| Plan Review Stops For Permit 04080160 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
F |
Date |
2005-08-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-04 |
Time |
15:06 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-08-04 |
Time |
15:06 |
Sent To |
PC |
|
| Notes |
| 2005-08-04 00:00:00 | ****CORRECTIONS**** | | | FIREPROOFING SUBMITTAL PREPARED BY | | | ARDAMAN & ASSOC | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)SUBMITTAL APPEARS CODE COMPLIANT. | | | PLEASE HAVE REVIEWED BY DOR AND | | | RESUBMIT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2005-07-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-21 |
Time |
09:18 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-07-21 |
Time |
09:18 |
Sent To |
PC |
|
| Notes |
| 2005-07-21 00:00:00 | SUBMITTAL DATED 7/19 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2005-07-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-19 |
Time |
13:54 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-07-19 |
Time |
13:54 |
Sent To |
PC |
|
| Notes |
| 2005-07-19 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | REVISION 7/3 | | | | | | 1.)PLEASE RESUBMIT PREVIOUS REVISION. | | | IMPACT FEES WERE REQUIRED BUT PLANS WERE | | | OTHERWISE APPEARED CODE COMPLIANT. | | | | | | 2.)EACH SHEET IS TO BE SIGNED AND | | | SEALED UNLESS AN INDEX SHEET IS USED, | | | FAC61G1-16.003.A TITLE BLOCK IS ALSO | | | REQUIRED ON EACH SHEET. | | | | | | 3.)THE 1 HOUR CEILING DETAIL APPEARS | | | CODE COMPLIANT BUT IS DIFFICULT TO | | | DETERMINE AS PARTS ARE ILLEGIBLE. | | | PLEASE PROVIDE A LEGIBLE COPY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2005-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-29 |
Time |
18:18 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-06-29 |
Time |
18:18 |
Sent To |
FIRE |
|
| Notes |
| 2005-06-29 00:00:00 | ****CORRECTIONS**** | | | | | | 1.)ADDITIONAL SQUARE FOOTAGE ON SECOND | | | FLOOR.IMPACT FEES REQUIRED, 233-5025. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2005-05-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-13 |
Time |
16:54 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2005-05-13 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2005-05-13 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)IMPACT FEES MAY BE DUE.CALL | | | 561-233-5025 (ADDITIONAL SQUARE FOOTAGE | | | SECOND FLOOR). | | | | | | 2.)FUTURE TENANT SPACE LS1 SHOWS | | | EXITING TO A WINDOW.APPROVED PLAN HAD | | | A DOOR. | | | | | | 3.)SHEET A4 IS MISSING REV 3 DATED | | | 12/9/04, SO HAS DETAILS WHICH WERE | | | PREVIOUSLY DENIED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2004-12-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-12-13 |
Time |
15:09 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2004-12-13 |
Time |
15:09 |
Sent To |
PC |
|
| Notes |
| 2004-12-13 00:00:00 | REVISED A2, A4, A6, A7 AS PER PROVISO | | | DATED 12/10/04 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-11-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-11-19 |
Time |
13:19 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2004-11-19 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2004-11-19 00:00:00 | PROVISO - REVISE A2, A4, A6, A7 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-11-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-11-08 |
Time |
08:38 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2004-11-08 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2004-11-08 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SEE THE PREVIOUS LIST, ITEM #14. | | | PROVIDE TWO ORIGINAL SOILS | | | INVESTIGATION | | | REPORTS.SIGNED, SEALED ORIGINALS | | | REQUIRED FAC61G15-23.002. | | | | | | 2.)SEE ATTACHED MISSILE IMPACT | | | PROTECTION STANDARD, ITEM #14. | | | REMOVABLE HURRICANE SHUTTERS ARE NOT | | | ALLOWED.AS PER CONVERSATION WITH JOE | | | COLOME, THE ALTERNATE #2 (SHEET A4) OF | | | A SOLID WALL WILL BE USED IN LIEU OF | | | WINDOWS.THIS HAS BEEN REDLINED ON THE | | | PLAN; REVISION TO BE SUBMITTED BEFORE | | | CONCRETE POUR.REVISE SHEETS A2, A4, | | | A6, A7. | | | | | | 3.)THE NOTICE OF COMMENCEMENT IS | | | EXPIRED FS714 (OVER 90 DAYS WITHOUT | | | COMMENCING WORK).PLEASE NOTE THAT THE | | | SAME CERTIFIED DOCUMENT CAN BE REFILED | | | WITH THE CLERK OF COURTS FOR A NEW | | | FILING DATE. | | | | | | 4.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-08-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-08-18 |
