Plan Review Details - Permit 04071120
Plan Review Stops For Permit 04071120
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-02-28 Cont ID  
Sent By jwitmer Date 2005-02-28 Time 11:28 Rev Time 0.50
Received By jwitmer Date 2005-02-28 Time 11:28 Sent To  
Notes
2005-02-28 00:00:0002-28-05 BAR JOIST SHOP DRAWINGSOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-02-18 Cont ID  
Sent By jwitmer Date 2005-02-18 Time 09:33 Rev Time 0.33
Received By jwitmer Date 2005-02-18 Time 09:33 Sent To PC
Notes
2005-02-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071120
 ADD: 1300 CLARE AVE
 CONT:BATTEN
 TEL:(561)719-1255
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST BAR JOIST REVIEW
 ACTION: DENIED
  
 1) PLANS DO NOT HAVE THE APPROVAL OF THE
  
 DESIGN PROFESSIONAL. THE DESIGN
 PROFESSIONAL IS TO REVIEW, OK , OK WITH
 COMMENTS OR DENY BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-11-16 Cont ID  
Sent By jwitmer Date 2004-11-03 Time 07:44 Rev Time 1.11
Received By jwitmer Date 2004-11-03 Time 07:44 Sent To  
Notes
2004-11-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071120
 ADD: 1300 CLARE AVE
 CONT: BATTEN
 TEL: (561)662-0309
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 3RD REVIEW
 ACTION: REVIEWED
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-10-06 Cont ID  
Sent By jwitmer Date 2004-10-06 Time 12:35 Rev Time 2.22
Received By jwitmer Date 2004-10-06 Time 12:35 Sent To  
Notes
2004-10-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071120
 ADD: 1308 CLARE AV
 CONT: BATTEN CONSTRUCTION
 TEL: (561)662-0309
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH LOCAL AMENDMENTS
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) LEGAL ISSUES:
 A) PROVIDE DEAD SHOWING OWNERSHIP
 B) PROVIDE DOCUMENTS FOR LOT SPLIT, SEE
 PLANNING.
 C) PROVIDE UNITY OF TITLE FOR LOTS
 1,2&3.
  
 3) FROM PREVIOUS REVIEW, COMMENT# 6 DELT
 WITH THE RATING OF THE EXTERIOR WALL
 0-3' FROM THE PROPERTY LINE. FOR TYPE IV
 CONSTRUCTION THIS IS A 2 HR RATED BLOCK,
 SHEET A4 INDICATES THE USE OF UL BLOCK,
 PROVIDE THE EQUIVANT THICKNESS FOR BLOCK
 SUPPLIED BY UL. IF YOUR BLOCK IS TO BE
 SUPPLIED BY RINKER, THEN THE EQUIVALENT
 THICKNESS (TABLE 709.3.1) OF THE BLOCK
 WOULD BE SUPPLIED BY RINKER.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR LOUVERS.
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 IF THE PRODUCT APPROVALS SUBMITTED
 DO NOT HAVE "STATE APPROVAL" THEN LOCAL
 PRODUCT APPROVAL WILL BE REQUIRED.
 A) PROVIDE THE INDEPENDENT THIRD PARTY
 QUALITY ASSURANCE PRORGAM IF NOT DADE
 COUNTY NOA.
 B) FOR THE CERTIFIIED TESTING REPORT,
 THIS MUST BE A SEALED REPORT WITH
 THE 3RD PARTY QUALITY ASSURANCE
 ENTITY AND LOCAL PRODUCT APPROVAL
 COVER SHEET FILLED OUT.
  
 6)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 7)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 8) THE WAREHOUSE REQUIRES 2 MEAN OF
 EGRESS, THE EGRESS THROUGH THE DOOR# 4
 INTO THE RETAIL AREA CAN ONLY HAVE AN
 EXIT LIGHT ON THE WAREHOUSE SIDE. THE
 EXIT LIGHT ON THE RETAIL SIDE TO BE RE-
 MOVED. YOU CAN NOT TAKE A PERSON THROUGH
 A MORE DANGEROUS OCCUPANCY.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-04 Cont ID  
Sent By jwitmer Date 2004-08-04 Time 08:16 Rev Time 4.00
Received By jwitmer Date 2004-08-03 Time 16:50 Sent To  
Notes
2004-08-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071120
 ADD: 1308 CLARE AV
 CONT: "PLAN REIEW"
 CONTACT: WILSON-ROWAN
 TEL: (561)833-5647
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.SUBMIT A COPY OF THE 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 3)61G15-23.002 P. E.- CERTIFICATE OF
 AUTHORIZATION.IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS,
 THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
  
 4) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". FLOOD ZONE A9=13'-6".
  
