Plan Review Details - Permit 04071089
Plan Review Stops For Permit 04071089
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-01-07 Cont ID  
Sent By alange Date 2005-01-07 Time 13:56 Rev Time 0.50
Received By alange Date 2005-01-07 Time 13:44 Sent To  
Notes
2005-01-07 00:00:00REV PAGE S-3 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-11-02 Cont ID  
Sent By alange Date 2004-11-02 Time 13:48 Rev Time 1.25
Received By alange Date 2004-11-02 Time 13:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-10-08 Cont ID  
Sent By csiegber Date 2004-10-20 Time 10:45 Rev Time 1.00
Received By alange Date 2004-10-08 Time 15:24 Sent To  
Notes
2004-10-08 00:00:00DENIED
 ITEMS FROM LAST REVIEW>
  
 2.PRODUCT APPROVALS ARE INCOMPLETE
 SEE NOTES ON PRODUCT APPROVALS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7.SIGN ENERGY CALCS SUBMITTED.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-16 Cont ID  
Sent By pkrauss Date 2004-10-05 Time 12:42 Rev Time 1.50
Received By alange Date 2004-08-16 Time 08:56 Sent To  
Notes
2004-08-16 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING, ROOFING MEMBRANE, SIMPSON
 STRAPS AND TIE DOWNS, CASEMENT WINDOW
 AND TRANSOM WINDOW.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 4.FBC 2309.6 SHOW ATTIC ACCESS AND
 SIZE.
  
 5.FBC 905.2.2SHOW ATTIC ACCESS
 COMPLYING WITH THIS SECTION.
  
 6.DETAIL S2 #5 SHOW STRAPING USED.
  
 7.SUBMIT 2 COPIES OF ENERGY CALCS
 PER FBC CHAPTER 13.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-06-14 Cont ID  
Sent By btrobaug Date 2005-06-14 Time 10:32 Rev Time 0.50
Received By btrobaug Date 2005-06-13 Time 17:43 Sent To PC
Notes
2005-06-14 00:00:00 
  
 PROVISO
 ````````````````````````````````````````
 ````````````````````````````````````````
  
 RELOCATED PANEL "H" DOES NOT APPEAR TO
 COMPLY WITH THE CLEARANCE REQUIREMENTS
 OF 110.26. THIS COULD SIMPLY BE THE WAY
 IT APPEARS ON THE DRAWING. IF IT IS IN
 FACT IN VIOLATION THE PANEL OR DRYER
 MUST BE MOVED. IF CORRECTED ACTION NEEDS
 TO BE TAKEN, RESUBMIT SAME FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-09-21 Cont ID  
Sent By btrobaug Date 2004-09-21 Time 12:16 Rev Time 0.50
Received By btrobaug Date 2004-09-21 Time 11:52 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:14 Rev Time 0.00
Received By btrobaug Date 2004-08-03 Time 07:21 Sent To P
Notes
2004-08-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED AND
 ALL EXISTING LOADS PER 215.15.
  
 2} THE RANGE CALCULATION MUST COMPLY
 WITH 220.19, 2002 NEC.
  
 3} THE SMALL APPLIANCE CALCULATION MUST
 COMPLY WITH 220.16 AND 210.11(C)(1), 20
 AMP, #12 WIRE.
  
 4} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BER ATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 5} INDICATE THE LOCATION OF THE SERVICE
 AND ALL RELATED EQUIPMENT ON DRAWINGS.
  
 6} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 7} THE DINING ROOM RECEPTACLES MUST
 COMPLY WITH 210.52(B), 20 AMP.
  
 8} SEE 220.3(B)(4) TO COMPUTE RECESSED
 LUMINAIRES. PLEASE ADD SAME TO LOAD
 CALCULATIONS, SHOW ON PLAN.
  
 9} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.FBC 905.2.2, NFPA-72 8-1.4.
  
 10} PLEASE LIST THE REQUIREDD ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 11:21 Rev Time 0.00
Received By shill Date 2005-06-08 Time 11:21 Sent To E
Notes
2005-06-08 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 14:22 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 14:22 Sent To Z
Notes
2005-03-14 00:00:00TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 12:22 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 12:22 Sent To Z
Notes
2005-02-28 00:00:00TO "Z" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 09:26 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 09:26 Sent To M
Notes
2005-01-03 00:00:00TO "M/AC" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 10:45 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 10:45 Sent To B
Notes
2004-10-20 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:14 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 15:14 Sent To E
Notes
2004-09-15 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-27 Cont ID  
Sent By csiegber Date 2004-07-27 Time 11:30 Rev Time 0.00
Received By csiegber Date 2004-07-27 Time 11:30 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-26 Cont ID  
Sent By mmclean Date 2004-07-27 Time 11:18 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 10:01 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2005-01-04 Time   Rev Time 0.00
Received By hmoser Date 2005-01-04 Time 16:53 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-10-05 Cont ID  
Sent By pkrauss Date 2004-10-05 Time 12:38 Rev Time 0.35
Received By pkrauss Date 2004-10-05 Time 12:31 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-08-13 Cont ID  
Sent By btrobaug Date 2004-09-21 Time 12:16 Rev Time 0.35
Received By pkrauss Date 2004-08-13 Time 11:35 Sent To B
Notes
2004-08-13 00:00:00DENIED:
 PLEASE PROVIDE ENERGY AND MANUAL J
 CALCULATIONS AS PER 2001 FBC CHAPTER 13
 SUB-CHAPTER 6.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-08-10 Cont ID  
Sent By btrobaug Date 2004-08-03 Time 09:08 Rev Time 0.25
Received By jleech Date 2004-08-10 Time 18:28 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2005-03-17 Cont ID  
Sent By mmclean Date 2005-03-17 Time 08:40 Rev Time 0.00
Received By mmclean Date 2005-03-17 Time 08:40 Sent To  
Notes
2005-03-17 00:00:00DENIED,
 1. MUST PULL A SEPERATE PERMIT FOR WALL,
 CANNOT BE ADDED TO A RENOVATION PERMIT
 OF A STRUCTURE.
 2. PROVIDE TWO COPY OF SITE WALL DETAIL
 AND SITE PLAN SHOWING THE LOCATION OF
 THE WALL AND UTILITY EASEMENT APPROVAL
 ATTACHED.
 3. MUST PROVIDE (2) CLEAR AND FULL SIZE
 SURVEY OF PROPERTY SHOWING THE DIMENSION
 OF LOT AND WITH THE LOCATION OF NEW
 WALKWAY WITH DIMENSION (WIDTH & LENTH).
 CALLED CONTR LEFT MSG ON VOICE MAIL
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2005-03-03 Cont ID  
Sent By mmclean Date 2005-03-03 Time 15:00 Rev Time 0.00
Received By mmclean Date 2005-03-03 Time 15:00 Sent To  
Notes
2005-03-03 00:00:00DENIED,
 1. NEED CLARIFICATION TO WHAT THE
 REVISION IS FOR.CALLED CONTR, FILE S
 FOR P/U
  
 CONTRACTOR CALLED BACK, IT'S FOR A
 PRIVACY WALL.
  
 DENIED,
 1. NEED CITY OF WEST PALM BEACH UTILITY
 DEPARTMENT EASEMENT RELEASE APPROVAL.
 INFORMED CONTRACTOR FILE S FOR P/U MM
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-27 Cont ID  
Sent By csiegber Date 2004-07-26 Time 10:01 Rev Time 0.00
Received By mmclean Date 2004-07-27 Time 11:18 Sent To I
Notes
***NONE***