Time |
10:07 |
Rev Time |
8.00 |
| Received By |
shill |
Date |
2004-08-18 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2004-08-18 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PROVIDE A COPY OF A RECORDED UNITY | | | OF TITLE COMBINING THE TWO LOTS. | | | OTHERWISE THE TWO LOTS MUST COMPLY WITH | | | FBC TABLE 600 REQUIREMENTS. | | | | | | 2.)PROVIDE DOCUMENTATION SHOWING THE | | | ABANDONMENT OF THE EASEMENTS, OR | | | PROVIDE EASEMENT RELEASES. | | | | | | 3.)THE PRINTED NAME OF THE PERSON | | | SEALING THE DOCUMENT IS TO BE ON | | | EACH SHEET, FAC61G1-23.003,004. | | | | | | 4.)SEPARATE PERMITS REQUIRED. | | | | | | 5.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 6.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE | | | STAMPED AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 FOR MORE | | | INFORMATION. | | | | | | 7.)ENERGY CALCS REQUIRED FOR SHELL | | | BUILDINGS, FBC13-101.1.6. | | | | | | 8.)THE PLANS SHOW AN OPENING BETWEEN | | | THE FIRST FLOOR EXISTING TENANT SPACE | | | (107) AND THE FUTURE TENANT SPACE (108). | | | IT IS UNCLEAR HOW ENERGY (A/C) NEEDS | | | WILL BE ADDRESSED WITH AN OPENING | | | BETWEEN CONDITIONED AND UNCONDITIONED | | | SPACE.IF THIS OPENING IS CLOSED, IT | | | APPEARS THAT TWO EXITS MAY BE REQUIRED | | | FOR THE FUTURE TENANT SPACE (108) | | | FBC1020.1(4).PLEASE ADDRESS (LS1). | | | | | | 9.)LS1, FUTURE TENANT SPACE (108) | | | SHOWS 59' TO A WINDOW.PLEASE REVISE | | | TO SHOW EGRESS THROUGH A DOOR. | | | | | | 10.) INDICATE THE FIRE RESISTANCE | | | RATING FOR THE EXIT PASSAGEWAY GOING | | | FROM EXISTING STAIR (103) TO THE | | | OUTSIDE.SHOW OPENING PROTECTIVES, | | | INCLUDING WINDOWS ON THE 2ND FLOOR. | | | PROVIDE WIDTH OF THE "NEW SIDEWALK". | | | PROVIDE SLOPE.THE SIDEWALK IS OFFSET | | | FROM THE DOOR; ADDRESS. | | | | | | 11.) EXIT PASSAGEWAYS (FBC1010.3) SHALL | | | BE BUILT IN ACCORDANCE WITH FBC1006.1.3. | | | 3, SHALL NOT BE USED FOR ANY PURPOSE | | | OTHER THAN MEANS OF EGRESS.THE | | | PASSAGEWAY FROM EXISTING STAIR (103) TO | | | THE OUTSIDE (67 FEET) SHOWS MECHANICAL | | | AND OTHER EQUIPMENT.ADDRESS. | | | | | | 12.) DOORS 08, 14 ARE TO COMPLY WITH | | | MANEUVERING CLEARANCE, FBC11 FIGURE 25. | | | | | | 13.) ADDITIONAL FEES DUE (RADON). | | | | | | 14.) PROVIDE A SOILS INVESTIGATION | | | REPORT. | | | | | | 15.) A6, WEST ELEVATION, PROPOSED AND | | | EXISTING ARE MISLABELED. | | | | | | 16.)LS1, TABLE 600 DATA, INDICATES | | | 14% OPENINGS FOR THE WEST WALL.THE | | | PARAPET CANNOT BE INCLUDED AS WALL AREA. | | | | | | 17.)INCLUDE THE ROOFTOP MECHANICAL | | | UNITS ON THE STRUCTURAL PLAN.PROVIDE | | | DESIGN LOAD INFORMATION.THE | | | ARCHITECTURALS SHOW A DIFFERENT LOCATION | | | FOR RTU#3 THAN THE MECHANICALS. | | | | | | 18.)THE RELOCATED LIGHT POLE IS TO | | | COMPLY WITH 140MPH. | | | | | | 19.)SIGNAGE REQUIRED PER FBC704.2.1.4 | | | IN CORRIDOR PARTITIONS, ETC. | | | | | | 20.)SUBMIT TEST REPORTS FOR THE | | | WINDOWS, STOREFRONT SYSTEM, ROOF SYSTEM, | | | MULLIONS.FLORDIA STATE OR LOCAL | | | PRODUCT APPROVAL REQUIRED IN ADDITION | | | TO TEST REPORT.WWW.FLORIDABUILDING.ORG | | | | | | WHEN RESUBMITTING, REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED.PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-05-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-04 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-05-04 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2005-05-04 00:00:00 | REV'S FOR SHEETS E1,2,3 ONLY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-11-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-19 |
Time |
17:13 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-11-19 |
Time |
17:13 |
Sent To |
|
|
| Notes |
| 2004-11-19 00:00:00 | GENERATOR TO BE REMOVED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-11-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-03 |
Time |
