Plan Review Details - Permit 04080053
Plan Review Stops For Permit 04080053
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-01-18 Cont ID  
Sent By alange Date 2006-01-18 Time 16:48 Rev Time 1.00
Received By alange Date 2006-01-18 Time 16:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-10-07 Cont ID  
Sent By alange Date 2005-10-07 Time 10:59 Rev Time 2.00
Received By alange Date 2005-10-07 Time 10:50 Sent To Z
Notes
2005-10-07 00:00:00REVISION DENIED
  
 1.LEFT SIDE ELEVATION DOES NOT REFLECT
 THE WINDOW LAYOUT FROM THE SECOND FLOOR
 FLOOR PLAN.
  
 2.GENERATOR IS SHOWN ON PLANS.A
 SEPERATE GENERATOR PERMIT IS REQUIRED.
 NOTE: WHEN APPLICATION IS SUBMITTED A
 SLAB DETAIL WILL BE REQUIRED TO SHOW THE
 TOP OF THE GENERATOR SLAB TO BE AT 6"
 ABOVE THE BASE FLOOD ELEVATION OF 7FT.
  
 3.NOTE: REVISION FORM WAS SUBMITTED
 WITH NO INFORMATION ON WHAT IS TO BE
 REVISED.REVISED PLANS HAVE MINIMAL
 NOTATIONS ON WHAT HAS BEEN CHANGED AND
 SOME PAGES SUBMITTED APPEAR TO HAVE NO
 CHANGES MADE.SUBMIT ONLY PAGES THAT
 ARE BEING REVISED.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-10-19 Cont ID  
Sent By alange Date 2004-10-19 Time 16:01 Rev Time 1.50
Received By alange Date 2004-10-19 Time 16:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-31 Cont ID  
Sent By pschmitz Date 2004-10-16 Time 13:49 Rev Time 4.00
Received By alange Date 2004-08-31 Time 10:31 Sent To  
Notes
2004-08-31 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PLEASE SIGN OWNER/ AGENT ON ENERGY
 CALCS.
  
 4.WILL YOU BE USEING ANY OF THE
 EXISTING STRUCTURE?IF SO SHOW TIE
 IN FROM NEW TO EXISTING ON PLANS.
  
 5.PRODUCT APPROVALS MISSING FOR
 STRAPS AND TIE-DOWNS, SKYLIGHTS AND
 IMPACT PROTECTION.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6. SEPERATE PERMIT REQUIRED FOR POOL.
 REMOVE POOL DETAILS AND SUBMIT WITH A
 POOL PERMIT APPLICATION.
  
 7.1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT
 WILLREJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 8. BUILDING IS IN A FLOOD ZONE SUBMIT AN
 EVAVATION CERTIFICATE SHOWING BUILDING
 ABOVE BASE FLOOD ELEVATION.
  
 9.SMOKE DETECTORS ARE REQUIRED IN
 STAIRWELLS PER FBC 905.2.2
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-05-11 Cont ID  
Sent By btrobaug Date 2006-05-11 Time 08:45 Rev Time 0.50
Received By btrobaug Date 2006-05-11 Time 08:45 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-04-20 Cont ID  
Sent By btrobaug Date 2006-04-20 Time 17:58 Rev Time 1.00
Received By btrobaug Date 2006-04-14 Time 07:41 Sent To PC
Notes
2006-04-20 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEERS SEAL IS REQUIRED TO BE
 CHANGED TO CONTAIN THE TERM "LICENSE"
 INSTEAD OF "CERTIFICATE" PER THE BOARD
 OF ENGINEERS, AS OF 1 JANUARY, 2006. SEE
 61G15-23.001 FAC.
  
 2} PLEASE PROVIDE A SCHEDULE FOR THE
 MAIN DISCONNECT PANEL IN THE METER/MAIN
 COMBO.INCLUDE THE OCP FOR THE ATS.
  
 3} THE DISCONNECTS AT THE A/C
 COMPRESSERS AND POOL EQUIPMENT ARE IN
 VIOLATION OF 110.26. PLEASE NOTE THESE
 WERE REDLINED IN THE LAST REVIEW, AN DID
 NOT GET CHANGED ON THIS PLAN. PLEASE SEE
 THAT THE DESIGNER SEES THE REDLINED SET.
 OFTEN THEY DON'T AND THEREFORE ARE NOT
 AWARE ANY COMMENT WAS MADE.
  
 4} THE RECEPTACLES ADDED TO THE ISLAND
 ARE CONSIDERED SERVING THE COUNTERTOP
 AND THEREFORE MUST BE GFI PER
 210.8(A)(6).
  
 5} ALL KITCHEN COUNTERTOP RECEPTACLES
 MUST COMPLY WITH 210.8(A)(6}, PLEASE SEE
 REVIEWED SET.
  
