Plan Review Details - Permit 04071171
Plan Review Stops For Permit 04071171
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-24 Cont ID  
Sent By rmcdouga Date 2005-03-24 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2005-03-24 Time 07:03 Sent To  
Notes
2005-03-24 00:00:00REVISED SHEETS FOR ROOF A6,A7,A8 & S4
 ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-03-11 Cont ID  
Sent By rmcdouga Date 2005-03-11 Time 07:15 Rev Time 0.00
Received By rmcdouga Date 2005-03-11 Time 07:15 Sent To  
Notes
2005-03-11 00:00:00STRUCTURE HAS A MEAN ROOF HEIGHT OF MORE
 THAN 33 FEET. ASPHALT SHINGLES WERE
 APPROVED FOR USE BY NEIL MELICK, B.O.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-03-07 Cont ID  
Sent By rmcdouga Date 2005-03-07 Time 08:36 Rev Time 0.00
Received By rmcdouga Date 2005-03-07 Time 08:36 Sent To  
Notes
2005-03-07 00:00:00DENIED
  
 1) SUBMIT COMPLETE TESTING REPORTS (WITH
 ANY LIMITATIONS) AND INSTALLATION
 INSTRUCTIONS AND DRAWINGS FOR THE
 ASPHALT ROOF SHINGLES. NOTE: STRUCTURE
 EXCEEDS 33 FEET.
  
 2) SUBMIT THE NOA OR EVALUATION REPORT
 FROM THE STATE PRODUCT APPROVAL WEBSITE
 FOR THE GLASS BLOCK. IT IS MISSING FROM
 THE SUBMITTAL.
  
 3) THE SIMPSON CONNECTOR SPECIFIED ON S4
 FOR MARK (J) IN THE SCHEDULE AS HDSA IS
 A TYPO AND SHOULD BE HD5A. PLEASE
 CORRECT.
  
 4) THE CONNECTOR SPECIFIED AT THE
 EXTERIOR WALL FOR THE MG1 GIRDER TRUSSES
 IS NOT ADEQUATE TO RESIST THE UPLIFT
 LISTED IN THE TRUSS DRAWINGS.
  
 5) PLEASE CLARIFY THAT DETAIL 10 ON S7
 IS TYPICAL FOR EACH END OF ALL THE GR2
 GIRDERS AND ONE END OF THE GR1 GIRDERS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-12-10 Cont ID  
Sent By rmcdouga Date 2004-12-10 Time 11:05 Rev Time 0.00
Received By rmcdouga Date 2004-12-09 Time 07:09 Sent To  
Notes
2004-12-10 00:00:00DENIED
  
 1) THE OWNER/AGENT IS REQUIRED TIO SIGN
 THE ENERGY CALC. FORMS. THE ENERGY
 CALCS. DO NOT SPECIFY THE 2X6 WOOD FRAME
 EXTERIOR WALLS WITH R-19 INSULATION. THE
 PLANS SPECIFY R-30 CEILING INSULATION
 AND THE ENERGY CALCS. LISTS R-19. PLEASE
 CORRECT.
  
 2) FBC 2504.2.1 REQUIRES EXTERIOR
 APPLICATIONS OF PORTLAND CEMENT PLASTER
 TO COMPLY WITH ASTM C 926. THIS STANDARD
 REQUIRES PLASTER OVER METAL BASE TO BE
 5/8" THICK ON HORIZONTAL APPLICATIONS
 AND 7/8" FOR VERTICAL APPLICATIONS.
  
 3) MEAN ROOF HEIGHT FOR THE STRUCTURE IS
 38'-5". SUBMIT ENGINEERED CALCULATIONS
 FOR THE ROOF SHEATHING FASTENING
 REQUIREMENTS.
  
 4) PROVIDE CAP DETAILS FOR THE WOOD
 COLUMN (WP-1) AND THE STEEL COLUMN
 (SC-1).
  
