Plan Review Details - Permit 04071421
Plan Review Stops For Permit 04071421
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-06 Cont ID  
Sent By pkrauss Date 2004-12-06 Time 14:53 Rev Time 0.35
Received By pkrauss Date 2004-12-06 Time 14:53 Sent To  
Notes
2004-12-06 00:00:00PER LUIS MARTINEZ & BILL TROBAUGH UL
 CERTIFICATION LETTER SUBMITTED &
 COMMENTS ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-07-30 Time 16:26 Rev Time 0.00
Received By nmccray Date 2004-08-11 Time 10:20 Sent To  
Notes
2004-08-11 00:00:00**********DENIED************************
 1) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 2) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENT
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 APPROVAL OF THESE PLANS OR PROOF OF
 APPLICATION TO UL.
  
 3) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
 4) ALL DUCT SMOKE DETECTORS SHALL SEND
 AND PUT THE SYSTEM IN GENERAL FIRE ALARM
 MODE IN THE CITY OF WEST PALM BEACH NOT
 A SUPERVISORY SIGNAL.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-30 Cont ID  
Sent By mjacobs Date 2004-11-30 Time 10:35 Rev Time 0.00
Received By mjacobs Date 2004-11-30 Time 10:35 Sent To FIRE
Notes
2004-11-30 00:00:00SENT TO "FIRRE" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-30 Cont ID  
Sent By csiegber Date 2004-07-30 Time 16:26 Rev Time 0.00
Received By csiegber Date 2004-07-30 Time 16:26 Sent To FIRE
Notes
***NONE***