Plan Review Details - Permit 04080107
Plan Review Stops For Permit 04080107
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status N Date 2005-06-15 Cont ID  
Sent By shill Date 2005-06-15 Time 11:11 Rev Time 0.00
Received By shill Date 2005-06-15 Time 11:11 Sent To  
Notes
2005-06-15 00:00:00ONLY ONE A SHEET SUBMITTED, ALREADY
 REVIEWED, RETURNED TO CONTRACTOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-06-03 Cont ID  
Sent By shill Date 2005-06-03 Time 10:40 Rev Time 0.50
Received By shill Date 2005-06-01 Time 16:35 Sent To PC
Notes
2005-06-03 00:00:00REV #4, A1 2/17/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-12-14 Cont ID  
Sent By shill Date 2004-12-14 Time 17:43 Rev Time 0.00
Received By shill Date 2004-12-14 Time 17:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-12-09 Cont ID  
Sent By shill Date 2004-12-09 Time 07:36 Rev Time 1.00
Received By shill Date 2004-12-09 Time 07:36 Sent To  
Notes
2004-12-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLEASE SEE PREVIOUS LIST, ITEM #1.
 SHEET A.1, KEY NOTE 14 SHOWS THE HWH IN
 THE CEILING.PROVIDE A STRUCTURAL
 DETAIL, INCLUDING DESIGN LOAD
 INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-03 Cont ID  
Sent By shill Date 2004-11-03 Time 15:14 Rev Time 1.00
Received By shill Date 2004-11-03 Time 15:14 Sent To PC
Notes
2004-11-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SHEET A.1, KEY NOTE 14 SHOWS THE
 HWH IN THE CEILING.PROVIDE A
 STRUCTURAL DETAIL, INCLUDING DESIGN
 LOAD
 INFORMATION.
  
 2.)SHEET P-1, ITEM 14 STILL SHOWS THE
 HWH AS UNDER THE CABINET.THIS IS
 INCONSISTENT WITH THE LANGUAGE ON A.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-08-19 Cont ID  
Sent By shill Date 2004-08-19 Time 14:53 Rev Time 2.00
Received By shill Date 2004-08-19 Time 11:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-06-23 Cont ID  
Sent By dpalmer Date 2005-06-23 Time 10:03 Rev Time 0.30
Received By dpalmer Date 2005-06-23 Time 10:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 12:21 Rev Time 0.50
Received By dpalmer Date 2005-06-13 Time 12:21 Sent To B
Notes
2005-06-13 00:00:00*********** UNSAT *************
  
 1)NOTE: PLEASE SEE MAIN DISC ATTACHED TO
 BUS-DUCT CHENGED FROM ORIG PLANS AS 800A
 DOWN TO 200A'S.
 PLEASE SEE PLANS/LOAD CALCULATIONS STILL
 SHOW THIS AS 800A'S??
  
 2)NOTE: PLEASE VERIFY ENGINEER NOW
 SIGNING PLANS.
 PLEASE SEE ORIGINAL ENGINEER OF RECORD
 IS NOT THE SAME AS INDICATED ON PLANS.
 PLEASE SEE TITLE BLOCK NOTES ENGINEER AS
 THE MECH ENG??
 FS 471.025
  
  
 NO OTHER REVISIONS INDICATED/NOTED.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-18 Cont ID  
Sent By dpalmer Date 2004-11-18 Time 16:31 Rev Time 0.25
Received By dpalmer Date 2004-11-18 Time 16:31 Sent To  
Notes
2004-11-18 00:00:00PASSED ON PREVIOUS REVIEW.
 NO NEW SHEETS FOUND.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-05 Cont ID  
Sent By dpalmer Date 2004-10-05 Time 18:07 Rev Time 0.25
Received By dpalmer Date 2004-10-05 Time 18:06 Sent To  
Notes
2004-10-05 00:00:00OLD/VOIDED SHEETS NOT REMOVED FROM SETS
 AS REQUESTED ON PREVIOUS REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-12 Cont ID  
Sent By dpalmer Date 2004-08-12 Time 09:10 Rev Time 0.75
Received By dpalmer Date 2004-08-12 Time 08:44 Sent To  
Notes
2004-08-12 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE EM LTS SHOWN AS
 FIXTURE TYPE "EM" APPEAR TO BE SWICTHED?
 PLEASE SEE CIRCUIT #H10
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS.
  
