Plan Review Details - Permit 04071234
Plan Review Stops For Permit 04071234
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-02 Cont ID  
Sent By alange Date 2004-11-02 Time 09:53 Rev Time 1.00
Received By alange Date 2004-11-02 Time 09:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-16 Cont ID  
Sent By pkrauss Date 2004-08-13 Time 14:36 Rev Time 1.25
Received By alange Date 2004-08-16 Time 16:35 Sent To  
Notes
2004-08-16 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.ARCHITECT MUST SIGN AND SEAL PLANS
 WITH TITLE BLOCK ON PAGE. 61G1-16.004
 FAC
  
 3.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR THE FOLLOWING:
 STRAPS AND TIE DOWNS, EXTERIOR DOORS,
 WINDOWS, IMPACT PROTECTION AND ROOFING.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.FBC 2309.6 SHOW ATTIC ACCESS AND
 SIZE.
  
 5.SUBMIT 2 COPIES OF A SOILS REPORT.
  
 6.FBC 2405.2.1 BATHROOM GLAZING SHALL
 COMPLY WITH THIS SECTION.
  
 7.SHOW RAKED TIE BEAM DETAILS.
  
 8.BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUATION HAS BEEN REVISED.
 1075SQ.FT. X $76.96 = $82,732 ADDITIONAL
 PERMIT FEES ARE DUE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-01 Cont ID  
Sent By btrobaug Date 2004-10-22 Time 10:50 Rev Time 0.00
Received By btrobaug Date 2004-10-21 Time 17:12 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-04 Cont ID  
Sent By csiegber Date 2004-10-18 Time 15:30 Rev Time 0.75
Received By btrobaug Date 2004-08-04 Time 16:45 Sent To P
Notes
2004-08-04 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A LOAD CALCULATION FOR
 THE EXISTING LOADS AS WELL AS THE NEW
 LOAD PER 215.5.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER110.9.
  
 3} THE PANEL MOUNTED ON THE NEW
 STRUCTURE MUST BE GROUNDED PER 250.32.
  
 4} THE DRYER IS SHOWN AS 5KW IN THE LOAD
 CALC, BUT SHOWN ON A 40 AMP BREAKER ON
 THE PANEL SCHEDULE, PLEASE CORRELATE.
  
 5} THE AIR HANDLER IS SHOWN AT 7500
 WATTS IN THE LOAD CALC BUT SHOWN ON A
 40 AMP BREAKER. THE AHU CIRCUIT MUST BE
 RATED @ 125% PER 424.22(E).
  
 6} THE ARCHITECT MUST PROVIDE A TITLE
 BLOCK ON THE PLAN PER 61G1-16.004, AND
 MUST DATE THE SEAL, SAME ART. FAC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-08 Cont ID  
Sent By adarroug Date 2006-03-08 Time 15:38 Rev Time 0.00
Received By adarroug Date 2006-03-08 Time 15:38 Sent To M
Notes
2006-03-08 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-18 Cont ID  
Sent By csiegber Date 2004-10-18 Time 15:30 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 15:30 Sent To E
Notes
2004-10-18 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-29 Cont ID  
Sent By csiegber Date 2004-07-29 Time 16:48 Rev Time 0.00
Received By csiegber Date 2004-07-29 Time 16:48 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-28 Cont ID  
Sent By mmclean Date 2004-07-29 Time 10:23 Rev Time 0.00
Received By csiegber Date 2004-07-28 Time 12:08 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-03-21 Cont ID  
Sent By tgordon Date 2006-03-21 Time 10:48 Rev Time 0.30
Received By tgordon Date 2006-03-21 Time 10:48 Sent To  
Notes
2006-03-21 00:00:00REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-03-09 Cont ID  
Sent By tgordon Date 2006-03-09 Time 09:25 Rev Time 0.30
Received By tgordon Date 2006-03-09 Time 09:25 Sent To  
Notes
2006-03-09 00:00:00*** DENIED ***
 1) ORIGINAL MECHANLCAL PLANS WERE DONE
 BY AN ARCHITECT (RAFAEL RODRIGUES) AND
 STAMPED. HE IS THE PERSON WHO NEEDS TO
 DESIGN AND STAMP ANY MECHANICAL
 REVISIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-13 Cont ID  
Sent By jleech Date 2004-08-10 Time 19:24 Rev Time 0.35
Received By pkrauss Date 2004-08-13 Time 14:36 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-11-01 Cont ID  
Sent By pschmitz Date 2004-11-01 Time 14:51 Rev Time 0.00
Received By pschmitz Date 2004-11-01 Time 14:51 Sent To  
Notes
2004-11-01 00:00:00SEPERATE PREMIT, PLANS FOR GAS

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-10 Cont ID  
Sent By btrobaug Date 2004-11-01 Time 10:52 Rev Time 0.33
Received By jleech Date 2004-08-10 Time 19:23 Sent To M
Notes
2004-08-10 00:00:00ARCHITECT TITAL BLOCK ARE MISSING

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-29 Cont ID  
Sent By csiegber Date 2004-07-28 Time 12:08 Rev Time 0.00
Received By mmclean Date 2004-07-29 Time 10:23 Sent To I
Notes
***NONE***