Plan Review Details - Permit 04071102
Plan Review Stops For Permit 04071102
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-08-03 Cont ID  
Sent By jwitmer Date 2004-08-03 Time 15:32 Rev Time 0.75
Received By jwitmer Date 2004-08-03 Time 15:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-08-03 Cont ID  
Sent By dpalmer Date 2004-08-03 Time 08:10 Rev Time 0.25
Received By dpalmer Date 2004-08-03 Time 08:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-09-20 Cont ID  
Sent By lmartine Date 2004-09-20 Time 15:14 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2004-09-20 00:00:00APPROVED BY M. CARSILLO 9/17/04 LM

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-08-26 Cont ID  
Sent By nmccray Date 2004-08-26 Time 15:07 Rev Time 0.00
Received By nmccray Date 2004-08-26 Time 15:07 Sent To  
Notes
2004-08-26 00:00:00************DENIED**********************
  
 NOTE:
 CHAPTER 553.80 (2) (B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION. NOTE THE
 COMMENTS LISTED BELOW AS "NOT ADDRESSED"
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE FIRE PLAN REVIEW
 OF 08-12-04:
  
 1) PLEASE INDICATE LOCATIONS OF ALL EXIT
 SIGNS, EMERGENCY LIGHTS, AND FIRE
 EXTINGUISHERS.
  
 2) BUILDING ADDRESS REGUIRED.
  
 3) PLEASE INDICATE OCCUPANY LOAD FOR THE
 BUILDING.
  
 4) PLEASE INDICATE EXIT DISCHARGE
 LOCATIONS.
  
 BY MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 ON 08-12-04561-835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-08-12 Cont ID  
Sent By csiegber Date 2004-08-20 Time 14:57 Rev Time 0.00
Received By mcarsill Date 2004-08-12 Time 16:36 Sent To  
Notes
2004-08-12 00:00:001) PLEASE INDICATE LOCATIONS OF ALL
 EXIT SIGNS, EMERGENCY LIGHTS,AND
 FIRE EXTINGUISHERS.
  
 2) BUILDING ADDRESS REQUIRED.
  
 3) PLEASE INDICATE OCCUPANT LOAD
 FOR THE BUILDING.
  
 4) PLEASE INDICATE EXIT DISCHARGE
 LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL]
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-17 Cont ID  
Sent By csiegber Date 2004-09-17 Time 09:00 Rev Time 0.00
Received By csiegber Date 2004-09-17 Time 09:00 Sent To  
Notes
2004-09-17 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-08-20 Time 14:57 Rev Time 0.00
Received By csiegber Date 2004-08-20 Time 14:57 Sent To FIRE
Notes
2004-08-20 00:00:00TO FIRE BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2004-08-12 Cont ID  
Sent By pkrauss Date 2004-08-12 Time 08:11 Rev Time 0.35
Received By pkrauss Date 2004-07-26 Time 17:05 Sent To  
Notes
2004-07-26 00:00:00TO COMM BD#53

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-12 Cont ID  
Sent By pkrauss Date 2004-08-12 Time 07:48 Rev Time 0.35
Received By pkrauss Date 2004-08-12 Time 07:42 Sent To  
Notes
2004-08-12 00:00:00PROVISO:
 1.SUPPLY AND RETURN AIR NOT INDICATED
 IN OFFICE #105.
  
 2.PLAN SHEET ME1 INDICATES THE
 ADDITION OF 2 TRANSFER GRILLES.PLAN
 DOES NOT INDICATE IF THE EXISTING RETURN
 AIR IS A PLENUM OF A DUCTED RETURN.
 PLEASE NOTE, IF RETURN IS A PLENUM NO
 COMBUSTIBLES ALLOWED IN THE RETURN AIR
 PLENUM.2001 FBC(M) 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.