Plan Review Details - Permit 04071323
Plan Review Stops For Permit 04071323
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-08-30 Cont ID  
Sent By mjacobs Date 2004-08-30 Time 09:38 Rev Time 0.50
Received By mjacobs Date 2004-08-30 Time 09:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-02 Cont ID  
Sent By alange Date 2004-08-02 Time 16:01 Rev Time 1.66
Received By alange Date 2004-08-02 Time 16:01 Sent To  
Notes
2004-08-02 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.FBC 2405.2.1 - 3 SAFTEY GLAZING
 REQUIRED WITHIN 24" OF A DOORWAY.
 SHOW ON PLANS.
  
 3.FBC CHAPTER 11 18" INCH CLEARANCE RE
 QUIRED ON THE LATCH SIDE OF A DOOR.
 SEE ATTACHED DIAGRAM.
  
 4.SHOW STAIR LANDING ON STAIR #13.
  
 5.WILL A SINK BE PROVIDED FOR THE
 LOUNGE.IF SO, SHOW HEIGHT OF SINK
 AND CLEARANCES.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 561-805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-30 Cont ID  
Sent By dpalmer Date 2004-08-30 Time 07:29 Rev Time 0.10
Received By dpalmer Date 2004-08-30 Time 07:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-02 Cont ID  
Sent By dpalmer Date 2004-08-02 Time 17:00 Rev Time 0.25
Received By dpalmer Date 2004-08-02 Time 17:00 Sent To  
Notes
2004-08-02 00:00:00MINOR ELECTRICAL SHOWN ON REFLECTED
 CEILING PLAN OK.
 HOWEVER, DUE TO BLDG REVIEW COMMENTS,
 PLANS CAN NOT BE STAMPED AT THIS TIME.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-08-25 Cont ID  
Sent By nmccray Date 2004-08-25 Time 09:53 Rev Time 0.00
Received By nmccray Date 2004-08-25 Time 09:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-08-10 Cont ID  
Sent By mcarsill Date 2004-08-10 Time 13:17 Rev Time 0.00
Received By mcarsill Date 2004-08-10 Time 13:17 Sent To  
Notes
2004-08-10 00:00:001) EXIT SIGNS AND EMERGENCY LIGHTS
 ARE DIFFICULT TO VISUALIZE. PLEASE
 CORRECT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 16:05 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 16:05 Sent To  
Notes
2004-08-24 00:00:00TO COMM BD#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-13 Cont ID  
Sent By alange Date 2004-08-13 Time 08:22 Rev Time 0.00
Received By alange Date 2004-07-29 Time 08:41 Sent To  
Notes
2004-07-29 00:00:00TO COMM BD#25