 5) SITE IS LOCATED IN A FIRE DISTRICT:
 A) NO TYPE VI CONSTRUCTION
 B) FBC* F102.2.4ROOF COVERINGS, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS, AS DEFINED
 IN FBC 1505.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
 C) FBC* F102.2.7ARCHITECTURAL TRIM,
 ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 6) PLANS DO NOT PROVIDE WHAT THE MINIMUM
 BUILDING TYPE IS? NOTE, TYPE V CONSTRUC-
 TION 0-3' FROM PROPERTY LINE REQUIRES A
 3 HR RATINGFOR BEARING & NON-BEARING
 WALLS. SHEET A4 INDICATES THE BACK WALL
 OF THE STRUCTURE BEING A 2 HR WALL. A
 3HR WALL IS REQUIRED FOR TYPE V CONSTRUC
 TION. PROVIDE THE EQUIVALENT THICKNESS
 (TABLE 709.3.1.) REPORT TO BE SUPPLIED
 BY THE BLOCK MANUFACTURER.
  
 7) SHEET A5 WIND LOAD PRESSURES CHART,
 IF THESE PRESSURES ARE FOR THE COMPOEN-
 ENTS AND CLADDING SEE TABLE 1606.2B &
 1606.2E. PRESSURES ARE LOW.
  
 8) SAME SHEET INDICATES THE USE OF ROOF
 SCUPPERS BUT NOT OVERFLOWS. SEE SECTION:
 1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 9) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 10)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 11)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR LOUVERS
 B) ROOFING ASSEMBLIES, INSULATION +
 ROOFING MATERIALS
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 14) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 15) WAREHOUSE REQUIRES 2 EXITS DOESN'T
 MEET THE REQUIREMENTS OF 1027.1.1 FOR
 SINGLE EXIT. THE 2ND EXIT CAN BE THE
 DOORWAY BETWEEN THE WAREHOUSE AND
 OFFICE, IT MEETS THE REUIREMENTS OF OVER
 1/2 OF THE DIAGONAL. THE EXIT SIGN SHOWN
 ON THE BUSINESS SIDE SHOULD BE ON THE
 WAREHOUSE SIDE. SEE A6.
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-04-11 Cont ID  
Sent By dpalmer Date 2005-04-11 Time 15:47 Rev Time 0.75
Received By dpalmer Date 2005-04-11 Time 15:47 Sent To  
Notes
2005-04-11 00:00:00*REDLINED *
  
 NO EQUIPMENT GROUNDING CONDUCTOR FROM
 METER TO MAIN/FIRST MEANS OF DISC.
 250.6,250.24

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-01 Cont ID  
Sent By dpalmer Date 2004-11-01 Time 13:45 Rev Time 0.50
Received By dpalmer Date 2004-11-01 Time 13:45 Sent To  
Notes
2004-11-01 00:00:00**NOTES REDLINED**
  
 PLEASE SEE NEW "SHOW" WINDOW RECEPTS
 WERE ADDED TO GENERAL RECEPT CIRCUIT.
 THESE ARE REQUIRED TO BE ON A SEPARATE
 CIRCUIT. 220.12

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-23 Cont ID  
Sent By dpalmer Date 2004-09-23 Time 06:53 Rev Time 0.33
Received By dpalmer Date 2004-09-23 Time 06:43 Sent To  
Notes
2004-09-23 00:00:00**** UNSAT ****
  
 PLEASE SEE PLANS ARE COMING BACK FOR
 OTHER COMMENTS, PLEASE ADDRESS THE
 FOLLOWING AT THIS TIME.
  