 6} THE RECEPTACLE REQUIRED BY
 210.52(G)WAS REMOVED FROM THE GARAGE,
 PLEASE PUT IT BACK AND PROTECT PER
 210.8(A)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-01-11 Cont ID  
Sent By btrobaug Date 2006-01-11 Time 14:10 Rev Time 1.00
Received By btrobaug Date 2006-01-11 Time 08:18 Sent To P
Notes
2006-01-11 00:00:00TO JOHN ./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-10-05 Cont ID  
Sent By btrobaug Date 2005-10-05 Time 15:58 Rev Time 0.50
Received By btrobaug Date 2005-10-03 Time 17:07 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-15 Cont ID  
Sent By btrobaug Date 2004-10-15 Time 15:36 Rev Time 0.75
Received By btrobaug Date 2004-10-15 Time 14:28 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-10-15 Time 11:32 Rev Time 1.00
Received By btrobaug Date 2004-08-10 Time 12:31 Sent To P
Notes
2004-08-11 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 SHOWN IS NOT IN COMPLIANCE WITH 250.66,
 MUST BE A MINIMUM #2 CU.
  
 2} THE GROUNDING ELECTRODE SYSTEM MUST
 REFLECT AND NOTE, ALL AVAILABLE
 COMPONENTS BONDED PER 250.50.
  
 3} THE #2 FEEDERS TO THE PANELS DO NOT
 COMPLY WITH 310.15(B)(6), #1 MINIMUM.
  
 4} PLEASE INDICATE THE SIZE AND TYPE OF
 WIRE AND CONDUCTORS USED AS FEEDERS FOR
 ALL EQUIPMENT SHOWN ON THE RISER
 DIAGRAM.
  
 5} SHOW THE LOCATION OF THE SERVICE
 EQUIPMENT ON THE PLAN. THE DICONNECT IS
 SHOWN ON THE RISER BUT NOT LOCATED ON
 PLAN.
  
 6} THE LOAD CALCULATIONS/PANEL
 SCHEDULE,SHOWS ONLY ONE WATER HEATER
 THERE ARE
 TWO SHON ON THE PLAN. PLEASE ADJUST
 CALCULATIONS.
  
 7} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 8} THE A/C DISCONNECT LOCATION DO NOT
 MEET SPACING REQUIREMENTS OF 110.26.
  
 9} A GFI RECEPTACLE IS REQUIRED FOR
 SERVICE USE @ THE CONDENSING UNITS PER
 210.63.
  
 10} PANEL "A" LOCATION MAY NOT MEET 110.
 26 CLEARANCE WITH PROXIMETY OF THE AIR
 HANDLERS. PLEASE CHECK DIMENSIONS.
  
 11} RECEPTACLE(S) NEED TO BE ADDED OR
 RELOCATED TO COMPLY WITH THE SPACING
 REQUIREMENTS OF 210.52 IN THE DINING
 ROOM, LIBRARY, BEDROOM #4, BEDROOM #3,
 BEDROOM #2 AND THE SITTING ROOM. SEE
 REVIWED SET OF PLANS.
  
 12} THE RECEPTACLE FOR THE WHIRLPOOL TUB
 MUST BE GFI PER 680.71 NEC.
  
 13} SMOKE DETECTORS ARE REQUIRED TO BE
 LOCATED AT THE STAIRWELLS PER 905.2.2
 FBC & NFPA-72 CHAPTER 8.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-05-15 Cont ID  
Sent By adarroug Date 2006-05-15 Time 16:10 Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 16:10 Sent To P
Notes
2006-05-15 00:00:00TO "MPERSON" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-11 Cont ID  
Sent By adarroug Date 2006-04-11 Time 09:01 Rev Time 0.00
Received By adarroug Date 2006-04-11 Time 09:01 Sent To E
Notes
2006-04-11 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2006-01-09 Time 14:11 Rev Time 0.00
Received By adarroug Date 2006-01-09 Time 14:11 Sent To E
Notes
2006-01-09 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-26 Cont ID  
Sent By adarroug Date 2005-09-26 Time 18:42 Rev Time 0.00
Received By adarroug Date 2005-09-26 Time 18:42 Sent To E
Notes
2005-09-26 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 14:48 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 14:48 Sent To M
Notes
2005-08-09 00:00:00TO "HMOSER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-15 Cont ID  
Sent By csiegber Date 2004-10-15 Time 11:32 Rev Time 0.00
Received By csiegber Date 2004-10-15 Time 11:32 Sent To E
Notes
2004-10-15 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-05 Cont ID  
Sent By mmclean Date 2004-10-14 Time 16:14 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 11:02 Sent To Z
Notes
2004-10-05 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-06 Cont ID  
Sent By csiegber Date 2004-08-06 Time 08:31 Rev Time 0.00
Received By csiegber Date 2004-08-06 Time 08:31 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-03 Cont ID  
Sent By mmclean Date 2004-08-05 Time 16:03 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 09:48 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-09 Cont ID  
Sent By hmoser Date 2005-08-09 Time 15:05 Rev Time 0.00
Received By hmoser Date 2005-08-09 Time 15:05 Sent To  
Notes
2005-08-09 00:00:00REVISON ON ENERGE CALCULATIONS OK.HM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-24 Cont ID  
Sent By btrobaug Date 2004-10-15 Time 15:36 Rev Time 0.35
Received By pkrauss Date 2004-08-24 Time 11:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-01-13 Cont ID  
Sent By jleech Date 2006-01-13 Time 09:38 Rev Time 0.33
Received By jleech Date 2006-01-13 Time 09:38 Sent To B
Notes
2006-01-13 00:00:00REVISED RISER DIAGRAM OK