 5) SECT.5 ON S7 WHICH SHOWS A 6X6 WD.
 POST, HOWEVER, NO ID TAG IS ON THE PLAN
 FOR THIS SECTION. PLEASE CLARIFY.
  
 6) SUBMIT PRODUCT APPROVALS FOR ASPHALT
 ROOF SHINGLES THAT WERE TESTED TO ASTM D
 3161 (MODIFIED TO 110 MPH) OR PA 107 AND
 ARE NOT LIMITED TO A 33'MRH.
  
 7) THE DOOR SCHEDULE FOR UNIT 2 & 2R
 DOES NOT LIST THE 16'WIDE OVERHEAD
 GARAGE DOOR OR THEIR REQUIRED DESIGN
 PRESSURES.
  
 8) THE NOA/EVALUATION REPORT FOR THE
 GLASS BLOCK IS MISSING.
  
 9) A PRODUCT APPROVAL FOR FIXED GLASS
 WINDOWS WAS SUBMITTED AND THERE AREN'T
 ANY SPECIFIED ON THE PLANS. PLEASE
 CLARIFY.
  
 10) THE TRUSS LAYOUTS AND DRAWINGS ARE
 REQUIRED TO HAVE THE ORIGINAL WET
 SIGNATURE OF THE TRUSS ENGINEER PER FAC
 61G15-23.002.
  
 NOTE: THE PRODUCT APPROVALS FOR THE
 6-UNIT "B" ELEVATION WERE USED FOR THIS
 REVIEW. SUBMIT COMPLETE SETS FOR EACH
 MASTER PERMIT.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2004-12-21 Cont ID  
Sent By rmcdouga Date 2004-07-29 Time 16:27 Rev Time 0.00
Received By rmcdouga Date 2004-07-29 Time 16:26 Sent To  
Notes
2004-07-29 00:00:00SEE PLAN REVIEW # 04021360 FOR COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-24 Cont ID  
Sent By dpalmer Date 2005-01-24 Time 17:05 Rev Time 0.50
Received By dpalmer Date 2005-01-24 Time 17:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-30 Cont ID  
Sent By dpalmer Date 2004-11-30 Time 07:34 Rev Time 0.33
Received By dpalmer Date 2004-11-30 Time 07:32 Sent To  
Notes
2004-11-30 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE RECEPT ON 2' OF WALL
 IN BEDRM #2, APPEARS TO BE "IN" A WALL?
 210.52
  
 2)NOTE: IT HAS COME TO OUR ATTENTION
 THE
 SEC'S ARE ACTUALLY BEING INSTALLED BY
 THE ELECTRICAL CONTRACTOR AND NOT FPL>
 IF INDEED THIS WILL BE, THEN SEC'S ARE
 TO BE SHOWN ON RISER DIAGRAM AND MUST
 MEET 310.16 2002 NEC.
  
 3)NOTE: PLEASE ALSO SEE 250.66 FOR
 SIZING OF GROUNDING ELECTRODE
 CONDUCTOR.
 THIS MAY NEED TO BE CORRECTED ON RISER
 DUE TO SEC'S CHANGES?
 SHOWN AS 1/0 NOW, WHICH IS NOT LARGE
 ENOUGH.
 PLEASE ADJUST.
  
 4)NOTE: PLEASE SEE TITLE BLOCKS FOR
 ELECTRICAL AND MECHANICAL SHEETS.
 THESE STILL INDICATE A "FIRM".
 PLEASE ADJUST TITLE BLOCK OR INCLUDE
 LICENSE # AS REQUIRED UNDER FAC
 61G15-23.002, FS 471.023.
 PLEASE SEE THIS IS REQUIRED OF OTHER
 POSSIBLE SHEETS WHEATHER OR NOT COMMENT
 OS MADE BY OTHER REVIEWER(S).
  
