Plan Review Details - Permit 04080129
Plan Review Stops For Permit 04080129
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-04-08 Cont ID  
Sent By jwitmer Date 2005-04-08 Time 10:50 Rev Time 0.00
Received By jwitmer Date 2005-04-08 Time 10:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-19 Cont ID  
Sent By jwitmer Date 2004-08-19 Time 14:16 Rev Time 2.22
Received By jwitmer Date 2004-08-19 Time 11:11 Sent To  
Notes
2004-08-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04080129
 ADD: 610 CLEMATIS ST
 CONT: SUPERIOR POOL & SPA
 TEL: (954)520-3368
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 COMMERCIAL POOL
  
 1) 412.1.ABCD.2.4.2 COVERS REQUIRED.
 SPAS AND HEATED POOLS SHALL BE EQUIPPED
 WITH A COVER DESIGNED TO MINIMIZE HEAT
 LOSS.
  
 2) 412.1.ABCD.3.5 POOL AND SPA HEATERS.
 ALL GAS AND OIL FIRED POOL HEATERS WHEN
 TESTED IN ACCORDANCE WITH ANSI Z21.56-
 1989 SHALL HAVE A NINIMUM THERMAL
 EFFICIENCY OF 78 PERCENT.
  
 3) PROVIDE INFORMATION ON THE CONCRETE
 FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE SIZE (CLEAR AREA) OF THE
 CONCRETE VENT IN THE POOL PUMP ROOM.
 EQUIPMENT LOCATED IN CONFINED SPACES.
  
 4)POOL PLAN SHEET 9 OF 10 "DEPTH MARKING
 DETAIL, INDICATES WHERE THE DEPTH MARKER
 SHALL BE PLACED IN THE POOL,
 424.1.2.3.1(2) THE MAXIMUM PERIMETER
 BETWEEN MARKINGS OF 25' AND SHALL BE
 LEGIBLE FROM INSIDE THE POOL AND ALSO
 FROM THE POOL DECK.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-03-14 Cont ID  
Sent By dpalmer Date 2005-03-14 Time 15:31 Rev Time 0.50
Received By dpalmer Date 2005-03-14 Time 15:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-10 Cont ID  
Sent By dpalmer Date 2004-08-10 Time 09:54 Rev Time 0.25
Received By dpalmer Date 2004-08-10 Time 09:54 Sent To  
Notes
2004-08-10 00:00:00********* UNSAT**********
  
 1)NOTE: PLEASE SUBMIT A WIRING DIAGRAM
 FOR ALL EQUIPMENT/PUMPS/LTS ETC.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2005-05-26 Cont ID  
Sent By adarroug Date 2005-05-03 Time 13:19 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 13:19 Sent To  
Notes
2005-05-26 00:00:00TO "COMM" BD#30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 15:53 Rev Time 0.00
Received By adarroug Date   Time   Sent To  
Notes
2005-03-09 00:00:00TO "COMM" BD#43

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 16:17 Sent To  
Notes
2004-08-03 00:00:00TO COMM BD#61

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-08-30 Cont ID  
Sent By pkrauss Date 2004-08-30 Time 09:11 Rev Time 0.45
Received By pkrauss Date 2004-08-30 Time 09:11 Sent To  
Notes
2004-08-30 00:00:00PLEASE INDICATE IF THE VENTILATION FOR
 THE POOL EQUIPMENT ROOM WAS ADDRESSED
 ON THE BUILDING PERMIT.REFERENCE
 PLAN SHEET WITH SUBMITTAL.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-05-26 Cont ID  
Sent By kstevens Date 2005-05-26 Time 13:25 Rev Time 1.00
Received By kstevens Date 2005-05-26 Time 13:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-22 Cont ID  
Sent By kstevens Date 2005-03-22 Time 17:39 Rev Time 0.64
Received By kstevens Date 2005-03-22 Time 17:39 Sent To  
Notes
2005-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 424 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 A) FROM PREVIOUS REVIEW:
 2) OVERFLOW FROM COLLECTOR TANKS SHALL
 DRAIN INTO STORM. - POOL PLANS INDICATE
 THAT OVERFLOW WILL DRAIN TO SANITARY ON
 SHEETS 7 & 8 OF 10.
 ***************NEW COMMENTS************
 1B) POOL PLANS ARE NOT COMPLETE, SHEETS
 2, 4, 7, 8 & 10 OF 10 WERE MISSING FROM
 ONE SET OF POOL PLANS SUBMITTED.
 2B) PLUMBING SHEETS SUBMITTED WITH THE
 POOL, SPA, AND FOUNTAIN PLANS SHALL BE
 SUBMITTED AS A REVISION UNDER THE
 BLD-COM PERMIT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-09-14 Cont ID  
Sent By kstevens Date 2004-09-14 Time 15:41 Rev Time 1.00
Received By kstevens Date 2004-09-14 Time 15:41 Sent To  
Notes
2004-09-14 00:00:00DENIED
 REFERENCE: FBC-2001 424 SWIMMING POOLS
  
 1) SECTION 424.1.6.5.14 THERMOSTAT REQ-
 UIRED ON HEATER RETURN LINE. SHEET 7
 2) OVERFLOW FROM COLLECTOR TANKS SHALL
 DRAIN INTO STORM.
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2005-06-02 Cont ID  
Sent By aaponte Date 2005-06-02 Time 15:55 Rev Time 0.00
Received By aaponte Date 2005-06-02 Time 15:55 Sent To  
Notes
***NONE***