Plan Review Details - Permit 04080151
Plan Review Stops For Permit 04080151
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-08 Cont ID  
Sent By shill Date 2005-03-08 Time 17:43 Rev Time 0.50
Received By shill Date 2005-03-08 Time 17:42 Sent To  
Notes
2005-03-08 00:00:00REVISED A1, A2, A3, A4, A6 DATED 2/21/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-16 Cont ID  
Sent By shill Date 2004-11-16 Time 10:30 Rev Time 1.00
Received By shill Date 2004-11-16 Time 10:30 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-17 Cont ID  
Sent By shill Date 2004-08-17 Time 14:14 Rev Time 2.00
Received By shill Date 2004-08-17 Time 14:14 Sent To  
Notes
2004-08-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE SEAL ON THE ARCHITECTURAL AND
 SPEC SHEETS IS ILLEGIBLE.PLEASE RESEAL
 THE DRAWINGS.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)SEPARATE PERMITS REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-23 Cont ID  
Sent By dpalmer Date 2004-10-23 Time 10:51 Rev Time 0.33
Received By dpalmer Date 2004-10-23 Time 10:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-12 Cont ID  
Sent By dpalmer Date 2004-08-12 Time 09:53 Rev Time 0.50
Received By dpalmer Date 2004-08-12 Time 09:53 Sent To  
Notes
2004-08-12 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE INCLUDE ALL REQUIRED
 LICENSE #'S ON TITLE BLOCK.
 FS 471.023, FAC 61G15-23.002
 THIS IS REQUIRED FOR ALL SHEETS/TRADES
 WHEATHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-11-05 Cont ID  
Sent By mcarsill Date 2004-11-05 Time 15:55 Rev Time 0.00
Received By mcarsill Date 2004-11-05 Time 15:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-09-15 Cont ID  
Sent By mcarsill Date 2004-09-15 Time 15:25 Rev Time 0.00
Received By mcarsill Date 2004-09-15 Time 15:25 Sent To  
Notes
2004-09-15 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-07-01 Cont ID  
Sent By pkrauss Date 2005-07-01 Time 09:01 Rev Time 0.00
Received By pkrauss Date 2005-07-01 Time 09:01 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 13:14 Rev Time 0.00
Received By shill Date 2005-06-20 Time 13:14 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-05 Cont ID  
Sent By adarroug Date 2005-04-29 Time 10:49 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 17:04 Sent To M
Notes
2005-05-03 00:00:00TO "PKRAUSS" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-02-24 Cont ID  
Sent By adarroug Date 2005-02-24 Time 13:38 Rev Time 0.00
Received By adarroug Date 2005-02-24 Time 13:38 Sent To P
Notes
2005-02-24 00:00:00TO KSTEVENS BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 15:36 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 15:36 Sent To  
Notes
2005-02-22 00:00:00TO "COMM" BD#44

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 13:10 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 13:10 Sent To M
Notes
2005-02-15 00:00:00TO "M" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-08 Cont ID  
Sent By adarroug Date 2005-02-08 Time 10:04 Rev Time 0.00
Received By adarroug Date 2005-02-08 Time 10:04 Sent To P
Notes
2005-02-08 00:00:00TO "P" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-18 Cont ID  
Sent By csiegber Date 2004-10-18 Time 17:43 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 17:43 Sent To  
Notes
2004-11-12 00:00:0011/12/04 TAKEN OFF COMM BD GIVEN TO SH
 FOR HER REVIEW
2004-10-18 00:00:00TO COMM BD#56

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 16:12 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 16:12 Sent To  
Notes
2004-08-03 00:00:00TO COMM BD#50

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2005-10-05 Cont ID  
Sent By hmoser Date 2005-10-05 Time 09:56 Rev Time 0.00
Received By hmoser Date 2005-10-05 Time 09:56 Sent To  
Notes
2005-10-05 00:00:0010/05/05 RESTAMP