 2 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE VERIFY LOAD ON EXISTING 800A BUS
 DISC.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS MAY BE SUBMITTED
 FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2004-12-14 Cont ID  
Sent By shill Date 2004-12-14 Time 13:08 Rev Time 0.00
Received By shill Date 2004-12-14 Time 13:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-09-01 Cont ID  
Sent By mcarsill Date 2004-09-01 Time 15:22 Rev Time 0.00
Received By mcarsill Date 2004-09-01 Time 15:22 Sent To  
Notes
2004-09-01 00:00:001) OXYGEN IS TO BE STORED AND HANDLED
 AND USED IN ACCORDANCE WITH APPLICABLE
 REQUIREMENTS.
  
 2) OXYGEN CLOSET IS TO BE FIRE
 SPRINKLER PROTECTED.
  
 3) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 08:46 Rev Time 0.00
Received By shill Date 2005-06-20 Time 08:46 Sent To E
Notes
2005-06-20 00:00:00TO DVP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 13:35 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 13:35 Sent To B
Notes
2005-05-31 00:00:00TO "SHILL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-14 Cont ID  
Sent By shill Date 2004-12-14 Time 13:09 Rev Time 0.00
Received By shill Date 2004-12-14 Time 13:09 Sent To P
Notes
2004-12-14 00:00:00TO KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 11:12 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 11:12 Sent To  
Notes
2004-11-12 00:00:00TO COMM BD#36

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 12:06 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 12:06 Sent To  
Notes
2004-10-29 00:00:00TOOK OFF COMM BD AND SENT TO SH DESK FOR
 HER REVIEW
2004-10-04 00:00:00TO COMM BD#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-15 Cont ID  
Sent By mjacobs Date 2004-09-15 Time 08:12 Rev Time 0.00
Received By mjacobs Date 2004-08-03 Time 14:16 Sent To  
Notes
2004-08-03 00:00:00TO COMM BD#23

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-06-21 Cont ID  
Sent By hmoser Date 2005-06-21 Time 16:00 Rev Time 0.00
Received By hmoser Date 2005-06-21 Time 16:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-10-13 Cont ID  
Sent By pkrauss Date 2004-10-13 Time 14:42 Rev Time 0.45
Received By pkrauss Date 2004-10-13 Time 14:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-27 Cont ID  
Sent By pkrauss Date 2004-08-27 Time 07:48 Rev Time 0.55
Received By pkrauss Date 2004-08-27 Time 07:40 Sent To  
Notes
2004-08-27 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION TO ALARM/STROBE IN NORMALLY
 OCCUPPIED AREAS PER 2001 FBC(M) 606.2.1
 & 606.4.1.
  
 PLEASE PROVIDE THE MANUFACTURER
 SUBMITTAL/INSTALLATION INSTRUCTIONS FOR
 THE COMPRESSOR AND VACUUM WITH THE
 THE RESUBMITTAL OF THIS PERMIT
 APPLICATION.
  
 EXHAUST TERMINATIONS SHALL BE LOCATED
 AS NOT TO RECIRCULATE BACK INTO THE
 VENTILATION SYSTEM PER 2001 FBC(M)
 501.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2004-12-14 Cont ID  
Sent By kstevens Date 2004-12-14 Time 17:46 Rev Time 0.33
Received By kstevens Date 2004-12-14 Time 17:46 Sent To  
Notes
2004-12-14 00:00:00SEPARATE MED-GAS PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-12-14 Cont ID  
Sent By kstevens Date 2004-12-14 Time 17:45 Rev Time 1.00
Received By kstevens Date 2004-12-14 Time 17:45 Sent To  
Notes
2004-12-14 00:00:00SEPARATE MED-GAS PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-12-10 Cont ID  
Sent By kstevens Date 2004-12-10 Time 07:37 Rev Time 0.75
Received By kstevens Date 2004-12-10 Time 07:37 Sent To  
Notes
2004-12-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A-4 ON ONE SET IS SEALED BY NOT
 SIGNED AND DATED. FAC 61G1-16.003 AND FS
 481.2055.
 2) SHT P-3 PLUMBING LEGEND. HAND WRITTEN
 CHANGES TO A SIGNED AND SEALED SET OF
 PLANS IS NOT APPROVED. EIGHER A NEW
 SHEET SHOWING CHANGES OR THE ENGINEER
 SIGNING AND DATING THE CHANGES ARE
 REQUIRED. SECTION 104.2.1.3.
 3) REMOVE ALL VOIDED SHEETS FROM BOTH
 SETS OF PLANS. SUBMIT ONE SET OF VOIDED
 SHEETS SEPARATELY FOR COMPAIRISON.
 SECTIONS 104.2.1 AND 104.2.1.3.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-10-15 Cont ID  
Sent By kstevens Date 2004-10-14 Time 17:38 Rev Time 3.25
Received By kstevens Date 2004-10-14 Time 17:38 Sent To  
Notes
2004-10-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 NFPA-99C MED-GAS
  