 1)NOTE: PLEASE SEE NOTE FROM FIRST RE-
 -VIEW: PLEASE SEE 250.6,250.24, AN
 EQUIPMENT GROUNDING CONDUCTOR IS STILL
 SHOWN FROM METER TO FIRST MEANS OF DISC-
 -ONNECT. PLEASE SEE ABOVE CODE, ONLY
 AFTER FIRST MEANS OF DISC.
  
 2)NOTE: PLEASE SEE 250.50, FOOTER STEEL
 IS REQUIRED ALONG WITH OTHER CONNECTION
 POINTS WHERE AVAILABLE.
 PLEASE INDICATE THESE POINTS ON GROUND-
 -ING ELECTRODE DETAIL FOR POINTS OF
 ATTACHMENT FOR THIS BLDG.
 215.5
  
 3)NOTE: PLEASE SEE FLOOR PLAN INDICATES
 TWO "ELECTRICAL PANELS", ONLY ONE SHOWN
 ON RISER? (MISPRINT)
  
 4)NOTE: PLEASE SEE "SHOW WINDOW" RECEPTS
 ARE REQUIRED FOR DISPLAY/ADVERTISEMENT.
 PLEASE SHOW. 210.62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-10 Cont ID  
Sent By dpalmer Date 2004-08-10 Time 10:46 Rev Time 0.75
Received By dpalmer Date 2004-08-10 Time 10:46 Sent To  
Notes
2004-08-10 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.
  
 2)NOTE: PLEASE INCLUDE/IDENTIFY SEC'S
 IN RISER TO METER.
 215.5
  
 3)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM TO METER CAN, PLEASE SEE 250.66
 WHICH REQUIRES A MIN OF #4.
 NOTES MENTIONS #6
 GEC REQUIRED TO CWP AND FOOTER STEEL AS
 A MIN. 250.50
 PLEASE ALSO SEE NOTE #2 MENTIONS AN
 EQUIPMENT GROUNDING CONDUCTOR FROM METER
 CAN TO THE FIRST MEANS OF DISCONNECT.?
 PLEASE SEE 250.24,250.6. EQUIPMENT GRNDS
 ARE ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 4)NOTE:
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42 ETC.
 IT WAS NOTED THAT A/C LOAD WAS INDICATED
 AT 125%.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWERS AS THEY MAY HAVE AN AFFECT ON
 THE ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETED
 SETS FOR REVIEW AND STAMPING.
  
 ***PLEASE NOTE: THIS PLAN IS ONLY IN FOR
 "PLAN REVIEW" ONLY AND NOT FOR PERMIT AT
 THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2004-11-02 Cont ID  
Sent By mamini Date 2004-11-02 Time 08:59 Rev Time 0.00
Received By mamini Date 2004-11-02 Time 08:59 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2004-09-21 Cont ID  
Sent By mamini Date 2004-09-21 Time 10:44 Rev Time 0.00
Received By mamini Date 2004-09-21 Time 10:44 Sent To  
Notes
2004-09-21 00:00:00FAILED:
 1. SEE REVIEW COMMENT NO.2 DATED
 07/30/04. SUBMIT CIVIL PLANS ONLY TO THE
 PUBLIC UTILITIES AND ENGINEERING FOR
 THEIR REVIEW OF THE CONNECTIONS TO THE
 SEVICES, THIS MUST BE DONE PRIOR TO
 GETTING ENGINEERING APPROVAL FROM
 CONSTRUCTION SERVICES.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-07-30 Cont ID  
Sent By mamini Date 2004-07-30 Time 13:44 Rev Time 1.00
Received By mamini Date 2004-07-30 Time 13:42 Sent To  
Notes
2004-07-30 00:00:00FAILED:
 1. PLEASE NOTE THAT DRAINAGE MUST BE
 CALCULATED AND DESIGED FOR ENTIRE SITE,
 EXISTING MUST BE INCLUDED IN PERVIOUS &
 IMPERVIOUS AREA.
 2. PLEASE SUBMIT CIVIL PLANS ONLY TO THE
 PUBLIC UTILITIES & ENGINEERING FOR THEIR
 REVIEW AND RECORD PRIOR TO SUBMITTAL FOR
 ACTUAL PERMITTING.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-09-28 Cont ID  
Sent By mcarsill Date 2004-09-28 Time 15:33 Rev Time 0.00
Received By mcarsill Date 2004-09-28 Time 15:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-08-13 Cont ID  
Sent By mcarsill Date 2004-08-13 Time 08:07 Rev Time 0.00
Received By mcarsill Date 2004-08-13 Time 08:07 Sent To  
Notes
2004-08-13 00:00:001) LANDSCAPE BUFFER SHALL NOT INTERFERE
 WITH THE EXISTING FIRE HYDRANT. SEVEN
 AND HALF FEET IS REQUIRED TO THE FRONT
 AND SIDES OF IT. FOUR FEET TO THE
 REAR OF THEM.
  
 2) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF 6" HIGH
 LETTERS ARE REQUIRED.
  
 3) PLEASE SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING CODE.
 IF BUILDING IS LOCATED IN THE FIRE
 LIMITS, CERTAIN RESTRICTIONS WILL
 APPLY.
  
 4) PLEASE INDICATE LOCATIONS OF
 EMERGENCY LIGHT FIXTURES.
  
 5) PLEASE INDICATE LOCATIONS OF ALL
 PORTABLE FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-04-05 Cont ID  
Sent By adarroug Date 2005-04-05 Time 08:22 Rev Time 0.00
Received By adarroug Date 2005-04-05 Time 08:22 Sent To E
Notes
2005-04-05 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 10:30 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 10:30 Sent To M
Notes
2005-03-10 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 10:51 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 10:51 Sent To B
Notes
2005-02-28 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-16 Cont ID  
Sent By adarroug Date 2005-02-16 Time 13:23 Rev Time 0.00
Received By adarroug Date 2005-02-16 Time 13:23 Sent To B
Notes
2005-02-16 00:00:00TO JWITMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 11:42 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 11:42 Sent To  
Notes
2004-10-28 00:00:00TO COMM BD#60

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-20 Cont ID  
Sent By csiegber Date 2004-09-20 Time 07:55 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 07:55 Sent To  
Notes
2004-09-20 00:00:00TO COMM BD#62

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-18 Cont ID  
Sent By kstevens Date 2004-08-18 Time 13:04 Rev Time 0.00
Received By kstevens Date 2004-07-26 Time 15:21 Sent To  
Notes
2004-07-26 00:00:00TO COMM BD#12

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-03-22 Cont ID  
Sent By pkrauss Date 2005-03-22 Time 14:37 Rev Time 0.30
Received By pkrauss Date 2005-03-22 Time 14:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-11-17 Cont ID  
Sent By pkrauss Date 2004-11-17 Time 14:27 Rev Time 0.40
Received By pkrauss Date 2004-11-17 Time 14:10 Sent To  
Notes
2004-11-17 00:00:00PROVISO:
 THE DUCT SMOKE DETECTOR IS TO BE
 INSTALLED IN THE SUPPLY AIR DUCT IN
 ACCORDANCE WITH 2001 FBC(M) 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-10-08 Cont ID  
Sent By pkrauss Date 2004-10-08 Time 13:33 Rev Time 0.35
Received By pkrauss Date 2004-10-08 Time 13:21 Sent To  
Notes
2004-10-08 00:00:00DENIED:
 2ND REQUEST
 1.PLEASE PROVIDE ENERGY CALCULATIONS
 IN ACCORDANCE WITH 2001 FBC CHAPTER 13
 SUB-CHAPTER 400.
  
 2.PLANS WERE NOT SUBMITTED WITH THE
 RE-SUBMITTAL.PLEASE PROVIDE MECHANICAL
 PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-08-13 Cont ID  
Sent By pkrauss Date 2004-08-13 Time 09:45 Rev Time 0.45
Received By pkrauss Date 2004-08-13 Time 09:45 Sent To  
Notes
2004-08-13 00:00:00DENIED:
 PLEASE PROVIDE ENERGY CALCULATIONS PER
 2001 FBC CHAPTER 13 SUB-CHAPTER 400.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-19 Cont ID  
Sent By kstevens Date 2004-11-19 Time 11:28 Rev Time 1.25
Received By kstevens Date 2004-11-19 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 13:21 Rev Time 0.50
Received By kstevens Date 2004-10-09 Time 13:21 Sent To  
Notes
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 FROM PREVIOUS REVIEW: NUMBER FOR COMMENT
 WILL REMAIN THE SAME AS FIRST REVIEW TO
 AVOID CONFUSION.
  
