1).
  
 9.)LS1, FUTURE TENANT SPACE (108)
 SHOWS 59' TO A WINDOW.PLEASE REVISE
 TO SHOW EGRESS THROUGH A DOOR.
  
 10.) INDICATE THE FIRE RESISTANCE
 RATING FOR THE EXIT PASSAGEWAY GOING
 FROM EXISTING STAIR (103) TO THE
 OUTSIDE.SHOW OPENING PROTECTIVES,
 INCLUDING WINDOWS ON THE 2ND FLOOR.
 PROVIDE WIDTH OF THE "NEW SIDEWALK".
 PROVIDE SLOPE.THE SIDEWALK IS OFFSET
 FROM THE DOOR; ADDRESS.
  
 11.) EXIT PASSAGEWAYS (FBC1010.3) SHALL
 BE BUILT IN ACCORDANCE WITH FBC1006.1.3.
 3, SHALL NOT BE USED FOR ANY PURPOSE
 OTHER THAN MEANS OF EGRESS.THE
 PASSAGEWAY FROM EXISTING STAIR (103) TO
 THE OUTSIDE (67 FEET) SHOWS MECHANICAL
 AND OTHER EQUIPMENT.ADDRESS.
  
 12.) DOORS 08, 14 ARE TO COMPLY WITH
 MANEUVERING CLEARANCE, FBC11 FIGURE 25.
  
 13.) ADDITIONAL FEES DUE (RADON).
  
 14.) PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 15.) A6, WEST ELEVATION, PROPOSED AND
 EXISTING ARE MISLABELED.
  
 16.)LS1, TABLE 600 DATA, INDICATES
 14% OPENINGS FOR THE WEST WALL.THE
 PARAPET CANNOT BE INCLUDED AS WALL AREA.
  
 17.)INCLUDE THE ROOFTOP MECHANICAL
 UNITS ON THE STRUCTURAL PLAN.PROVIDE
 DESIGN LOAD INFORMATION.THE
 ARCHITECTURALS SHOW A DIFFERENT LOCATION
 FOR RTU#3 THAN THE MECHANICALS.
  
 18.)THE RELOCATED LIGHT POLE IS TO
 COMPLY WITH 140MPH.
  
 19.)SIGNAGE REQUIRED PER FBC704.2.1.4
 IN CORRIDOR PARTITIONS, ETC.
  
 20.)SUBMIT TEST REPORTS FOR THE
 WINDOWS, STOREFRONT SYSTEM, ROOF SYSTEM,
 MULLIONS.FLORDIA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION
 TO TEST REPORT.WWW.FLORIDABUILDING.ORG
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED.PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-05-04 Cont ID  
Sent By dpalmer Date 2005-05-04 Time 15:11 Rev Time 0.00
Received By dpalmer Date 2005-05-04 Time 14:58 Sent To  
Notes
2005-05-04 00:00:00REV'S FOR SHEETS E1,2,3 ONLY.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-19 Cont ID  
Sent By dpalmer Date 2004-11-19 Time 17:13 Rev Time 0.33
Received By dpalmer Date 2004-11-19 Time 17:13 Sent To  
Notes
2004-11-19 00:00:00GENERATOR TO BE REMOVED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-03 Cont ID  
Sent By dpalmer Date 2004-11-03 Time 16:39 Rev Time 1.00
Received By dpalmer Date 2004-11-03 Time 16:19 Sent To  
Notes
2004-11-03 00:00:00****** NOTE ******
  
 ELECTRICAL PLANS ARE ON HOLD AT THIS
 TIME ANDSHALL REMAIN IN FAILED STATUS
 UNTIL POSSIBLE ISSUE WITH LOCATION OF
 EXISITING GENERATOR AND GENERATOR
 EXHAUST.
 GENERATOR LOCATION MAY NEED TO BE MOVED
 TO "OUTSIDE" THE BLDG.
 EVEN WITH GENERATOR BEING EXISTING, THE
 CONDITION IS BEING CREATED BY NEW
 ADDITION AND SHALL ALSO MEET ANY
 REQUIREMENTS FOR CURRENT CODES DUE TO
 ADDITION %'S ETC WHICH FALL UNDER
 REQUIREMENTS OF CHAPTER 34 FBC.
 ARCHITECTUAL SHEETS DO NOT CORRELATE
 WITH ELECTRICAL FOR LAYOUT OF WALK, COND
 UNITS, GENERATOR ETC.
  
