Plan Review Details - Permit 04071169
Plan Review Stops For Permit 04071169
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-04-22 Cont ID  
Sent By rmcdouga Date 2005-04-22 Time 16:22 Rev Time 0.00
Received By rmcdouga Date 2005-04-22 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-23 Cont ID  
Sent By rmcdouga Date 2005-03-23 Time 12:33 Rev Time 0.00
Received By rmcdouga Date 2005-03-23 Time 06:58 Sent To  
Notes
2005-03-23 00:00:00DENIED
  
 1) TRUSS CONNECTOR MARK 'J' ON SHEET S4
 CALLS FOR (2) HDSA. IS THIS SUPPOSE TO
 BE A SIMPSON HD5A CONNECTOR? A TWO
 MEMBER TRUSS IS SPECIFIED IN THE
 CONNECTOR SCHEDULE AT THIS LOCATION,
 HOWEVER IT IS A 4 MEMBER TRUSS. HOW WAS
 THE UPLIFT DETERMINED FOR THESE
 CONNECTORS. THE SIMPSON CATALOG LISTS A
 TENSION LOAD OF 3980# FOR ONE CONNECTOR.
  
 2) THE MG1 TRUSSES HAVE AN -1181# AT THE
 EXTERIOR WALLS. THIS EXCEEDS THE
 ALLOWABLE UPLIFT OF 990# OF THE SIMPSON
 H10 CONNECTORS THAT ARE SPECIFIED.
  
 3) THE GLASS BLOCK PRODUCT APPROVAL
 SUBMITTAL IS MISSING THE MIAMI-DADE NOA
 WITH THE INSTALLATION INSTRUCTIONS.
  
 4) THE PRODUCT APPROVAL SUBMITTAL FOR
 THE ASPHALT SINGLES IS MISSING THE
 INSTALLATION INSTRUCTIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-02-24 Cont ID  
Sent By dpalmer Date 2005-02-24 Time 17:47 Rev Time 0.30
Received By dpalmer Date 2005-02-24 Time 17:47 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-02-14 Cont ID  
Sent By mamini Date 2005-02-14 Time 09:23 Rev Time 0.50
Received By mamini Date 2005-02-14 Time 09:23 Sent To  
Notes
2005-02-14 00:00:00PASSED:
  
 1. SEE PERMIT # 04010006 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-22 Cont ID  
Sent By mwennerg Date 2005-03-22 Time 17:11 Rev Time 0.00
Received By mwennerg Date 2005-03-22 Time 17:11 Sent To  
Notes
2005-03-22 00:00:001) PLEASE BE ADVISED THAT ALL LIFE
 SAFETY MUST COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) PLANS DON'T SHOW A SMOKE DETECTOR IN
 THE MASTER BEDROOM IN UNIT 1448.
  
 3) PLEASE BE ADVISED THAT THE FIRE ALARM
 SHALL BE MONITORED BY A UL LISTED
 CENTRAL STATION SERVICE.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-27 Cont ID  
Sent By adarroug Date 2005-04-27 Time 11:20 Rev Time 0.00
Received By adarroug Date 2005-04-27 Time 11:20 Sent To B
Notes
2005-04-27 00:00:00TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-01 Cont ID  
Sent By adarroug Date 2005-04-01 Time 14:21 Rev Time 0.00
Received By adarroug Date 2005-04-01 Time 14:21 Sent To B
Notes
2005-04-01 00:00:00TO "RMCDOUGAL" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 08:18 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 08:18 Sent To  
Notes
2005-02-14 00:00:00TO "COMM" BD #60 ON RACK, 1 ROLL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2005-03-12 Time   Rev Time 0.00
Received By hmoser Date 2005-03-12 Time 08:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-26 Cont ID  
Sent By pkrauss Date 2004-08-26 Time 10:18 Rev Time 0.45
Received By pkrauss Date 2004-08-26 Time 10:18 Sent To  
Notes
2004-08-26 00:00:00PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE CEILING RADIATION
 DAMPERS ON THE JOBSITE AT THE TIME OF
 INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-04-22 Cont ID  
Sent By rmcdouga Date 2005-04-22 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2005-04-22 Time 16:23 Sent To  
Notes
2005-04-22 00:00:00PASSED BY K.STEVENS ON 3/11/05

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-14 Cont ID  
Sent By eschneid Date 2005-02-14 Time 14:48 Rev Time 0.20
Received By eschneid Date 2005-02-14 Time 14:36 Sent To  
Notes
***NONE***