Plan Review Details - Permit 04071332
Plan Review Stops For Permit 04071332
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-03-08 Cont ID  
Sent By alange Date 2005-03-08 Time 10:46 Rev Time 0.50
Received By alange Date 2005-03-08 Time 10:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-02-28 Cont ID  
Sent By alange Date 2005-02-28 Time 08:28 Rev Time 3.25
Received By alange Date 2005-02-25 Time 14:17 Sent To  
Notes
2005-02-28 00:00:00DENIED
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-13 Cont ID  
Sent By alange Date 2005-01-13 Time 08:37 Rev Time 1.00
Received By alange Date 2005-01-13 Time 08:37 Sent To Z
Notes
2005-01-13 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS FOR THE FOLLOWING, GLASS
 BLOCK, STRAPS AND TIE-DOWNS, WINDOWS,
 EXTERIOR DOORS, IMPACT PROTECTION FOR
 EXT. DOORS, AND ROOFING.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED TO EACH
 APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEW NOTES:
  
 A. PLANS SHOW ALL EXTERIOR DOORS AS
 EXISTING, BUT PRODUCT APPROVALS HAVE
 BEEN SUBMITTED FOR EXTERIOR DOORS.
 PLEASE VERIFY ON PLANS.
  
 B.BUILDING VALUATION IS TOO LOW.
 ADJUST VALUATION TO REFLECT WORK ON NEW
 PLANS SUBMITTED.ADDITIONAL PERMIT FEES
 ARE DUE.
  
 C.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS. FBC 2309.6
  
 D. WATER STOP - WHERE EXTERIOR MASONARY
 UNITS BEAR ON A CONCRETE FLOOR SURFACE,
 A 1.5" RECESS SHALL BE PROVIDED TO
 MINIMIZE WATER INTRUSION. WPB
 AMMENDMENTS TO THE FBC 2111.1.9
  
 E.ON 2 X 8 PT TOP PLATE, SHOW SIZE AND
 TYPE OF ANCHOR AND SPACING.
  
 F. PLEASE SUBMIT 2 COPIES OF MANUAL J
 ENERGY CALCS.
  
 G.THE ARCHITECTS SEAL IS REQUIRED PER
 61G1-16.001 PLEASE PUT SEAL ON ALL
 PAGES
 AND SIGN.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-17 Cont ID  
Sent By prafter Date 2005-01-05 Time 14:23 Rev Time 1.00
Received By alange Date 2004-08-17 Time 09:35 Sent To  
Notes
2004-08-17 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.SUBMIT 2 COMPLETE COPIES OF PRODUCT
 APPROVALS.PRODUCT APPROVALS ALSO
 NEEDED FOR STRAPS AND TIEDOWNS AND
 GLASSBLOCK.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.SPECIFY TYPED OF STRAPS USED.
  
 4.FBC 1707.4.4.2UNLESS OTHERWISE
 TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME SUCH THAT FULL SUPPORT OF THE
 FRAME IS PROVIDED.SHOW DETAIL ON PLANS
  
 5.SHOW DETAILS FOR FOOTINGS.
  
 6. FBC 104.2.1 ALL INFORMATION, DRAWINGS
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 7.IMPACT PROTECTION REQUIRED. SUBMIT
 PRODUCT APPROVALS.
  
 8.SUBMIT FLOOR PLANS, SHOW LOCATIONS
 OF BEDROOMS.SHOW WINDOW SILL HEIGHT
 AND TYPE AND SIZE OF BEDROOM WINDOWS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-08-13 Cont ID  
Sent By btrobaug Date 2007-08-13 Time 14:31 Rev Time 0.00
Received By btrobaug Date 2007-08-13 Time 14:17 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-06-15 Cont ID  
Sent By btrobaug Date 2006-06-15 Time 13:03 Rev Time 0.50
Received By btrobaug Date 2006-06-15 Time 12:58 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2005-03-03 Cont ID  
Sent By btrobaug Date 2005-03-03 Time 16:17 Rev Time 0.33
Received By btrobaug Date 2005-03-03 Time 16:12 Sent To B
Notes
2005-03-03 00:00:00PASSED REVIEW 2.25.05./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-25 Cont ID  
Sent By btrobaug Date 2005-02-25 Time 08:48 Rev Time 0.50
Received By btrobaug Date 2005-02-25 Time 08:27 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-01-03 Cont ID  
Sent By btrobaug Date 2005-01-03 Time 16:27 Rev Time 0.50
Received By btrobaug Date 2005-01-03 Time 15:41 Sent To M
Notes
2005-01-03 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} PLEASE SUBMIT AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT BEING INSTALL- ED.
 MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9.
  
 2} INDICATE GROUNDING ELECTRODE SYSTEM
 PER 250.50 & 250.66, INCLUDE ON PLAN.
  
 3} BEDROOM #2 NEEDS A RECEPTACLE ADDED
 TO COMPLY WITH 210.52(A)(1).
  
 4} THE ARCHITECTS SEAL PER 61G1-16.001,
 MUST BE ON PLAN.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-05 Cont ID  
Sent By csiegber Date 2004-07-30 Time 16:55 Rev Time 0.50
Received By btrobaug Date 2004-08-05 Time 12:57 Sent To P
Notes
2004-08-05 00:00:00 
 PROVIDE PLANS FOR REVIEW PER 104.2 FBC.
 AND RISER DIAGRAM AND CALCULATIONS PER
 215.5 NEC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 14:46 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 14:46 Sent To Z
Notes
2007-08-06 14:47:13TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 18:34 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 18:34 Sent To E
Notes
2006-06-08 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-04 Cont ID  
Sent By adarroug Date 2005-03-02 Time 16:42 Rev Time 0.00
Received By adarroug Date 2005-03-02 Time 16:42 Sent To  
Notes
2005-03-04 00:00:00TO LMARTINEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-23 Cont ID  
Sent By adarroug Date 2005-02-23 Time 13:42 Rev Time 0.00
Received By adarroug Date 2005-02-23 Time 13:42 Sent To E
Notes
2005-02-23 00:00:00TO "BT" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 14:53 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 14:53 Sent To Z
Notes
2005-02-15 00:00:00TO "Z" BOX/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 14:40 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 14:39 Sent To E
Notes
2005-01-03 00:00:00TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-30 Cont ID  
Sent By csiegber Date 2004-07-30 Time 16:55 Rev Time 0.00
Received By csiegber Date 2004-07-30 Time 16:55 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-29 Cont ID  
Sent By mmclean Date 2004-07-30 Time 12:17 Rev Time 0.00
Received By csiegber Date 2004-07-29 Time 15:21 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-02-25 Cont ID  
Sent By pkrauss Date 2005-02-25 Time 10:53 Rev Time 0.25
Received By pkrauss Date 2005-02-25 Time 10:53 Sent To B
Notes
2005-02-25 00:00:00NO MECHANICAL CONTRACTOR INDICATED ON
 THE PERMIT APPLICATION.PER ARCHITECT'S
 NOTE, A/C CONTRACTOR TO SUBMIT PLANS FOR
 HIS APPROVAL.SEPARATE PERMIT REQUIRED
 FOR MECHANICAL, PLEASE PROVIDE PLANS AND
 MANUAL J CALCULATIONS WITH PERMIT
 APPLICATION.ENERGY CALCS SUBMITTED
 WITH THE BUILDING PERMIT APPLICATION.
 1.PLAN SHEET A.4, MECHANICAL FLOOR
 PLAN NOTES; A/C CONTRACTOR TO PROVIDE
 SHOP DRAWINGS FOR ARCHITECT'S APPROVAL.
 PLEASE REVISE THE PLANS TO INDICATE THE
 FOLLOWING -
 - RETURN AIR REQUIRED FROM HABITABLE
 ROOMS ISOLATED FROM THE RETURN AIR BACK
 TO THE AIR HANDLING UNIT 2001
 FBC(M)601.4.
 - INDICATE LINE SIZES FOR THE LIQUID,
 SUCTION & CONDENSATE.PLEASE NOTE,
 CONDENSATE TO TERMINATE A MINIMUM OF 12"
 FROM THE BUILDING STRUCTURE.
 - PROVIDE DUCT AND GRILLE SIZE.
 - AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001
 FBC(M)307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-01-04 Cont ID  
Sent By prafter Date 2005-01-04 Time F Rev Time 0.45
Received By prafter Date 2005-01-05 Time 14:22 Sent To B
Notes
2005-01-04 00:00:00MECH . FAILED.
 NO ENERGY MANUAL J CALCULATION.
  
