Plan Review Details - Permit 04070958
Plan Review Stops For Permit 04070958
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-10-19 Cont ID  
Sent By alange Date 2004-10-19 Time 13:23 Rev Time 1.00
Received By alange Date 2004-10-19 Time 13:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-10-06 Cont ID  
Sent By alange Date 2004-10-06 Time 16:27 Rev Time 0.00
Received By alange Date 2004-10-19 Time 13:22 Sent To  
Notes
2004-10-06 00:00:00DENIED
 SEE #4 FROM LAST TWO REVIEWS.
 A PERMIT CANNOT BE ISSUED UNTIL ALL
 PRODUCT APPROVALS ARE SUBMITTED.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-09-16 Cont ID  
Sent By csiegber Date 2004-09-22 Time 14:33 Rev Time 1.50
Received By alange Date 2004-09-16 Time 14:43 Sent To  
Notes
2004-09-16 00:00:00DENIED
  
 ITEMS NOT ADDRESSED FROM LAST REVIEW:
  
 3.SUBMIT TWO SIGNED COPIES OF ENERGY
 CALCS.
  
 4.PRODUCT APPROVALS MISSING FOR STRAPS
 AND TIE DOWNS.ALL PRODUCT APPROVALS
 REQUIRE THE FOLLOWING.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.FBC 11-11 AT LEAST ONE BATHROOM DOOR
 SHALL HAVE A CLEAR OPENING OF 29"
 USE A 32" DOOR.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-05 Cont ID  
Sent By dpalmer Date 2004-09-16 Time 09:47 Rev Time 1.75
Received By alange Date 2004-08-05 Time 10:26 Sent To  
Notes
2004-08-05 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 4.PRODUCT APPROVALS MISSING FOR W-2
 WINDOW AND STRAPS AND TIE DOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.FBC 11-11 AT LEAST ONE BATHROOM
 DOOR SHALL HAVE A CLEAR OPENING OF 29".
  
 6.SHEATHING AT PERIMETER ZONES
 REQUIRE 4" SPACING AT THE EDGE, SHOW
 ON PLANS.
  
 7.IF THERE IS NOT A FIREPLACE BEING
 INSTALLED REMOVE DETAIL.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-06-06 Cont ID  
Sent By btrobaug Date 2007-06-05 Time 14:53 Rev Time 0.33
Received By btrobaug Date 2007-06-05 Time 14:03 Sent To P
Notes
2007-06-05 14:52:59 
  
 CALLED RICK FOR SHEET E-2.0 WILL BRING TOMORROW./WRT.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-09-22 Cont ID  
Sent By btrobaug Date 2006-09-22 Time 13:09 Rev Time 1.00
Received By btrobaug Date 2006-09-22 Time 07:19 Sent To PC
Notes
2006-09-22 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 250.52(A)(3) CONCRETE-ENCASED
 ELECTRODE.
 AN ELECTRODE ENCASED BY AT LEAST 50 MM
 (2 IN.) OF CONCRETE, LOCATED WITHIN AND
 NEAR THE BOTTOM OF A CONCRETE FOUNDATION
 OR FOOTING THAT IS IN DIRECT CONTACT
 WITH THE EARTH, ETC.IF THE SERVICE IS
 NEW THIS REQUIREMENT SHOULD HAVE BEEN
 ADDRESED WHEN FOOTER STEEL WAS
 INSTALLED. ISSUES LIKE THIS IS WHY WE
 REQUIRE THE PROPOSED WORK BE COMPLETE
 AND CORRECT ON THE PLANS SUBMITTED FOR
 REVIEW.
  
 2} THE EQUIPMENT GROUNDING CONDUCTOR
 MUST COMPLY WITH 250.66. THE NOTE ON THE
 COMMENT SHEET STATINDG THAT THE #4 IS
 "OVERSIZED" IS INCORRECT. THE LARGEST
 SERVICE ENTRANCE CONDUCTOR AS STATED IN
 250.66 IS PARALLEL 2/0. SEE EXHIBIT
 250.28 IN THE HANDBOOK FOR
 CLARIFICATION. THE DESIGNER INDICATES A
 400 AMP SERVICE IS BEING SUPPLIED. 400
 MCM WOULD BE A 1/0 GEC. IF THE EXAMPLE
 IN THE HANDBOOK IS USED, THE GEC WOULD
 BE #2CU,(133100CMX2, ROUNDED UP) THEN
 TECHNICALLY THE SERVICE IS ONLY RATED
 FOR 350 AMPS.
  
 3} THE CONDUCTOR SIZES WERE REMOVED FROM
 THE SCHEDULE, PLEASE PUT THEM BACK ON
 SOTHAT OCP AND CONDUCTOR SIZE CAN BE
 REVIEWED FOR COMPLIANCE PER 310.16.
  
 4} CIRCUIT #B5 IS MARKED AS A SMALL
 APPLIANCE CIRCUIT IN THE SCHEDULE, BUT
 IS THE BATH CIRCUIT ON TEH PLAN.
  
 5} AHU #1 IS NOT LISTED ON THE SCHEDULE.
  
 6} A/C COMPRESSER #1 IS NOT LISTED AND
 HAS THE WRONG CIRCUIT NUMBERS AT THE
 UNIT ON THE PLAN.
  
 7} PER 210.12 CIRCUIT G5 (SMOKE
 DETECTORS) MUST BE ON A AFCI. THEY
 CANNOT BE ON THE BATHROOM CIRCUIT, SEE
 210.11(C)(3).
  
 8} THE INITIALS ON THE ARCHITECTS SEAL
 IS NOT THE SAME AS THE "SIGNATURE" ON
 THE SEAL DATED 8/13/04. THE ARCHITECT
 MUST SIGN HIS SEAL PER 61G1-16.003
 FLORIDA ADMINISTRATIVE CODE. ONE SET OF
 PLANS IS BEING RETAINED BY THIS OFFICE
 WITH THIS APPARANTLY UNAUTHORIZED "
 SIGNATURE".
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-07-10 Cont ID  
Sent By btrobaug Date 2006-07-10 Time 17:10 Rev Time 1.00
Received By btrobaug Date 2006-07-07 Time 09:34 Sent To PC
Notes
2006-07-10 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE REVISED PLAN SHOWS AN EXISTING
 SERVICE THAT DOES NOT CORRELATE WITH THE
 "EXISTING SERVICE" SUBMITTED ON THE
 ORIGINAL PLAN. THIS WILL BE REVIEWED AS
 A NEW SERVICE, AND THE FOLLOWING
 COMMENTS APPLY.
 A)PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
 B) THE GROUNDING ELECTRODE MUST COMPLY
 WITH THE MINIMUM SIZE FOR THE SERVICE
 PER 250.66.
 C) THE RISER INDICATES THE MAINS IN THE
 PANELS, THE PLAN SHOWS A MAIN DISCONNECT
 AT THE METER. PLEASE INDICATE PROPOSED
 INTENTION.
 D) ALL AVAILABLE ELECTRODES MUST BE
 BONDED PER 250.50.
  
 2} INDICATE THE LOCATION OF THE PANELS
 ON THE PLAN.
  
 3} THE RISER SHOWS PANEL "A" FEEDING
 PANEL "G", BUT NOT SHOWN ON THE PANEL
 SCHEDULE.INDICATE FEEDER AND OCP SIZE IN
 THE SCHEDULE.
  
 4} THE CIRCUIT NUMBERS DESIGNATIONS ARE
 DUPLICATED IN BOTH PANELS. PLEASE USE
 PANEL DESIGNATION (1A)FOR CIRCUIT #1
 PANEL "A".
  
 5} CIRCUIT 17B AND 19A HAS AN INCORRECT
 OCP (25 AMPS), AND WIRE SIZE(#10) FOR
 THE 10300 WATT LOAD. 310.16.
  
 6} CIRCUITS 1 AND 3, PANEL "G", SAME
 COMMENT AS #5.
  
 7} THE WIRE SIZE IS TOO SMALL SMALL FOR
 THE LOAD AND OCP, CIRCUIT 2 &4, PANEL
 "G". 310.16.
  
 8} CIRCUIT #2A, PANEL"A", BATH#2 MUST
 COMPLY WITH 210.11(C)(3), IF SERVING THE
 RECEPTACLE.
  
 9) THE ELECTRICAL NOTES INDICATE A
 MINIMUM WIRE SIZE OF #12, BUT #14 IS
 SHOWN ON THE PANEL SCHEDULE IN SEVERAL
 PLACES. PLEASE ADJUST THE NOTE OR CHANGE
 THE SCHEDULE TO REFLECT THE NOTE. THIS
 IS THE SECOND TIME THIS COMMENT HAS BEEN
 MADE.
  
 10} NOTE 24 IS CODE COMPLIANT AS LONG AS
 THE CIRCUIT IS AFCI PROTECTED PER
 210.12.
  
 11} SMOKE DETECTORS ARE REQUIRED PER
 313.1 FBC.
  
 12} RECEPTACLES ARE REQUIRED WITHIN 25'
 OF THE CONDENSING UNITS PER 210.63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-09-16 Cont ID  
Sent By dpalmer Date 2004-09-16 Time 09:47 Rev Time 0.75
Received By dpalmer Date 2004-08-26 Time 12:30 Sent To B
Notes
2004-09-16 00:00:00***** NOTES REDLINED ****
  
 BATH CIRCUIT STILL SHOWN AS #14/15AMP
 CIRCUIT. PLEASE SEE 210.52D/210.11C3
  
 NOTE MENTIONS ALL WIRING TO BE MIN #12
 AND YET PANEL SCHEDULE INDICATES #14 FOR
 MANY CIRCUITS.
  
 SD'S TO NOTED TO BE ON BATH/KITCHEN LTS
 PLEASE SEE "ALL OUTLETS" IN 210.12 2002
 NEC. THIS INCLUDES SD'S.
  
  
 ** PLEASE SEE SD'D REQUIRED IN EXISTING
 BEDRMS.
  
  
  
 **REVISE BEFORE ROUGH. ***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-08-24 Time 15:35 Rev Time 0.75
Received By btrobaug Date 2004-07-26 Time 07:26 Sent To P
Notes
2004-07-28 00:00:00 
 THE PANEL SCHEDULE SHOWS EXISTING
 CIRCUITS AND THE DRAWING IS SHOWING NEW
 CIRCUITS. PLEASE CORRELATE WHAT IS
 BEING ADDED OR CHANGED.
 THE CIRCUIT NUMBERS ON THE PANEL
 SCHEDULE DO NOT MATCH THE NUMBERS ON
 THE DRAWINGS IN THE KITCHEN. IS THIS
 NEW OR EXISTING WORK?
  
 PLEASE CLARIFY THE SCOPE AND CORRELATE
 THE DRAWINGS. ALSO SEE HIGHLIGHTED
 NOTES ON SHEET E-1-0 ARE QUOTING OUT
 DATED CODES.
  
 PLEASE NOTE THAT THE ARCHITECTS
 SIGNATURE IS REQUIRED ON HIS/HER SEAL
 PER 61G116.003.INITIALS ARE NOT
 ACCEPTABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-14 Cont ID  
Sent By adarroug Date 2006-09-14 Time 11:00 Rev Time 0.00
Received By adarroug Date 2006-09-14 Time 11:00 Sent To E
Notes
2006-09-14 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 08:48 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 08:48 Sent To E
Notes
2006-06-27 00:00:00TO "BTROBAUGH" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-09-22 Cont ID  
Sent By csiegber Date 2004-09-22 Time 14:33 Rev Time 0.00
Received By csiegber Date 2004-09-22 Time 14:32 Sent To B
Notes
2004-09-22 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 15:35 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 15:35 Sent To E
Notes
2004-08-24 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-23 Cont ID  
Sent By mmclean Date 2004-08-24 Time 11:54 Rev Time 0.00
Received By csiegber Date 2004-08-23 Time 14:42 Sent To Z
Notes
2004-08-23 00:00:00TO MM RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 16:04 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 16:04 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-22 Cont ID  
Sent By mmclean Date 2004-07-22 Time 15:58 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 09:35 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-03 Cont ID  
Sent By jleech Date 2004-07-31 Time 11:03 Rev Time 0.25
Received By pkrauss Date 2004-08-03 Time 14:48 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-07-31 Cont ID  
Sent By btrobaug Date 2007-06-06 Time 12:50 Rev Time 0.33
Received By jleech Date 2004-07-31 Time 11:03 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-08-24 Cont ID  
Sent By mmclean Date 2004-08-24 Time 11:54 Rev Time 0.00
Received By mmclean Date 2004-08-24 Time 11:54 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-08-23 Time 14:42 Rev Time 0.00
Received By mmclean Date 2004-07-22 Time 15:58 Sent To I
Notes
2004-07-22 00:00:00DENIED, NEED TO PROVIDE SITE PLAN OR
 SURVEY WITH SETBACKS AND SHOWING THE
 ADDITION.CALLED CONTR


Account Summary | Usage Policy | Privacy Policy