16:39 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-11-03 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2004-11-03 00:00:00 | ****** NOTE ****** | | | | | | ELECTRICAL PLANS ARE ON HOLD AT THIS | | | TIME ANDSHALL REMAIN IN FAILED STATUS | | | UNTIL POSSIBLE ISSUE WITH LOCATION OF | | | EXISITING GENERATOR AND GENERATOR | | | EXHAUST. | | | GENERATOR LOCATION MAY NEED TO BE MOVED | | | TO "OUTSIDE" THE BLDG. | | | EVEN WITH GENERATOR BEING EXISTING, THE | | | CONDITION IS BEING CREATED BY NEW | | | ADDITION AND SHALL ALSO MEET ANY | | | REQUIREMENTS FOR CURRENT CODES DUE TO | | | ADDITION %'S ETC WHICH FALL UNDER | | | REQUIREMENTS OF CHAPTER 34 FBC. | | | ARCHITECTUAL SHEETS DO NOT CORRELATE | | | WITH ELECTRICAL FOR LAYOUT OF WALK, COND | | | UNITS, GENERATOR ETC. | | | | | | THE LOCATION IS NOW BEING PARTIALLY | | | ENCLOSED AND ALSO CONTAINS A REQUIRED | | | EGRESS PATH. | | | FURTHER CONSULTATION WITH FIRE, | | | MEACHANICAL AND BLDG REVIEW WILL BE | | | NEEDED. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-08-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-19 |
Time |
09:45 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-08-19 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2004-08-19 00:00:00 | *********** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE PLANS AND APPLICATION | | | CALL FOR A NEW TWO-STORY BLDG, HOWEVER | | | ONLY ELECTRICAL PLANS FOR SECOND FLR | | | LIGHTING AND POWER WERE SUBMITTED? | | | PLEASE SEE A MIN LTS ETC FOR LS 101 | | | MAY BE REQUIRED. | | | | | | 2)NOTE: PLEASE CLARIFY GENERATOR FEED? | | | ATS? ETC. | | | PLEASE ALSO PROVIDE NOTE FOR SIGNAGE | | | PER 230.2E | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 4)NOTE: PLEASE PROVIDE ALL WIND LOAD | | | INFORMATION ON EXISTING POLES TO BE | | | RELOCATED OR NEW POLES. | | | FBC 140 MPH | | | | | | **PLEASE SEE PLANS ARE NOT COMPLETE AT | | | THIS TIME. UABLE TO DO COMPLETE PLAN | | | REVIEW. | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | WHICH MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW SHEETS INTO TWO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2005-05-02 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-05-02 |
Time |
10:42 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2005-05-02 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2005-05-02 00:00:00 | PASSED: | | | | | | 1. REVIEWED FOR THE REVISIONS SUBMITTED | | | 04-19-05. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2004-08-09 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-08-09 |
Time |
13:49 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2004-08-09 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2004-08-09 00:00:00 | PASSED WITH PROVISOS: | | | 1. ANY WORK WITHIN PUBLIC R.O.W | | | REQUIRES A SEPARATE PERMIT FROM PUBLIC | | | UTILITIES AND ENGINEERING, WINDEL PALMER | | | , 494-1086. | | | 2. ANY NEW CONNECTION TO THE CITY | | | SERVICES, SUCH AS WATER, SEWER REQUIRES | | | REVIEW AND APPROVAL FROM PUBLIC UTILITY | | | & ENGINEERING, MANNY GONZALEZ,494-1085. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-20 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-20 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2005-07-20 00:00:00 | REVISION DATED 7/19/05 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-07-06 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-06 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-06 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2005-07-06 00:00:00 | REVISION DATED 6/3/05 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-05-09 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-05-09 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2005-05-09 00:00:00 | 1) REVISION DATED 4/19/05 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2004-11-12 |
Time |