 5)NOTE: PLEASE SEE PLANS STILL INDICATE
 A MAIN DISC AND 8-METERS. THIS COMMENT
 WAS GIVEN ONPREVIOUS REVIEW UNDER
 #04021360 THIS DOE NOT CORRELATE WITH
 RISER.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-11-30 Cont ID  
Sent By mamini Date 2004-11-30 Time 09:03 Rev Time 0.50
Received By mamini Date 2004-11-30 Time 09:02 Sent To  
Notes
2004-11-30 00:00:00PASSED:
  
 1.SEE # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-03-02 Cont ID  
Sent By nmccray Date 2005-03-02 Time 13:59 Rev Time 0.00
Received By nmccray Date 2005-03-02 Time 13:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-21 Cont ID  
Sent By nmccray Date 2004-12-21 Time 12:07 Rev Time 0.00
Received By nmccray Date 2004-12-21 Time 11:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-09 Cont ID  
Sent By rmcdouga Date 2004-12-09 Time 07:12 Rev Time 0.00
Received By rmcdouga Date 2004-12-09 Time 07:12 Sent To  
Notes
2004-12-09 00:00:00SEE PERMIT # 04021360 FOR REVIEW NOTES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 11:57 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 11:57 Sent To  
Notes
2005-01-20 00:00:00TO "COMM BD#43/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-29 Cont ID  
Sent By mjacobs Date 2004-11-29 Time 08:13 Rev Time 0.00
Received By mjacobs Date 2004-11-29 Time 08:13 Sent To  
Notes
2004-11-29 00:00:00SENT TO COMM BD#54
 PRODUCT APPROVALS ARE ON THE S.F.R. RACK
 ABOVE ELEC.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-04 Cont ID  
Sent By pkrauss Date 2004-12-04 Time 07:58 Rev Time 0.45
Received By pkrauss Date 2004-12-04 Time 07:58 Sent To  
Notes
2004-12-04 00:00:00DENIED: 6 UNITS/A ELEVATION
 SEE COMMENT #4 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.PLANS ARE
 OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-03-11 Cont ID  
Sent By rmcdouga Date 2005-03-11 Time 07:22 Rev Time 0.00
Received By rmcdouga Date 2005-02-16 Time 18:56 Sent To  
Notes
2005-03-11 00:00:00OK PER KEN STEVENS ON 2-17-05

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-13 Cont ID  
Sent By kstevens Date 2004-12-13 Time 15:00 Rev Time 0.66
Received By kstevens Date 2004-12-13 Time 15:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-09 Cont ID  
Sent By rmcdouga Date 2004-12-09 Time 07:14 Rev Time 0.00
Received By rmcdouga Date 2004-12-09 Time 07:14 Sent To  
Notes
2004-12-09 00:00:00SEE PERMIT #04021360 FOR REVIEW COMMENTS

Review Stop Z ZONING
Rev No 3 Status P Date 2005-02-02 Cont ID  
Sent By eschneid Date 2005-02-02 Time 12:00 Rev Time 0.25
Received By eschneid Date 2005-02-02 Time 11:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2004-12-13 Cont ID  
Sent By eschneid Date 2004-12-13 Time 15:30 Rev Time 0.25
Received By eschneid Date 2004-12-13 Time 15:15 Sent To  
Notes
2004-12-13 00:00:00BUILDING EXCEEDS MAXIMUM TOWNHOUSE
 HEIGHT OF 35 FEET PER SECTION
 94-307(G)(6)C OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
 FALSE CHIMNEYS EXCEED MAXIMUM ALLOWED
 HEIGHT OF 38.5 FEET PER SECTION
 94-304(A) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-09 Cont ID  
Sent By rmcdouga Date 2004-12-09 Time 07:15 Rev Time 0.00
Received By rmcdouga Date 2004-12-09 Time 07:15 Sent To  
Notes
2004-12-09 00:00:00SEE PERMIT #04021360 FOR REVIEW NOTES