| 2004-08-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04071120 |
| | ADD: 1308 CLARE AV |
| | CONT: "PLAN REIEW" |
| | CONTACT: WILSON-ROWAN |
| | TEL: (561)833-5647 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES |
| | BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'.SUBMIT A COPY OF THE 'UNITY |
| | OF TITLE' DOCUMENT SO THAT FBC TABLE 600 |
| | BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | |
| | 3)61G15-23.002 P. E.- CERTIFICATE OF |
| | AUTHORIZATION.IF PRACTICING THROUGH A |
| | DULY AUTHORIZED ENGINEERING BUSINESS, |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME AND LICENSE NUMBER, AS WELL AS, |
| | THE NAME, ADDRESS, AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. |
| | |
| | 4) PROVIDE FLOOD ZONE ELEVATION |
| | CERTIFICATE FOR NEW CONSTRUTION WITH |
| | BASE FLOOD ELEVATION, CITY CODE REQUIRES |
| | AN ADDITIONAL 6". FLOOD ZONE A9=13'-6". |
| | |
| | 5) SITE IS LOCATED IN A FIRE DISTRICT: |
| | A) NO TYPE VI CONSTRUCTION |
| | B) FBC* F102.2.4ROOF COVERINGS, ON |
| | BUILDINGS LOCATED IN THE FIRE DISTRICT, |
| | SHALL CONFORM TO THE REQUIREMENTS OF |
| | CLASS A OR B ROOF COVERINGS, AS DEFINED |
| | IN FBC 1505.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | C) FBC* F102.2.7ARCHITECTURAL TRIM, |
| | ON BUILDINGS LOCATED IN THE FIRE |
| | DISTRICT, SHALL BE CONSTRUCTED OF |
| | APPROVED NON-COMBUSTIBLE MATERIALS OR |
| | FIRE RETARDANT TREATED WOOD.ANNOTATE |
| | THE PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 6) PLANS DO NOT PROVIDE WHAT THE MINIMUM |
| | BUILDING TYPE IS? NOTE, TYPE V CONSTRUC- |
| | TION 0-3' FROM PROPERTY LINE REQUIRES A |
| | 3 HR RATINGFOR BEARING & NON-BEARING |
| | WALLS. SHEET A4 INDICATES THE BACK WALL |
| | OF THE STRUCTURE BEING A 2 HR WALL. A |
| | 3HR WALL IS REQUIRED FOR TYPE V CONSTRUC |
| | TION. PROVIDE THE EQUIVALENT THICKNESS |
| | (TABLE 709.3.1.) REPORT TO BE SUPPLIED |
| | BY THE BLOCK MANUFACTURER. |
| | |
| | 7) SHEET A5 WIND LOAD PRESSURES CHART, |
| | IF THESE PRESSURES ARE FOR THE COMPOEN- |
| | ENTS AND CLADDING SEE TABLE 1606.2B & |
| | 1606.2E. PRESSURES ARE LOW. |
| | |
| | 8) SAME SHEET INDICATES THE USE OF ROOF |
| | SCUPPERS BUT NOT OVERFLOWS. SEE SECTION: |
| | 1503.4.2 OVERFLOW DRAINS SHALL BE |
| | THE SAME SIZE AS ROOF DRAINS, INSTALLED |
| | WITH THE INLET FLOW LINE LOCATED 2" |
| | ABOVE THE LOWEST POINT OF THE ROOF LINE. |
| | OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| | 4"IN HEIGTH AND SHALL BE PLACED IN WALLS |
| | OR PARARETS WITH THE INLET FLOW LINE |
| | NOT LESS THAN 2" ABOVE THE ROOF SURFACE. |
| | |
| | 9) 1503.4.4 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. |
| | |
| | 10)1511.7 ROOF MOUNTED MECHANICAL UNIT |
| | S SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| | MECH. 301.13 WIND RESISTANCE |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUP |
| | PORTS THAT ARE EXPOSED TO WIND SHALL BE |
| | DESIGNED AND INSTALLED TO RESIST THE |
| | WIND PRESSURES ON THE EQUIPMENT & THE |
| | SUPPORTS AS DETERMINED IN ACCORDANCE |
| | WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| | LISHED BY DESIGN OR BY APPLICATION OF |
| | SECTION 301.13.1. |
| | |
| | 11)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) EXTERIOR LOUVERS |
| | B) ROOFING ASSEMBLIES, INSULATION + |
| | ROOFING MATERIALS |
| | |
| | 12) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 13)PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY THE 2001 FLORIDA ENERGY |
| | EFFICIENTCY CODE FOR BUILDING CONSTRUC- |
| | TION. |
| | |
| | 14) FBC 13-103.1.2 BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | |
| | 15) WAREHOUSE REQUIRES 2 EXITS DOESN'T |
| | MEET THE REQUIREMENTS OF 1027.1.1 FOR |
| | SINGLE EXIT. THE 2ND EXIT CAN BE THE |
| | DOORWAY BETWEEN THE WAREHOUSE AND |
| | OFFICE, IT MEETS THE REUIREMENTS OF OVER |
| | 1/2 OF THE DIAGONAL. THE EXIT SIGN SHOWN |
| | ON THE BUSINESS SIDE SHOULD BE ON THE |
| | WAREHOUSE SIDE. SEE A6. |
| | |
| | 16)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |