Plan Review Details - Permit 04070976
Plan Review Stops For Permit 04070976
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-08-24 Cont ID  
Sent By jwitmer Date 2004-08-24 Time 09:33 Rev Time 1.11
Received By jwitmer Date 2004-08-24 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-28 Cont ID  
Sent By jwitmer Date 2004-07-28 Time 10:48 Rev Time 1.25
Received By jwitmer Date 2004-07-28 Time 10:47 Sent To  
Notes
2004-07-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04070976
 ADD: 4415 BROADWAY AV
 CONT: PRECISION PETROLEUM INC
 TEL: (727)224-5162
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)SITE PLAN, IS NOT AN ORIGINAL,BUT A
 COPY,PLANS,SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3) SITE PLAN INDICATES THE USE OF THE
 WRONG CODES:
 A) 2002STANDARD FIRE PREVENTION CODE
 B) LOCAL PALM BEACH COUNTY CODES
 SHOULD READ:
 A) 2001 FL DLDG CODE
 B) LOCAL WEST PALM BEACH AMENDMENTS
  
 4) THERE IS NO SITE PLAN OR FLOOR PLAN
 GIVING THE LOCATION OF THE CANOPY IN RE-
 LATION TO THE PROPERTY LINE NOR TO OTHER
 BUILDINGS.
  
 5) PLANS DO NOT PROVIDE MINIMUM BUILDING
 TYPE?
  
 6) STRUCTURAL PLANS INDICATE A WIND
 DESIGN OF 123 MPH, CORRECT TO 140 HPH.
 CORREECT TO APPROPRIATE WIND ZONE. IF
 THE DESIGN IS 146/ EXPOSURE "C" THEN
 PLANS ARE TO REFLECT THIS ALSO.
  
 7) SHEET CS-1 INDICATES THE USE OF
 ACM FACIA, THERE IS NO DESCRIPTION OF
 THIS PRODUCT?
 403.3.2(2) APPROVED PLASTICS COVERED BY
 AN ALUMINIUM FACING HAVING A MINIMUM
 THICKNESS OF 0.020" OR CORROSION-RESIS-
 TANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016". THE APPROVED PLAS-
 TIC SHALL HAVE A FLAMESPREAD RATING OF
 25 OR LESS WHEN TESTED IN THE FORM
 INTENDED FOR USE IN ACCORDANCE WITH
 ASTM E 84.
 PROVIDE DOCUMENTATION OF COMPLIANCE
 WITH THIS SECTION OF THE CODE.
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2004-07-27 Cont ID  
Sent By dpalmer Date 2004-07-27 Time 13:13 Rev Time 0.25
Received By dpalmer Date 2004-07-27 Time 13:13 Sent To  
Notes
2004-07-27 00:00:00NO ELECTRICAL PLANS SUBMITTED FOR
 REVIEW. NO ELECTRICAL CONT SIGNED ON.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-10-04 Cont ID  
Sent By nmccray Date 2004-10-04 Time 09:55 Rev Time 0.00
Received By nmccray Date 2004-10-04 Time 09:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-08-10 Cont ID  
Sent By mcarsill Date 2004-08-10 Time 13:07 Rev Time 0.00
Received By mcarsill Date 2004-08-10 Time 13:06 Sent To  
Notes
2004-08-10 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY REMOVAL OF UNDERGROUND FUEL
 TANKS. PLANS MUST BE STAMPED BY PBC
 DERM PRIOR TO SUBMITTAL.
  
 2) PLEASE INDICATE FLAME SPREAD
 CRITERIA FOR NEW CANOPY.
  
 3) SEPARATE PLANS AND PEMITS REQUIRED
 FOR ANY NEW INSTALLATION FOR ANY NEW
 UNDERGROUND FUEL TANKS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-20 Cont ID  
Sent By mmclean Date 2004-08-30 Time 12:46 Rev Time 0.00
Received By csiegber Date 2004-08-20 Time 15:41 Sent To  
Notes
2004-08-20 00:00:00TO COMM BD#44

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-10 Cont ID  
Sent By csiegber Date 2004-08-20 Time 15:40 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 12:02 Sent To  
Notes
2004-07-22 00:00:00TO COMM BD#24

Review Stop Z ZONING
Rev No 2 Status P Date 2004-08-30 Cont ID  
Sent By mmclean Date 2004-08-30 Time 12:46 Rev Time 0.00
Received By mmclean Date 2004-08-30 Time 12:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-07-29 Cont ID  
Sent By mmclean Date 2004-07-29 Time 12:34 Rev Time 0.00
Received By mmclean Date 2004-07-29 Time 12:34 Sent To  
Notes
2004-07-29 00:00:00NEED TO PROVIDE SIGN & SEALED SITE PLANS
 (2 SETS) FRONT ARCHITECT BERT THOMAS.
 CALLED LEFT MSG ON VOICE MAIL.