| Plan Review Stops For Permit 04070992 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-09-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-09-20 |
Time |
15:49 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2004-09-20 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-07-30 |
Time |
07:11 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2004-07-30 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2004-07-30 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)SEPARATE PERMITS REQUIRED. | | | | | | 3.)A CERTIFICATE OF AUTHORIZATION IS | | | REQUIRED FOR ANDREW MORGAN SERVICES PER | | | CARRIE FLYNN OF FPBE.MR. MORGAN HAS | | | BEED ADVISED OF THIS IN WRITING FROM | | | THIS OFFICE TWICE.SEE ATTACHED. | | | FAC61G15-23.002, FS471.025. | | | | | | 4.)SPECIFY THE SLOPE FOR THE "NEW | | | ACCESSIBLE RAMP", C1, BOTTOM LEFT. | | | | | | 5.)SUBMIT PRODUCT APPROVALS FOR THE | | | MODIFIED ROOF FOR REVIEW, OR CAN BE | | | SUBMITTED WITH THE ROOF PERMIT | | | APPLICATION. | | | | | | 6.)STUCCO IN A VERTICAL APPLICATION | | | IS REQUIRED TO BE 7/8" MIN. (7-A2), | | | FBC2504.2.2, ASTMC926.CHECK ALL | | | DETAILS. | | | | | | 7.)DECLARE A BUILDING TYPE.IS THIS | | | BUILDING SPRINKLED? IF IT IS, SPRINKLERS | | | ARE REQUIRED (NOTE REQUIREMENT, IF ANY, | | | ON PLAN).IF REQUIRED, SUBMIT SPRINKLER | | | PLANS FBC104.3.1.1(5). |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-10-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-10-19 |
Time |
09:43 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-10-19 |
Time |
09:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-08-30 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-12 |
Time |
11:42 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-08-30 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2004-08-30 00:00:00 | ******** UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE NOTE FROM PREVIOUS | | | REVIEW. | | | PLEASE INCLUDE ALL INFORMATION ON TITLE | | | BLOCK PER FAC 61G15-23.002 AS REQUIRED | | | UNDER FS 471.023 | | | | | | THIS IS REQUIRED ON ALL SHEETS WHEATHER | | | OR NOT COMMENT IS MADE BY OTHER REVIEW- | | | -ERS. | | | PLEASE ALSO SEE F-1 SHEET. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-07-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-27 |
Time |
08:54 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-07-27 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2004-07-27 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE INCLUDE ALL LICENSE #'S | | | AS REQUIRED PER FAC 61G15-23.002 | | | FS 471.023. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2004-09-21 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-09-21 |
Time |
11:17 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2004-09-21 |
Time |
11:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-09-21 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-09-21 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-09-21 |
Time |
15:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2004-07-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-07-30 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-07-30 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2004-07-30 00:00:00 | 1) ALL NEW RAMPS SHALL BE EQUIPPED | | | WITH HANDRAILS ON BOTH SIDES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-10-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-12 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-12 |
Time |
11:42 |
Sent To |
E |
|
| Notes |
| 2004-10-12 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-08-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-23 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-23 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2004-08-23 00:00:00 | TO COMM BD#55 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-08-04 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-08-04 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-22 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2004-07-22 00:00:00 | TO COMM BD#42 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2004-08-23 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-08-23 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-08-23 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2004-08-23 00:00:00 | APPROVED BY RANDALL GRANBERRY, PLANNER | | | 805-1454 MM |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-08-04 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-08-04 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-07-26 |
Time |
09:34 |
Sent To |
I |
|
| Notes |
| 2004-08-04 00:00:00 | DENIED, BY RANDALL GRANBERRY, PLANNER | | | 822-1454.NEED TO PROVIDE UPDATED | | | SITEPLAN.CONTRACTOR CALLED. |
|
|