Plan Review Details - Permit 04080139
Plan Review Stops For Permit 04080139
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-03 Cont ID  
Sent By shill Date 2005-03-03 Time 09:34 Rev Time 1.00
Received By shill Date 2005-03-03 Time 09:34 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-02-03 Cont ID  
Sent By shill Date 2005-02-03 Time 09:53 Rev Time 0.50
Received By shill Date 2005-02-03 Time 09:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-12-01 Cont ID  
Sent By shill Date 2004-12-01 Time 15:03 Rev Time 0.00
Received By shill Date 2004-12-01 Time 15:03 Sent To  
Notes
2004-12-01 00:00:00***NOT A REVIEW***
 SUBMITTAL - DEED SHOWING CURRENT OWNER,
 ORCHID RESERVE, OR BK 14613/1560

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-22 Cont ID  
Sent By shill Date 2004-11-22 Time 11:21 Rev Time 0.50
Received By shill Date 2004-11-22 Time 11:21 Sent To PC
Notes
2004-11-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE DEED PROVIDED IS FOR PARCELS C
 AND D; PLEASE PROVIDE PROOF OF
 OWNERSHIP
 FOR TRACT L (FROM PREVIOUS LIST ITEM
 #1).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-08-19 Time 16:42 Rev Time 0.00
Received By shill Date 2004-08-19 Time 15:16 Sent To  
Notes
2004-08-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE PROOF OF OWNERSHIP.OUR
 RECORDS SHOW E SUTTIN AS THE OWNER;
 THE APPLICATION STATES VINTAGE
 PROPERTIES.SEE ATTACHED.
  
 2.)PLEASE REMOVE THE TRUSS DRAWINGS
 FROM US TRUSS FROM THE PACKAGE.THIS
 INFORMATION IS ALREADY CONTAINED IN
 THE PLAN; OR SEAL THE TRUSS DRAWINGS.
  
 3.)SHEET C1, LOAD SCHEDULE, INDICATES
 THE BUILDING DESIGN AS ENCLOSED.THIS
 APPEARS TO THE WRONG ENCLOSURE CATEGORY.
 ALSO THIS SHEET DECLARES THE STRUCTURE
 AS A SINGLE FAMILY RESIDENCE. PLEASE
 REVISE.
  
 4.)A3, SECTION REFERS TO DETAIL 2/A-1
 FOR THE ARCHED PLYWD SOFFIT W/STUCCO
 FINISH.THIS DETAIL IS NOT ON THE
 PLAN.
  
 5.)PROVIDE ELEVATIONS FOR THE ACCESS
 TO THE MAIL CENTER.THIS BUILDING
 MUST BE ACCESSIBLE AND COMPLY WITH
 THE REQUIREMENTS OF FBC CHAPTER 11.
 SHOW COMPLIANCE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-02-23 Cont ID  
Sent By dpalmer Date 2005-02-23 Time 13:52 Rev Time 0.30
Received By dpalmer Date 2005-02-23 Time 13:52 Sent To B
Notes
2005-02-23 00:00:00ELEC OK,
 SENT TO BLDG FOR PROCESSING.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-02-01 Cont ID  
Sent By dpalmer Date 2005-02-01 Time 15:02 Rev Time 0.30
Received By dpalmer Date 2005-02-01 Time 14:50 Sent To  
Notes
2005-02-01 00:00:00********* UNSAT 3RD REVIEW*******
  
 PLEASE SEE NOTES 3 AND 4 FROM PREVIOUS
 REVIEW.
  
  
 1)NOTE: NOTE #3, PLEASE SEE MISSING
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 DISC TO PANEL.
 250.24,250.110,250.122
  
 2)NOTE: PLEASE SEE MISSING MEANS OF DISC
 AT DETACHED STRUCTURE PER 225.31.
  
 ** OWES RESUB FEE FOR THIS RESUB.
 ** WILL ALSO OWE RESUB FOR NEXT RESUB.
  
  
 PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B). THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-15 Cont ID  
Sent By dpalmer Date 2004-11-15 Time 07:29 Rev Time 0.30
Received By dpalmer Date 2004-11-15 Time 07:23 Sent To  
Notes
2004-11-15 00:00:00*** UNSAT ***
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASECLARIFY IF ALUM LT POLES
 SHOWN ON PLANS ARE INCLUDED ON THIS
 PERMIT AND SCOPE OF WORK. IF THEY ARE
 INCLUDED, PLEASE INCLUDE WIND LOADING
 FOR FBC 140 MPH
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISC TO
 PANEL. 250.24,250.122
  
 4)NOTE: PLEASE NOTE: IF ELECTRICAL
 DEVICES/LOADS WILL BE ON MAIL KIOSK,
 THEN A MEANS OF DISC WILL BE REQUIRED.
 225.31 PLANS ONLY MENTIONS A J-BOX AT
 THIS TIME.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-10 Cont ID  
Sent By dpalmer Date 2004-08-10 Time 13:35 Rev Time 0.25
Received By dpalmer Date 2004-08-10 Time 13:35 Sent To  
Notes
2004-08-10 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE NOT ENOUGH ELECTRICAL
 INFORAMTION WAS SUBMITTED FOR REVIEW.
 PLAN ONLY INDICATES TWO LT FIXTURES ON
 WALL?
 IS THERE LIGHTING ETC AT MAILBOX/BLDG/
 SHELTER?
 PLEASE SEE 225.31 FOR MEANS OF DISC.
  
 PLEASE SHOW CIRCUIT(S), POWER FEED,
 (CONCUITS AND CONDUCTORS) AND FROM WHERE
 ?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 16:36 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 16:36 Sent To E
Notes
2005-02-14 00:00:00TO DPALMER DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 07:59 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 07:59 Sent To  
Notes
2005-01-31 00:00:00TO "COMM BD#14/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-04 Cont ID  
Sent By csiegber Date 2004-11-04 Time 13:18 Rev Time 0.00
Received By csiegber Date 2004-11-04 Time 13:18 Sent To  
Notes
2004-11-04 00:00:00TO COMM BD#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-19 Time 16:42 Rev Time 0.00
Received By shill Date 2004-08-03 Time 16:42 Sent To  
Notes
2004-08-03 00:00:00TO COMM BD#57

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-10 Cont ID  
Sent By gjoyce Date 2004-08-10 Time 10:36 Rev Time 1.00
Received By gjoyce Date 2004-08-10 Time 10:36 Sent To  
Notes
***NONE***