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2005-09-30 Cont ID  
Sent By rregueir Date 2005-09-30 Time 07:35 Rev Time 0.00
Received By rregueir Date 2005-09-30 Time 07:35 Sent To PC
Notes
2005-09-30 00:00:00---------------DENIED-------------------
  
 2 SETS OF PLANS SUBMITTED FOR RESTAMP.
 COPIES DO NOT MATCH EACH OTHER, ONLY ONE
 IS STAMPED BY ENGINEER, BOTH HAVE BEEN
 MODIFIED WITH PEN.PLEASE SUBMIT
 MATCHING COPIES, BOTH SIGNED/STAMPED BY
 ENGINEER AND UNMODIFIED BY OTHER THAN
 THE ENGINEER.
  
 RONALD J REGUEIRO
 561.805.6734

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2005-07-01 Cont ID  
Sent By pkrauss Date 2005-07-01 Time 09:01 Rev Time 0.35
Received By pkrauss Date 2005-07-01 Time 09:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-06-22 Cont ID  
Sent By hmoser Date 2005-06-22 Time 15:02 Rev Time 0.00
Received By hmoser Date 2005-06-22 Time 15:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-05-05 Cont ID  
Sent By pkrauss Date 2005-05-05 Time 11:10 Rev Time 0.40
Received By pkrauss Date 2005-05-05 Time 11:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2005-03-24 Time   Rev Time 0.00
Received By hmoser Date 2005-03-24 Time 17:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-10-26 Cont ID  
Sent By pkrauss Date 2004-10-26 Time 07:24 Rev Time 0.00
Received By prafter Date 2005-02-17 Time 10:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-28 Cont ID  
Sent By pkrauss Date 2004-08-28 Time 11:12 Rev Time 0.55
Received By pkrauss Date 2004-08-28 Time 10:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-03-09 Cont ID  
Sent By kstevens Date 2005-03-09 Time 17:57 Rev Time 0.75
Received By kstevens Date 2005-03-05 Time 16:10 Sent To  
Notes
2005-03-09 00:00:00REVISION OK - ADD SINK WITH PIPING

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-02-23 Cont ID  
Sent By kstevens Date 2005-02-23 Time 06:28 Rev Time 0.75
Received By kstevens Date 2005-02-22 Time 18:36 Sent To  
Notes
2005-02-23 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-1 REVISION FOR SANITARY RISER
 DIAGRAM SHOWS NO CHANGES FROM STAMPED
 SET REVIEWED 11-5-4. PLEASE CLARIFY.
 SECTION 104.2.1.
 2) SHT P-2 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE PIPING SHOWN ON THE
 FLOOR PLAN SHT P-1. PLEASE CORRELATE THE
 FLOOR PLAN AND THE SANT. RISER DIAGRAM.
 SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-11-05 Cont ID  
Sent By kstevens Date 2004-11-05 Time 17:50 Rev Time 0.75
Received By kstevens Date 2004-11-05 Time 17:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-09-15 Cont ID  
Sent By kstevens Date 2004-09-15 Time 08:17 Rev Time 1.00
Received By kstevens Date 2004-09-15 Time 08:16 Sent To  
Notes
2004-09-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT D-1 DEMO NOTES "N" AND DEMO KEYS
 "11" IN THE INSTALLATION OR REMOVAL OF
 ANY PARY OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED.
 2) SHT A-1 SECTION 403.2 WHERE PLUMBING
 FIXTURES ARE REQUIRED, SEPARATE FACILIT-
 IES SHALL BE PROVIDED FOR EACH SEX.
 3) SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 FOR THE DRINKING FOUNTAIN.
 4) SHT P-1 PLUMBING NOTES #13 AIR CHAMB-
 ERS ARE NOT APPROVED. DELETE FROM REFER-
 ENCE.
 5)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025 - NO CERT-
 IFICATE OF AUTHORIZATION SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]