Plan Review Details - Permit 04071101
Plan Review Stops For Permit 04071101
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-10-28 Cont ID  
Sent By jwitmer Date 2004-10-28 Time 14:10 Rev Time 0.75
Received By jwitmer Date 2004-10-28 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-03 Cont ID  
Sent By jwitmer Date 2004-08-03 Time 15:42 Rev Time 0.77
Received By jwitmer Date 2004-08-03 Time 15:37 Sent To  
Notes
2004-08-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071101
 ADD: 1860 N CONGRESS AV
 CONT: GATE SYSTEMS UNLIMITED
 TEL: (561)718-6975
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 (1) COPY OF DENCE DETAILIS NOT SEALED
 ENGINEERES SIGNATRE NOT SEALED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-08-03 Cont ID  
Sent By dpalmer Date 2004-08-03 Time 09:33 Rev Time 0.25
Received By dpalmer Date 2004-08-03 Time 09:32 Sent To  
Notes
2004-08-03 00:00:00CHANGE OUT OF GATE CONTROLS ONLY.
 ELECTRICAL CONT WHICH SIGNED ON IS NOT
 CURRENT AND NO ELECTRICAL # WAS GENERATE
 -D FOR THIS REASON.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-11-01 Cont ID  
Sent By nmccray Date 2004-11-01 Time 14:38 Rev Time 0.00
Received By nmccray Date 2004-11-01 Time 14:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-08-10 Cont ID  
Sent By mcarsill Date 2004-08-10 Time 14:35 Rev Time 0.00
Received By mcarsill Date 2004-08-10 Time 14:35 Sent To  
Notes
2004-08-10 00:00:001) WHAT HAPPENS WHEN LOSS OF POWER
 OCCURS TO THE GATES. ARE THEY FAIL
 SAFE OR FAIL SECURE. CAN THE GATES
 BE OPERATED MANUALLY SHOULD LOSS OF
 POWER OCCUR.
  
 2) OPENINGS THAT FIRE RESCUE ARE
 EXPECTED TO PASS THRU MUST BE AT
 LEAST 20 FEET IN CLEAR WIDTH. PLEASE
 ILLUSTRATE THIS ON THE SITE PLAN.
  
 3) KNOX-BOX KEY SWITCHES WERE NOTED
 ON THE PERMIT APPLICATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 13:58 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 13:58 Sent To  
Notes
2004-10-25 00:00:00TO COMM BD#58

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 13:51 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 13:51 Sent To  
Notes
2004-10-20 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-10 Cont ID  
Sent By mmclean Date 2004-08-10 Time 15:35 Rev Time 0.00
Received By alange Date 2004-07-26 Time 15:01 Sent To  
Notes
2004-07-30 00:00:007/26/04 TO Z
 TO COMM BD#55

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-30 Cont ID  
Sent By csiegber Date 2004-07-26 Time 15:01 Rev Time 0.00
Received By mmclean Date 2004-07-30 Time 08:15 Sent To I
Notes
2004-07-30 00:00:00NEEDS ELEC & FIRE TO REVIEW/5FT HIGH
 FENCE MM