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-10-06 Cont ID  
Sent By jleech Date 2005-10-06 Time 14:33 Rev Time 0.75
Received By jleech Date 2005-10-06 Time 14:33 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-10-16 Cont ID  
Sent By pschmitz Date 2004-10-16 Time 13:47 Rev Time 1.00
Received By pschmitz Date   Time   Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-14 Cont ID  
Sent By btrobaug Date 2004-10-15 Time 15:39 Rev Time 0.75
Received By pschmitz Date 2004-08-14 Time 13:44 Sent To M
Notes
2004-08-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT 1 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS.
 A) POWDER ROOM FIXTURES DO NOT REFLECT
 LAYOUT ON FLOOR PLAN. SECTION 104.2.1
 B) WASH MACHINE REQUIRES A STANDPIPE
 MIN. 2', AND A CLEANOUT 4' ABOVE THE
 FLOOR. SECTIONS 1002.1/802.4 & 708.10.
 WASH MACHINE AND LAUNDRY SINK SHALL NOT
 CONNECT TO STACK AT THE SAME ELEVATION.
 W/M SHALL CONNECT BELOW L/T. SECTION
 706.3.
 C) BATHROOM BY BEDROOM #4 THE SHOWER
 IS ON THE RIGHT SIDE OF THE W/C ON THE
 FLOOR PLAN, BUT ON THE LEFT SIDE ON THE
 RISER. THE SHOWER IS NOT VENTED AND
 SHALL CONNECT TO THE LAV BRANCH. SECTION
 104.2.1. & 901.2.1
 D) CABANA BATH SHOWER IS NOT VENTED.
 LAV SHALL CONNECT TO THE SHOWER BRANCH
 TO VENT SHOWER. SECTION 901.2.1
 E) WET BAR DOES NOT REFLECT THE FLOOR
 PLAN. WET BAR SHALL BELOCATED ON THE
 OTHER SIDE OF THE WALL FROM THE CABANA
 BATH. SECTION 104.2.1
 F) MASTER BATH DOES NOT REFLECT THE
 FLOOR PLAN, W/C ON RIGHT, TO THE LEFT
 THE BIDET, THEN THE TUB, THEN SHOWER,
 AND THE LAV IS ON THE OPPOSITE WALL.
 BIDET AND SHOWER ARE NOT VENTED AS SHOWN
 G) BATHROOM FOR BEDROOM #2, NO FITTINGS
 APPROVED FOR W/C, TUB, LAV AS SHOWN.
 W/C BETWEEN LAV AND TUB. 2" SHOWN TO W/C
 H) WASH MACHINE REQUIRES A 2' STANDPIPE
 AND A CLEANOUT 4' ABOVE THE FLOOR. SECT-
 IONS 1002.1/802.4 & 708.10
 I) NO APPROVED FITTINGS FOR CONNECTION
 OF W/C, TUB, AND LAV AS SHOWN ON RISER
 FOR BATHROOM FIXTURES FOR BATHROOM FOR
 BEDROOM #3.
 MAKE CORRECTIONS ON RISER DIAGRAM AND
 RESUBMIT FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2005-10-20 Cont ID  
Sent By mmclean Date 2005-10-20 Time 13:44 Rev Time 0.00
Received By mmclean Date 2005-10-20 Time 13:44 Sent To  
Notes
2005-10-20 00:00:00DENIED, - REVISION
 1. MUST PROVIDE THE DIMENSION FOR THE
 CICURLAR DRIVEWAY/WALKWAY (LENGTH &
 WIDTH).
 MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCPAE QHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 ****************************************
 NOTE: NEED TO PULL A SEPERATE PERMIT FOR
 WALL/COLUMNS/GATE/FENCE WITH EASEMENT
 APPROVAL FROM THE CITY OF WEST PALM
 BEACH UTILITY DEPT.
  
 NOTE: MAXIMUM HEIGHT ALLOWED WITH THE
 FRONT SETBACK IS MAXIMUM OF 4FT IN
 HEIGHT AND 10% OF MAXIMUM HEIGHT OF WALL
 FOR DECORATIVE LIGHTINGS.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-14 Cont ID  
Sent By mmclean Date 2004-10-14 Time 16:14 Rev Time 0.00
Received By mmclean Date 2004-10-14 Time 16:14 Sent To I
Notes
2004-10-14 00:00:00MUST PULL A SEPARATE PERMIT FOR POOL/SPA

Review Stop Z ZONING
Rev No 1 Status F Date 2004-08-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 11:02 Rev Time 0.00
Received By mmclean Date 2004-08-05 Time 16:03 Sent To I
Notes
2004-08-05 00:00:00DENIED, CHIMNEY OVER THE HEIGHT
 REQUIREMENT 33FT.MUST PULL A SEPARATE
 PERMIT FOR POOL/SPA MM