 FROM PREVIOUS REVIEW: COMMENT NUMBER TO
 REMAIN THE SAME TO AVOID CONFUSION.
 3) SHT A.1 SHOW CLEAR FLOOR SPACE REQUI-
 RED BY SECTION 11-4.24.5 WHICH SHALL BE
 PROVIDED IN FRONT OF THE SINKS TO ALLOW
 FORWARD APPROACH. THIS IS FOR THE SINKS
 IN THE COFFEE ROOM AND THE CONFERENCE
 ROOM. SINKS SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. DETAIL DOES
 NOT SHOW HEIGHT 11-4.24.2, KNEE CLEARAN-
 CE 11-4.24.3, SINK DEPTH 11-4.24.4,
 CLEAR FLOOR SPACE 11-4.24.5, (ONLY THE
 TURNING AREA IS SHOWN), SEE FIG. 32,
 EXPOSED PIPES AND SURFACES 11-4.24.6.
 6) SHT P-1 X-RAY PROCESSOR, SUBMIT MAN-
 UFACTURE SPECIFICATION/INSTALLATION
 SHEETS. THIS PROCESSOR MAY REQUIRE A
 CHEMICAL NUTRALIZER AND/OR A METAL INT-
 ERCEPTOR. IF EITHER IS REQUIRED, RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE SHALL BE
 CONTACTED. WASTE ORD. #2938-96. TO CON-
 TACT MR. COMPO (561) 837-4074. - NO RES-
 PONSE NOTED TO THIS COMMENT.
 7) SHT P.1 UNDER COUNTER WATER HEATER
 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DE-
 TAIOL. SECTION 501.4. - NO RESPONSE NOT-
 ED.
 8) SHT P.1 INDICATE TYPE OF SINK LOCATED
 IN THE CLOSET WITH THE VACUUM AND THE
 AIR COMPRESSOR. SECTION 104.2.1 - NO RE-
 SPONSE NOTED TO THIS COMMENT.
 11) SHT P.4 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 RISER DIAGRAM. SECTION 604.9 - WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9, (AT ICE MAKERS, DISH WASHERS, &
 WASH MACHINES), SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. - SHOW
 WATER HAMMER ARRESTORS ON RISER DIAGRAM
 WHERE REQUIRED.
 12) SHT WATER FILTER SHALL COMPLY WITH
 NSF-42, OR NSF-58 WHICH EVER APPLIES.
 SECTION 611.1 THRU 611.4. SUBMIT MANUF.
 SPECIFICATIONS. - NOT SUBMITTED.
 13) BACKFLOW REQUIRED AT X-RAY PROCESSOR
 PER SECTION 608.16.9 - THIS IS SHOWN ON
 THE ICE MAKER AND NOT ON THE X-RAY PRO-
 CESSOR.
 15) SHT P.5 COMPRESSOR DETAIL NOW CALLS
 FOR A 4" METAL VENT PIPE SHOWN ON SHEET
 AC-1. INDICATE THE TERMINATION POINT FOR
 THIS VENT PIPE. PROVIDE A DETAIL FOR THE
 TRANSITION FROM 2" PVC TO 4" METAL DUCT.
 SPECIFY MATERIAL OF METAL DUCT. T-FIN
 NOT APPROVED FOR THIS APPLICATION.
 16) SHT P.5 VACUUM DETAIL NOT APPROVED.
 SEE SECTION 4-5.2.1.3 LIQUIDS FROM A
 LEVEL 3 VACUUM SYSTEM PER 4-5.2.2 SHALL
 BE DIRECTLY CONNECTED TO THE SANITARY
 DRAINAGE SYSTEM THROUGH AN APPROIATELY
 TRAPPED AND VENTED DRAIN. SEE ATTACHED
 SHEETS FROM FIRST REVIEW.
 ------------SECOND NOTICE--------------
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-20 Cont ID  
Sent By kstevens Date 2004-08-20 Time 17:23 Rev Time 5.00
Received By kstevens Date 2004-08-20 Time 17:23 Sent To  
Notes
2004-08-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 NFPA-99C MED-GAS
 FBC-2001 BUILDING
  
