Plan Review Details - Permit 04071209
Plan Review Stops For Permit 04071209
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-05 Cont ID  
Sent By jwitmer Date 2004-08-05 Time 09:43 Rev Time 2.22
Received By jwitmer Date 2004-08-05 Time 09:43 Sent To  
Notes
2004-08-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071209
 ADD: 1601 BELVEDERE RD# 303 SOUTH
 CONT: NEW LINE CONSTRUCTION
 TEL: (954)648-0955
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) ARCHITECTURAL PLANS MISSING :
 481.219(2) F.S.A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, PARTNERSHIP, OR PERSON
 PRACTICING UNDER A FICTITIOUS NAME,
 OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
  
 3) SHEET A-1.2 SHOWS A NEW ENTRY DOOR AT
 THE ENTRY. PLANS DO NOT INDICATE DOOR
 RATING. NOTE NO MINIMUM BUILDING TYPE
 PROVIDED. IS THE BUILDING PROTECTED OR
 FIRE SPRINKLERED.
  
 4) FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION:
 GLASS NEXT TO DOORWAYS & WALKWAYS.
  
 5) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 6) SHEET A-2.1 DETAIL A BREAK ROOM
 CABINETRY & SINK TO COMPLY WITH:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 8) SHEET A-1.2 NOTE"H" INDICATES THE USE
 OF A PRE-FABRICATED COLUMN, PROVIDE ADD-
 ITIONAL INFORMATION. 803.4 FOAM PLASTIC
 TRIM SHALL NOT BE USED AS INTERIOR
 FINISHES.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-08-03 Cont ID  
Sent By dpalmer Date 2004-08-03 Time 09:42 Rev Time 0.33
Received By dpalmer Date 2004-08-03 Time 09:42 Sent To  
Notes
2004-08-03 00:00:00*** PLANS MISSING CA# ON TITLE BLOCK
 WHICH IS REQUIRED UNDER FS 471.023,
 FAC 61G15-23.002.
 THE CA # HAS BEEN PRINTED ON E-SHEETS
 ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-08-19 Cont ID  
Sent By mcarsill Date 2004-08-19 Time 08:10 Rev Time 0.00
Received By mcarsill Date 2004-08-19 Time 08:10 Sent To  
Notes
2004-08-19 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED DAILY FROM
 THE SITE.
  
 3) WHAT IS THE RATING OF THE NEW DOOR
 ON PAGE A-1.2.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2004-08-19 Cont ID  
Sent By mjacobs Date 2004-08-19 Time 10:43 Rev Time 0.00
Received By mjacobs Date 2004-07-29 Time 11:55 Sent To  
Notes
2004-07-29 00:00:00TO COMM BD#4

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***