 3) SHT A5 SUBMIT CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS PER SECT-
 IONS 1106 & 1107. SHOW SQUARE FOOTAGE OF
 THE ROOF AND 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS BEING ADDED TO
 SF OF ROOF AREA. (THIS INCLUDES THE WALL
 OF THE ADJACENT EXISTING BUILDING IF THE
 BLDGS ARE ATTACHED).
 6) SUBMIT A WATER RISER DIAGRAM REQUIRED
 BY SECTION 104.3.1.1. (NOTE: AIR CHAMB-
 ERS ARE NOT APPROVED. WATER HAMMER ARR-
 ESTORS REQUIRED BY SECTION 604.9 SHALL
 BE LOCATED IN AN EFFECTIVE RANGE PER
 PDI-WH 201 AND MANUF. INSTALLATION RE-
 QUIREMENTS.
 *********NEW COMMENT
 1B SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-18 Cont ID  
Sent By kstevens Date 2004-08-18 Time 12:45 Rev Time 1.00
Received By kstevens Date 2004-08-18 Time 12:45 Sent To  
Notes
2004-08-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A4 MINIMUM FACILITIES REQUIRES A
 DRINKING FOUNTAIN. TABLE 403.1. ALSO SEE
 SECTION 410.1. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 11-4.15 AND ALL SUBSECT-
 IONS. ALSO SEE SECTION 11-4..1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 2) SHT A4 CLEAR FLOOR SPACE IS REQUIRED
 FOR ALL ACCESSIBLE FIXTURES. 11-4.16.2
 WATER CLOSETS, 11-4.19.3 LAVS, 11-4.22.3
 TOILET ROOMS, & 11-4.24.5 SINKS SHALL
 SHOW CLEAR FLOOR SPACE TO ALLOW FORWARD
 APPROACH.
 3) SHT A5 SUBMIT CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS PER SECT-
 IONS 1106 & 1107. SHOW SQUARE FOOTAGE OF
 THE ROOF AND 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS BEING ADDED TO
 SF OF ROOF AREA. IF PRIMARY AND SECOND-
 ARY ROOF DRAINS ARE THRU THE SAME SCUPP-
 ER, THEN THE SCUPPER SHALL BE SIZED FOR
 THE TOTAL AREA REQUIRED FOR PRIMARY AND
 SECONDARY SCUPPER SIZE.
 4) SHT A10 DETAIL #2/A10 SHOW COMPLIANCE
 WITH SECTION 11-4.19.4 EXPOSED PIPES AND
 SURFACES.
 5) SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH 11-4.24 AND ALL SUBSECTIONS FOR THE
 BREAK ROOM SINK.
 6) SUBMIT A WATER RISER DIAGRAM REQUIRED
 BY SECTION 104.3.1.1. (NOTE: AIR CHAMB-
 ERS ARE NOT APPROVED. WATER HAMMER ARR-
 ESTORS REQUIRED BY SECTION 604.9 SHALL
 BE LOCATED IN AN EFFECTIVE RANGE PER
 PDI-WH 201 AND MANUF. INSTALLATION RE-
 QUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-09-23 Cont ID  
Sent By mmclean Date 2004-09-23 Time 10:28 Rev Time 0.25
Received By mmclean Date 2004-09-23 Time 10:27 Sent To  
Notes
2004-09-23 00:00:00PER G JOYCE IFSP APPROVED

Review Stop Z ZONING
Rev No 1 Status F Date 2004-07-29 Cont ID  
Sent By mmclean Date 2004-07-29 Time 11:59 Rev Time 0.00
Received By mmclean Date 2004-07-29 Time 11:59 Sent To  
Notes
2004-07-29 00:00:00PPRC ON AUG 11TH - GRACE JOYCE PLANNER
 822-1447 (PLAN & PLATS REVIEW COMMITTE)


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved