| Plan Review Stops For Permit 04070865 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-08-11 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-08-11 |
Time |
13:53 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
2004-08-11 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-11 |
Time |
11:04 |
Rev Time |
2.50 |
| Received By |
lsmith |
Date |
2004-07-23 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2004-07-23 00:00:00 | BUILDING PLAN REVIEW | | | | | | 1. THE RIGHT ELEVATION SHOWS A 24" X | | | 36"FIRE DOOR.IT IS NOT SHOWN ON THE | | | FLOORPLAN. PLEASE CLARIFY. | | | | | | 2. SUBMIT THE FLORIDA PRODUCT APPROVALS | | | FOR THE USP STRUCTURAL COMPONENTS USED | | | IN THE HOUSE. | | | | | | 3. THE FIXED WINDOW FROM A & P CUSTOM | | | WINDOW MFG., INC. DOES NOT HAVE FLORIDA | | | PRODUCT APPROVAL.YOU WILL HAVE TO | | | SUBMIT A "SITE SPECIFIC APPLICATION" OR | | | SELECT ANOTHER SUPPLIER. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-04-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-27 |
Time |
13:19 |
Rev Time |
0.70 |
| Received By |
dpalmer |
Date |
2005-04-27 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2005-04-27 00:00:00 | ******** UNSAT ******** | | | | | | 1)NOTE: PLEASE SEE PLANS MUST CONTAIN | | | ORIGINAL SIGNATURE WHEN SIGNING AND | | | SEALING PLANS. | | | FS 481.221 | | | PLEASE SEE PLANS SUBMITTED ARE SEALED | | | PHOTOCOPIES OF SIGNED PLANS. | | | | | | 2)NOTE: PLEASE SEE RISER HAS NOW | | | COMPLETELY CHANGED FROM ORIGINAL PLANS. | | | PLEASE SEE THERE IS NO MAIN SHOWN? ETC. | | | PLEASE SEE 215.5,240.4,225.31-36,230.70 | | | 240.4 ETC. | | | | | | 3)NOTE: PLEASE SEE PANEL IS SHOWN AS MLO | | | WITH OUT ANY MAIN.225.31 ETC. | | | | | | 4)NOTE: PLEASE SEE AN EQUIPMENT | | | GROUNDING CONDUCTOR IS SHOWN FROM METER | | | TO MAIN? | | | PLEASE SEE 250.6,250.24. | | | | | | 5)NOTE: PLEASE SEE THE # OF CONDUCTORS | | | SHOWN FROM MAIN PANEL TO SUB PANEL. | | | 2-HOTS, AND ONE GROUND AS NOTED.??? | | | 215.5 | | | | | | 6)NOTE: PLEASE SEE "WHITE OUT" AND | | | HANDDRAWN CHANGES ON PLANS WHICH ARE NOT | | | PERMITTED TO SIGNED AND SEALED PLANS. | | | FS 481.221 | | | | | | 7)NOTE: PLEASE SEE ONE COPY OF PLANS | | | SUBMITTED ARE NOW BEING RETAINED FOR | | | POSSIBLE REVIEW BY THE DBPR AND STATE | | | BOARD FOR ARCHITECTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-08-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-11 |
Time |
11:04 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-08-11 |
Time |
11:04 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-07-22 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-06 |
Time |
16:47 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2004-07-22 |
Time |
16:46 |
Sent To |
M |
|
| Notes |
| 2004-07-22 00:00:00 | ************ UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN | | | ON PANEL SCHEDULE BUT NO GFI SHOWN ON | | | PLANS. | | | | | | 2)NOTE: PLEASE SEE DEDICATED CIRCUIT | | | SHOWN FOR GOLF CHARGER BUT NOT ON PANEL | | | SCHEDULE. | | | | | | 3)NOTE: PLEASE SEE 210.52D FOR MISSING | | | GFI TO BE W/IN 3' FROM LAV. | | | | | | 4)NOTE: PLEASE SEE 210.52 FOR A COUPLE | | | OF MISSING RECEPTS. | | | | | | 5)NOTE: PLEASE SEE 210.52C3,5 FOR PENIN- | | | -SULAR SPACE. | | | | | | 6)NOTE: PLEASE SEE OCP SHOWN FOR AHU #2, | | | 5.5KW W/ 50 OCP. | | | 424.3B | | | | | | 7)NOTE: PLEASE SEE 250.122 FOR SIZING | | | OF EQUIPMENT GROUNDING CONDUCTORS. | | | #4 SHOWN FOR BOTH SUB PANELS, WHICH IS | | | PERMITTED BUT OVERSIZED. THIS IS ONLY | | | A NOTE. IF SHOWN THIS SIZE ON PLAN, | | | THEN THEY WILL BE REQUIRED TO BE PUT IN. | | | | | | PLEASE PROVIDE RM DESIGNATION ON PLANS. | | | PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY | | | INSERT NEW SHEETS INTO TWO COMPLETE SETS | | | FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-04-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-25 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-25 |
Time |
10:59 |
Sent To |
E |
|
| Notes |
| 2005-04-25 00:00:00 | TO "DPALMER" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-08-06 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-06 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-06 |
Time |
16:47 |
Sent To |
E |
|
| Notes |
| 2004-08-06 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-08-03 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-07-21 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2004-07-21 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2004-07-22 00:00:00 | TO SFD RACK/E | | 2004-07-21 00:00:00 | TO Z |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-08-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2004-07-27 |
Time |
17:10 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-08-03 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2004-08-03 00:00:00 | PROVISO: | | | RETURN AIR TO BEDROOM #3 SHALL BE A | | | MINIMUM OF 9", PER THE 2001 FBC(M) 601.4 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2004-07-27 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2004-07-27 |
Time |
17:10 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2004-07-27 |
Time |
17:10 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-07-21 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-07-21 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-07-21 |
Time |
12:46 |
Sent To |
I |
|
| Notes |
|
|