 NO A/C PLANS OR EQUIPMENT INFORMATION.
 PAT RAFTER 561/805/6725 OR 805/6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-08-16 Cont ID  
Sent By jleech Date 2004-08-10 Time 20:05 Rev Time 0.20
Received By pkrauss Date 2004-08-16 Time 11:24 Sent To B
Notes
2004-08-16 00:00:00NO MECHANICAL PLANS SUBMITTED OR
 CONTRACTOR INDICATED ON PERMIT
 APPLICATION.PROVIDE ENERGY & MANUAL J
 CALCULATIONS, EQUIPMENT SCHEDULE AND
 PLANS WITH MECHANICAL PERMIT APPLICATION
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-08-10 Cont ID  
Sent By btrobaug Date 2004-08-05 Time 13:21 Rev Time 0.25
Received By jleech Date 2004-08-10 Time 20:04 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2007-08-07 Cont ID  
Sent By choops Date 2007-08-07 Time 08:20 Rev Time 0.00
Received By choops Date 2007-08-07 Time 08:20 Sent To E
Notes
2007-08-07 08:26:27***FAILED***REVISION***
  
  
 1)CLARIFY SCOPE OF WORK...DRIVEWAY BEING REPLACE?
  
 2)PLEASE PROVIDE A PHOTMETRIC PLAN SHOWING THE
 ILLUMINATION OF PROPOSED LIGHTS AT THE NEAREST
 ADJOINGING PROPERTIES.PURSUANT TO THE CITY OF WEST
 PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS,
 SECTION 94-310(D):
  
 GLARE.ANY OPERATION OR ACTIVITY PRODUCING GLARE SHALL
 BE CONDUCTED SO THAT DIRECT OR INDIRECT LIGHT FROM THE
 SOURCE SHALL NOT CAUSE ILLUMINATION IN EXCESS OF 0.5
 FOOT CANDLES WHEN MEASURED IN A RESIDENTIAL DISTRICT.
  
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 3 Status P Date 2005-02-22 Cont ID  
Sent By mmclean Date 2005-02-22 Time 16:26 Rev Time 0.00
Received By mmclean Date 2005-02-22 Time 16:26 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-01-20 Cont ID  
Sent By mmclean Date 2005-01-18 Time 16:53 Rev Time 0.00
Received By mmclean Date 2005-01-18 Time 16:54 Sent To  
Notes
2005-01-20 00:00:00DENIED, NEED TO GET CLARIFICATION TO
 WHAT IS BEING DONE AT THE LOCATION.
 PERMIT APPLICATION STATES "CONVERT
 CARPORT TO GARAGE AND PLANS SHOWS AN NEW
 REAR PORCH ADDITION.CALLED OWNER
 (WIFE) AND LEFT MSG TO CALL REGARDING
 THE PERMIT.FILE S FOR P/U

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-30 Cont ID  
Sent By csiegber Date 2004-07-29 Time 15:21 Rev Time 0.00
Received By mmclean Date 2004-07-30 Time 12:17 Sent To I
Notes
***NONE***