 THE LOCATION IS NOW BEING PARTIALLY
 ENCLOSED AND ALSO CONTAINS A REQUIRED
 EGRESS PATH.
 FURTHER CONSULTATION WITH FIRE,
 MEACHANICAL AND BLDG REVIEW WILL BE
 NEEDED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-19 Cont ID  
Sent By dpalmer Date 2004-08-19 Time 09:45 Rev Time 1.00
Received By dpalmer Date 2004-08-19 Time 08:52 Sent To  
Notes
2004-08-19 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SEE PLANS AND APPLICATION
 CALL FOR A NEW TWO-STORY BLDG, HOWEVER
 ONLY ELECTRICAL PLANS FOR SECOND FLR
 LIGHTING AND POWER WERE SUBMITTED?
 PLEASE SEE A MIN LTS ETC FOR LS 101
 MAY BE REQUIRED.
  
 2)NOTE: PLEASE CLARIFY GENERATOR FEED?
 ATS? ETC.
 PLEASE ALSO PROVIDE NOTE FOR SIGNAGE
 PER 230.2E
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE PROVIDE ALL WIND LOAD
 INFORMATION ON EXISTING POLES TO BE
 RELOCATED OR NEW POLES.
 FBC 140 MPH
  
 **PLEASE SEE PLANS ARE NOT COMPLETE AT
 THIS TIME. UABLE TO DO COMPLETE PLAN
 REVIEW.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-05-02 Cont ID  
Sent By mamini Date 2005-05-02 Time 10:42 Rev Time 0.50
Received By mamini Date 2005-05-02 Time 10:41 Sent To  
Notes
2005-05-02 00:00:00PASSED:
  
 1. REVIEWED FOR THE REVISIONS SUBMITTED
 04-19-05.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-08-09 Cont ID  
Sent By mamini Date 2004-08-09 Time 13:49 Rev Time 1.00
Received By mamini Date 2004-08-09 Time 13:49 Sent To  
Notes
2004-08-09 00:00:00PASSED WITH PROVISOS:
 1. ANY WORK WITHIN PUBLIC R.O.W
 REQUIRES A SEPARATE PERMIT FROM PUBLIC
 UTILITIES AND ENGINEERING, WINDEL PALMER
 , 494-1086.
 2. ANY NEW CONNECTION TO THE CITY
 SERVICES, SUCH AS WATER, SEWER REQUIRES
 REVIEW AND APPROVAL FROM PUBLIC UTILITY
 & ENGINEERING, MANNY GONZALEZ,494-1085.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-07-20 Cont ID  
Sent By mwennerg Date 2005-07-20 Time 07:19 Rev Time 0.00
Received By mwennerg Date 2005-07-20 Time 07:19 Sent To  
Notes
2005-07-20 00:00:00REVISION DATED 7/19/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-07-06 Cont ID  
Sent By mwennerg Date 2005-07-06 Time 11:05 Rev Time 0.00
Received By mwennerg Date 2005-07-06 Time 11:05 Sent To  
Notes
2005-07-06 00:00:00REVISION DATED 6/3/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-05-09 Cont ID  
Sent By mwennerg Date 2005-05-09 Time 13:23 Rev Time 0.00
Received By mwennerg Date 2005-05-09 Time 13:23 Sent To  
Notes
2005-05-09 00:00:001) REVISION DATED 4/19/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-11-12 Cont ID  
Sent By lmartine Date 2004-11-12 Time 16:59 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2004-11-12 00:00:00CONVERSATION WITH MIKE AND HAROLD ON
 PHONE, MIKE CONFIRMED OK TO APPROVE
 REVIEW,11/12/04LM

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-09-01 Cont ID  
Sent By mcarsill Date 2004-09-01 Time 15:25 Rev Time 0.00
Received By mcarsill Date 2004-09-01 Time 15:25 Sent To  
Notes
2004-09-01 00:00:001) WILL THE EXISTING SPACE 107, AND NEW
 SPACE 108 CONTAIN THE SAME OR
 DIFFERENT TENANTS.
  
 2) PLEASE EXPLAIN EQUIPMENT CONTAINED
 WITHIN THE EXIT DISCHARGE AREA.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 4) TACTILE SIGNAGE REQUIRED AT EXIT
 DOOR LOCATIONS.
  
 5) PLEASE ILLUSTRATE ALL PORTABLE
 FIRE EXTINGUISHER LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 14:40 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 14:40 Sent To M
Notes
2005-07-28 00:00:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 14:38 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 14:38 Sent To B
Notes
2005-07-28 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 15:27 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 15:27 Sent To M
Notes
2005-07-22 00:00:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-07-15 Cont ID  
Sent By adarroug Date 2005-07-15 Time 11:05 Rev Time 0.00
Received By adarroug Date 2005-07-15 Time 11:05 Sent To B
Notes
2005-07-15 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-07-13 Cont ID  
Sent By shill Date 2005-07-13 Time 14:19 Rev Time 0.00
Received By shill Date 2005-07-13 Time 14:19 Sent To M
Notes
2005-07-13 00:00:00TO HAROLD MOSER'S DESK PER CONTRACTOR
 REQUEST

Review Stop I INCOMING/PROCESSING
Rev No 9 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2005-07-13 Time 14:20 Sent To  
Notes
2005-07-13 00:00:00SUBMITTAL PICKED UP BY CONTR - STILL
 NEEDS FIRE & BUILDING - ROUTED TO FIRE
 BOX

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-07-08 Cont ID  
Sent By adarroug Date 2005-07-08 Time 11:14 Rev Time 0.00
Received By adarroug Date 2005-07-08 Time 11:14 Sent To  
Notes
2005-07-08 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-06-27 Cont ID  
Sent By adarroug Date 2005-06-27 Time 14:48 Rev Time 0.00
Received By adarroug Date 2005-06-27 Time 14:48 Sent To B
Notes
2005-06-27 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 10:30 Rev Time 0.00
Received By shill Date 2005-06-08 Time 10:30 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 17:44 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 17:44 Sent To P
Notes
2005-05-24 00:00:00TO "KSTEVENS" BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 08:41 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 08:41 Sent To  
Notes
2005-05-31 00:00:00MOVED TO BD#1
2005-04-26 00:00:00TO "COMM" BD#62

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-13 Cont ID  
Sent By mjacobs Date 2004-12-13 Time 12:22 Rev Time 0.00
Received By mjacobs Date 2004-12-13 Time 12:22 Sent To B
Notes
2004-12-13 00:00:00SENT TO "SH" DESK./REV.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-27 Cont ID  
Sent By csiegber Date 2004-10-27 Time 15:20 Rev Time 0.00
Received By csiegber Date 2004-10-27 Time 15:20 Sent To  
Notes
2004-10-27 00:00:00TO COMM BD#43

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-01 Cont ID  
Sent By mmclean Date 2004-08-10 Time 14:59 Rev Time 0.00
Received By csiegber Date 2004-08-04 Time 14:28 Sent To  
Notes
2004-08-10 00:00:00TO MM DESK/BROUGHT IN SITE PLAN
2004-08-04 00:00:00TO COMM BD#16

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2005-08-02 Cont ID  
Sent By rregueir Date 2005-08-02 Time 18:11 Rev Time 0.00
Received By rregueir Date 2005-08-02 Time 18:11 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-07-23 Cont ID  
Sent By rregueir Date 2005-07-23 Time 11:39 Rev Time 0.00
Received By rregueir Date 2005-07-23 Time 11:39 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-07-13 Cont ID  
Sent By hmoser Date 2005-07-13 Time 18:17 Rev Time 0.00
Received By hmoser Date 2005-07-13 Time 18:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-07-12 Cont ID  
Sent By prafter Date 2005-07-12 Time 11:06 Rev Time 1.50
Received By prafter Date 2005-07-12 Time 11:06 Sent To  
Notes
2005-07-12 00:00:00MECH. PLAN REVISION 7/7/05.
  
 A/C ENG. PLANS MUST BE CORRECTED TO
 REFLECTED JOB CONDISIONS, AND RESUBMIT
 CORRECTED A/C PLANS.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-01 Cont ID  
Sent By hmoser Date 2005-06-01 Time 18:03 Rev Time 0.00
Received By hmoser Date 2005-06-01 Time 17:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-28 Cont ID  
Sent By pkrauss Date 2004-08-28 Time 09:07 Rev Time 0.55
Received By pkrauss Date 2004-08-28 Time 09:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-11-08 Cont ID  
Sent By pschmitz Date 2005-11-08 Time 14:35 Rev Time 0.00
Received By pschmitz Date 2005-11-08 Time 14:35 Sent To  
Notes
2005-11-08 00:00:00REVISIOM FOR ROOF DRAINS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-06-25 Cont ID  
Sent By pschmitz Date 2005-06-25 Time 09:45 Rev Time 0.00
Received By pschmitz Date 2005-06-25 Time 09:45 Sent To PC
Notes
2005-06-25 00:00:00PLUMBING SHT P-1 ADDED TO ROLL OF PLANS.
 SHOWS ROOF DRAINS AND OVER FLOW DRAINS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-06-02 Cont ID  
Sent By kstevens Date 2005-06-02 Time 10:59 Rev Time 1.25
Received By kstevens Date 2005-06-02 Time 10:59 Sent To  
Notes
2005-06-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW TOTAL SQUARE
 FOOTAGE OF ROOF. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED
 TO SQUARE FOOTAGE OF ROOF IN
 CALCULATIONS. INDICATE TOTAL SQUARE
 FOOTAGE BEING DRAINED BY EACH ROOF
 DRAIN. PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS.
 2. SUBMIT A STORM RISER DIAGRAM SHOWING
 ALL PIPE SIZES, SLOPE OF PIPE & SQUARE
 FOOTAGE DRAINED ON PIPE. SECTION
 104.3.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status N Date 2004-11-09 Cont ID  
Sent By kstevens Date 2004-11-09 Time 12:55 Rev Time 0.52
Received By kstevens Date 2004-11-09 Time 12:55 Sent To  
Notes
2004-11-09 00:00:00NO PLUMBING SHOWN THIS PLAN - ALL
 FIXTURES ARE EXISTING - ONLY WATER
 COOLER TO BE ADDED FOR FUTURE TENANT.
 COMMON TOILET FACILITIES AVAILABLE.
 KSTEVENS

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-19 Cont ID  
Sent By kstevens Date 2004-08-19 Time 17:57 Rev Time 1.00
Received By kstevens Date 2004-08-19 Time 17:57 Sent To  
Notes
2004-08-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A1 FUTURE TENANT SPACE MINIMUM
 FIXTURE REQUIREMENTS 1 WATER CLOSET, 1
 LAV AND 1 DRINKING FOUNTAIN. TAB. 403.1
 2) SHT A2 A DRINKING FOUNTAIN IS REQUIR-
 ED FOR EXIXTING SPACE. TABLE 403.1
 3) SHT A3 CHAPTER 11 ANALYSIS & OVERFLOW
 DETAIL #6 INDICATE 5" DOWNSPOUTS, BUT
 ROOF PLAN INDICATES 4 6"X6" DOWNSPOUTS.
 PLEASE CLARIFY. SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-08-10 Cont ID  
Sent By mmclean Date 2004-08-10 Time 14:59 Rev Time 0.00
Received By mmclean Date 2004-08-10 Time 14:59 Sent To I
Notes
2004-08-10 00:00:00APPROVED BY JOSH LONG, PLANNER 822-1449
 INFORMAL SITEPLAN WAS APPROVED 04-07

Review Stop Z ZONING
Rev No 1 Status F Date 2004-08-05 Cont ID  
Sent By sgraham Date 2004-08-05 Time 10:12 Rev Time 0.00
Received By sgraham Date 2004-08-05 Time 10:12 Sent To  
Notes
2004-08-05 00:00:00NEED A INFORMAL SITE PLAN REVIEW 8-5-04