Plan Review Details - Permit 04070860
Plan Review Stops For Permit 04070860
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-12-19 Cont ID  
Sent By jwitmer Date 2005-12-19 Time 07:54 Rev Time 0.33
Received By jwitmer Date 2005-12-19 Time 07:54 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-08-11 Cont ID  
Sent By jwitmer Date 2005-08-11 Time 16:10 Rev Time 0.77
Received By jwitmer Date 2005-08-11 Time 16:10 Sent To PC
Notes
2005-08-12 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 04070860
 ADD: 7115 EAGLE TERRACE
 CONT: G. W. PURUCKER
 TEL: (561)722-6109
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REV:REVIEW
 ACTION: DENIED
  
 1) PLANS FROM PARKER-YANNETTE LANDSCAPE
 ARCHITECT DOES NOT HAVE TITLE BLOCK NOR
 PRINTED NAME FOR THE PERSON SEALING THE
 DOCUMENT.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 G61G1-16 REQUIREMENTS FOR TITLE BLOCK.
  
 2) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-11-08 Cont ID  
Sent By lsmith Date 2004-11-08 Time 07:55 Rev Time 1.00
Received By lsmith Date 2004-11-08 Time 07:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-10-28 Cont ID  
Sent By lsmith Date 2004-10-28 Time 14:36 Rev Time 1.00
Received By lsmith Date 2004-10-28 Time 14:36 Sent To  
Notes
2004-10-28 00:00:00BUILDING PLAN REVIEW FAILED
  
 1. SEE ZONING NOTE ON HEIGHT OF
 FIREPLACE.
  
 2. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERKS OFFICE AND A
 COPY SUBMITTED BEFORE A PERMIT CAN BE
 ISSUED.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-09-20 Cont ID  
Sent By lsmith Date 2004-09-20 Time 13:36 Rev Time 1.00
Received By lsmith Date 2004-09-20 Time 13:35 Sent To  
Notes
2004-09-20 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. SEE ELEC. PLUMB ZONING & MECH NOTES
  
 2. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERKS OFFICE BEFORE
 A PERMIT CAN BE ISSUED.
  
 3. SECOND FIREPLACE STILL NOT SHOWN ON
 FLOOR PLAN.
  
 4. TITLE BLOCK IS STILL MISSING THE
 COMPANY'S LICENSE #.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-09 Cont ID  
Sent By jleech Date 2004-09-15 Time 20:02 Rev Time 2.00
Received By lsmith Date 2004-08-09 Time 11:42 Sent To  
Notes
2004-08-09 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. SUBMIT PRODUCT APPROVAL FOR THE FLAT
 ROOF.(FLORIDA PRODUCT APPROVAL)
  
 2. 2ND FIREPLACE NOT SHOWN ON FLOOR
 PLANPLEASE CLARIFY LOCATION.
  
 3. SUBMIT FLORIDA PRODUCT APPROVALS FOR
 THE STRUCTURAL COMPONENTS (TRUSS
 STRAPS,ETC.)
  
 4. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERK OFFICE AND A
 COPY SUBMITTED BEFORE A PERMIT CAN BE
 ISSUED.
  
 5. TITLE BLOCK MUST INCLUDE LICENSE
 NUMBER OF COMPANY & NAME & LICENSE
 NUMBER OF PERSON SEALING PLANS PER
 STATE STATUTE FAC 61GL-16.004.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS REVIEW
 805-6713

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-01-24 Cont ID  
Sent By jleahy Date 2006-01-24 Time 14:31 Rev Time 0.30
Received By jleahy Date 2006-01-24 Time 14:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-01-05 Cont ID  
Sent By dpalmer Date 2006-01-05 Time 15:31 Rev Time 0.00
Received By dpalmer Date 2006-01-05 Time 15:31 Sent To  
Notes
2006-01-05 00:00:00REV DOES NOT INCLUDE THE GENERATOR.
 MAY ONLY OBTAIN TCO UNTIL GEN PERMIT IS
 ISSUED AND FINALED.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-12-30 Cont ID  
Sent By dpalmer Date 2005-12-30 Time 06:23 Rev Time 0.00
Received By dpalmer Date 2005-12-30 Time 06:03 Sent To  
Notes
2005-12-30 00:00:00********** UNSAT **********
  