16:59 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2004-11-12 00:00:00 | CONVERSATION WITH MIKE AND HAROLD ON | | | PHONE, MIKE CONFIRMED OK TO APPROVE | | | REVIEW,11/12/04LM |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-09-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-09-01 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-09-01 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2004-09-01 00:00:00 | 1) WILL THE EXISTING SPACE 107, AND NEW | | | SPACE 108 CONTAIN THE SAME OR | | | DIFFERENT TENANTS. | | | | | | 2) PLEASE EXPLAIN EQUIPMENT CONTAINED | | | WITHIN THE EXIT DISCHARGE AREA. | | | | | | 3) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 4) TACTILE SIGNAGE REQUIRED AT EXIT | | | DOOR LOCATIONS. | | | | | | 5) PLEASE ILLUSTRATE ALL PORTABLE | | | FIRE EXTINGUISHER LOCATIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-28 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-28 |
Time |
14:40 |
Sent To |
M |
|
| Notes |
| 2005-07-28 00:00:00 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-28 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-28 |
Time |
14:38 |
Sent To |
B |
|
| Notes |
| 2005-07-28 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2005-07-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-22 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-22 |
Time |
15:27 |
Sent To |
M |
|
| Notes |
| 2005-07-22 00:00:00 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2005-07-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-15 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-15 |
Time |
11:05 |
Sent To |
B |
|
| Notes |
| 2005-07-15 00:00:00 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2005-07-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-13 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-07-13 |
Time |
14:19 |
Sent To |
M |
|
| Notes |
| 2005-07-13 00:00:00 | TO HAROLD MOSER'S DESK PER CONTRACTOR | | | REQUEST |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-07-13 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2005-07-13 00:00:00 | SUBMITTAL PICKED UP BY CONTR - STILL | | | NEEDS FIRE & BUILDING - ROUTED TO FIRE | | | BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-07-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-08 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-08 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2005-07-08 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-06-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-06-27 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-06-27 |
Time |
14:48 |
Sent To |
B |
|
| Notes |
| 2005-06-27 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-06-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-08 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-08 |
Time |
10:30 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-05-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-24 |
Time |
17:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-24 |
Time |
17:44 |
Sent To |
P |
|
| Notes |
| 2005-05-24 00:00:00 | TO "KSTEVENS" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-04-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-26 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-26 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2005-05-31 00:00:00 | MOVED TO BD#1 | | 2005-04-26 00:00:00 | TO "COMM" BD#62 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-12-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-13 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-13 |
Time |
12:22 |
Sent To |
B |
|
| Notes |
| 2004-12-13 00:00:00 | SENT TO "SH" DESK./REV. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-10-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-27 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-27 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2004-10-27 00:00:00 | TO COMM BD#43 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-09-01 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-08-10 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-04 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2004-08-10 00:00:00 | TO MM DESK/BROUGHT IN SITE PLAN | | 2004-08-04 00:00:00 | TO COMM BD#16 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2005-08-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2005-08-02 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2005-08-02 |
Time |
18:11 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2005-07-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2005-07-23 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2005-07-23 |
Time |