 1) SHT A.3 FINISH SCHEDULE INDICATES THE
 BASE IN THE TOILET ROOMS WILL BE WOOD.
 PLEASE INDICATE HOW THIS COMPLIES WITH
 SECTION 1204.2 WHICH STATES THE WALLS
 AND FLOORS OF ALL PUBLIC REST ROOMS
 SHALL BE LINED WITH NONABSORBENT MATER-
 IAL TO A HEIGHT OF 4' ABOVE THE FLOOR.
 2) SHT A.1 WAS IT YOUR INTENTION NOT TO
 HAVE A SINK IN PROCEDURE ROOM #2? NOTE
 NO SINK SHOWN ON FLOOR PLAN. SECTION
 104.2.1
 3) SHT A.1 SHOW CLEAR FLOOR SPACE REQUI-
 RED BY SECTION 11-4.24.5 WHICH SHALL BE
 PROVIDED IN FRONT OF THE SINKS TO ALLOW
 FORWARD APPROACH. THIS IS FOR THE SINKS
 IN THE COFFEE ROOM AND THE CONFERENCE
 ROOMS. SINKS SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL.
 4) SHTS A.1 & A.5 DETAIL 14/A5 ON SHEET
 #1 SHOWN IN TWO DIFFERENT LOCATIONS WITH
 DIFFEREN ELEVATIONS. PLEASE CLARIFY.
 SECTION 104.2.1
 5) SHT A.5 DETAIL #16 LABELED AS "OFFICE
 DESK" BUT SHOWS SINK. PLEASE CLARIFY
 SECTION 104.2.1
 6) SHT P-1 X-RAY PROCESSOR, SUBMIT MAN-
 UFACTURE SPECIFICATION/INSTALLATION
 SHEETS. THIS PROCESSOR MAY REQUIRE A
 CHEMICAL NUTRALIZER AND/OR A METAL INT-
 ERCEPTOR. IF EITHER IS REQUIRED RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE SHALL BE
 CONTACTED. WASTE ORD. #2938. TO CONTACT
 MR. COMPO (561) 837-4074.
 7) SHT P.1 UNDER COUNTER WATER HEATER
 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DE-
 TAIL. SECTION 501.4.
 8) SHT P.1 INDICATE TYPE OF SINK LOCATED
 IN THE CLOSET WITH THE VACUUM AND AIR
 COMPRESSOR. SECTION 104.2.1
 9) SHT P.3 SUBMIT A VENT ISOMETRIC WITH
 PIPE SIZES TO COMFIRM COMPLIANCE WITH
 TABLE 916.1
 10) SHT P.3 ELECTRIC WATER HEATER DETAIL
 THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2. SUBMIT DETAIL
 11) SHT P.4 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 RISER DIAGRAM. SECTION 604.9 - WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9, (AT ICE MAKERS, DISH WASHERS, &
 WASH MACHINES), SHALL BE LOCATED NEAR
 THE FIXTURES, IN AN "EFFECTIVE RANGE",
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 & MANUF. INSTALL. INSTRUCTIONS.
 12) SHT WATER FILTER SHALL COMPLY WITH
 NSF-42, OR NSF-58 WHICH EVER APPLIES.
 SECTION 611.1, THRU 611.4 SUBMIT MANUF.
 SPECIFICATIONS.
 13) BACKFLOW REQUIRED AT X-RAY PROCESSOR
 PER SECTION 608.16.9
 14) SEPARATE PERMIT REQUIRED FOR THE
 MED-GAS. MED-GAS CERTIFICATION IS REQUI-
 RED FOR THE QUALIFIER, INSTALLER, AND
 THE BRAZER. THESE CERTIFICATIONS WITH
 PICTURE IDENTIFICATION IS REQUIRED AT
 THE TIME OF APPLICATION FOR PERMIT.
 15) SHT P.5 COMPRESSOR DETAIL CALLS FOR
 A 2" PVC SCHED. 30 PIPE CONNECTED TO THE
 RETURN AIR DUCT. THIS IS NOT APPROVED.
 THE AIR INTAKE SHALL BE FROM OUTSIDE THE
 BUILDING WHEN PRACTICAL OR SHALL BE LOC-
 ATED WITHIN A ROOM WHERE NO CHEMICAL-
 BASED MATERIAL IS STORED. NFPA 99C SECT-
 ION 4-5.1.1.3(E)
 16) SHT P.5 VACUUM DETAIL NOT APPROVED.
 SEE ATTACHED SHEETS (PAGE 48) FROM NFPA
 99C FIGURES 4-5.2.1.3(A) OR 4-5.2.1.3(B)
 FOR APPROVED DRAINAGE. - SEE OTHER
 SHEETS FOR DESIGN FOR VACUUM.
 17) SHT P.5 BACKFLOW REQUIRED FOR THE
 WATER SOURCE TO VACUUM PER SECTION
 608.16.9.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2004-12-15 Cont ID  
Sent By lmartine Date 2004-12-15 Time 13:25 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***