11:39 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2005-07-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-07-13 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-07-13 |
Time |
18:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2005-07-12 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-07-12 |
Time |
11:06 |
Rev Time |
1.50 |
| Received By |
prafter |
Date |
2005-07-12 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2005-07-12 00:00:00 | MECH. PLAN REVISION 7/7/05. | | | | | | A/C ENG. PLANS MUST BE CORRECTED TO | | | REFLECTED JOB CONDISIONS, AND RESUBMIT | | | CORRECTED A/C PLANS. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-06-01 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-06-01 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-06-01 |
Time |
17:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-08-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-08-28 |
Time |
09:07 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2004-08-28 |
Time |
09:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2005-11-08 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-11-08 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-11-08 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2005-11-08 00:00:00 | REVISIOM FOR ROOF DRAINS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-06-25 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-06-25 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-06-25 |
Time |
09:45 |
Sent To |
PC |
|
| Notes |
| 2005-06-25 00:00:00 | PLUMBING SHT P-1 ADDED TO ROLL OF PLANS. | | | SHOWS ROOF DRAINS AND OVER FLOW DRAINS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-06-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-02 |
Time |
10:59 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2005-06-02 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2005-06-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. SUBMIT CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS. SHOW TOTAL SQUARE | | | FOOTAGE OF ROOF. SHOW 1/2 AREA OF ALL | | | VERTICAL WALLS INCLUDING PARAPETS ADDED | | | TO SQUARE FOOTAGE OF ROOF IN | | | CALCULATIONS. INDICATE TOTAL SQUARE | | | FOOTAGE BEING DRAINED BY EACH ROOF | | | DRAIN. PER SECTIONS 1106 & 1107 AND ALL | | | SUBSECTIONS. | | | 2. SUBMIT A STORM RISER DIAGRAM SHOWING | | | ALL PIPE SIZES, SLOPE OF PIPE & SQUARE | | | FOOTAGE DRAINED ON PIPE. SECTION | | | 104.3.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2004-11-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-09 |
Time |
12:55 |
Rev Time |
0.52 |
| Received By |
kstevens |
Date |
2004-11-09 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2004-11-09 00:00:00 | NO PLUMBING SHOWN THIS PLAN - ALL | | | FIXTURES ARE EXISTING - ONLY WATER | | | COOLER TO BE ADDED FOR FUTURE TENANT. | | | COMMON TOILET FACILITIES AVAILABLE. | | | KSTEVENS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-08-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-08-19 |
Time |
17:57 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-08-19 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2004-08-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A1 FUTURE TENANT SPACE MINIMUM | | | FIXTURE REQUIREMENTS 1 WATER CLOSET, 1 | | | LAV AND 1 DRINKING FOUNTAIN. TAB. 403.1 | | | 2) SHT A2 A DRINKING FOUNTAIN IS REQUIR- | | | ED FOR EXIXTING SPACE. TABLE 403.1 | | | 3) SHT A3 CHAPTER 11 ANALYSIS & OVERFLOW | | | DETAIL #6 INDICATE 5" DOWNSPOUTS, BUT | | | ROOF PLAN INDICATES 4 6"X6" DOWNSPOUTS. | | | PLEASE CLARIFY. SECTION 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2004-08-10 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-08-10 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-08-10 |
Time |
14:59 |
Sent To |
I |
|
| Notes |
| 2004-08-10 00:00:00 | APPROVED BY JOSH LONG, PLANNER 822-1449 | | | INFORMAL SITEPLAN WAS APPROVED 04-07 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-08-05 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2004-08-05 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2004-08-05 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2004-08-05 00:00:00 | NEED A INFORMAL SITE PLAN REVIEW 8-5-04 |
|
|