 1)NOTE: PLEASE SEE PREVIOUS NOTES DATED
 11/21/05, 10/04 ETC.
 GENERATOR WAS TO DONE UNDER A SEPARATE
 PERMIT. THIS NOTICE TO BLDG CONTRACTOR
 WAS REDLINED ON PLANS IN 10/04", AND A
 PERMIT APPLICATION FOR GENERATOR WAS NOT
 MADE UNTIL 11//05.
 IT IS THE UNDERSTANDING OF THIS OFFICE
 THAT THE GENERATOR IS ALREADY INSTALLED
 AND WIRED INTO SERVICE. PLEASE SEE FBC
 104AND FS 468 WHICH STATES WORK SHALL
 NOT COMMENCE WITH OUT THE POSTING OF
 SAID PERMIT FOR THE SCOPE OF WORK TO BE
 PERFORMED.
 PLEASE SEE A POSSIBLE 4X FEE MAY BE
 ADDED TO SAID GEN PERMIT BY INSPECTOR OR
 ELECTRICAL PLAN REVIEW FOR GEN.
  
  
 2)NOTE: PLEASE SEE PREVIOUS REVIEW WHICH
 REQUIRES ALL EQUIPMENT/HEAT LOADS FOR
 AHU SHALL BE FIGURED AT 100%.THIS IS
 DONE.PLEASE KNOW, IT IS POSSIBLE TO SHED
 THE HEAT LOAD, HOWEVER A DETAIL ON
 METHOD AND WIRING OF THIS WAS REQUIRED
 TO BE PLACED ON PLANS, WHICH IS NOT.
 702.5, 220,215.5
 *** PLEASE ALSO SEE GEN SPECS FOR MAX
 LOADING, AS LOAD AT PRESENT IS 12.91 KW
 ON A 13KW GEN. THIS CURRENTLY MAY EXCEED
 THE 80% RECOMMENDED BY MANUFACTURE.
 PLEASE SEE SPECS FOR MAX CONTINUOUS LOAD
 FOR NAT GAS AND FOR LP.
  
 3)NOTE: PLEASE SEE ORIG PLANS DID NOT
 SHOW THE LOCATION OF THE DISCONNECTING
 MEANS FOR GENERATOR. PLEASE SEE 230.72
 AND 225.34 WHICH REQUIRES ALL MAINS TO
 BE GROUPED. PLEASE SEE A MCB IN THE GEN
 PANEL WOULD MEET THIS REQUIREMENT.
 PLEASE ADJUST PLANS AND REVISE.
  
  
 ** PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-11-21 Cont ID  
Sent By dpalmer Date 2005-11-21 Time 12:33 Rev Time 0.25
Received By dpalmer Date 2005-11-21 Time 12:33 Sent To P
Notes
2005-11-21 00:00:00**** UNSAT ****
  
  
 1)NOTE: PLEASE SEE NO ELECTRICAL
 REVISION SUBMITTED INCLUDING GENERATOR
 MAY BE DONE UNTIL PERMIT IS ISSUED FOR
 GENERATOR. PLEASE SEE PLANS ARE NOW
 INLCUDING GEN, WHEN ORIGINAL PLANS
 CALLED FOR THIS BEING FUTURE.
  
 2)NOTE: PLEASE ALSO CORRELATE SIZING OF
 GEN WITH GEN PERMIT APPLICATION.
  
 3)NOTE: PLEASE PROVIDE LOAD CALCS FOR
 GEN PANEL TO INCLUDE LOADS FOR HEAT AT
 100% OR PLEASE PROVIDE A DETAIL FOR ANY
 LOAD SHEDDING WHICH MAY TAKE PLACE.
 702.5, 240.4 ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW ONCE GEN PERMIT IS ISSUED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-19 Cont ID  
Sent By dpalmer Date 2004-10-19 Time 15:06 Rev Time 0.75
Received By dpalmer Date 2004-10-19 Time 15:03 Sent To P
Notes
2004-10-19 00:00:00** NOTE **
  
 GENERATOR IS SHOWN AS FUTURE.
 THIS MUST BE PERMITTED AT TIME OF INSTA-
 -LLATION.
 PLEASE BE SURE TO VERIFY ALL REQUIRED
 CLEARENCES FOR GEN AND ANY OTHER EQUIP-
 -MENT. A/C/ ELEC ETC..

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-08-27 Cont ID  
Sent By csiegber Date 2004-10-18 Time 15:41 Rev Time 1.50
Received By dpalmer Date 2004-08-27 Time 13:41 Sent To P
Notes
2004-08-27 00:00:00********* UNSAT 2ND REVIEW ***********
  
 PLEASE SEE THERE ARE NUMEROUS NOTES FROM
 FIRST REVIEW NOT ADDRESSED.
  
  
 1)NOTE: NOTE#1 NO. PLEASE SEE FS AND FAC
 FROM PREVIOUS REVIEW.
  
 2)NOTE; NOTE#2 NO.THIS IS REQUIRED AT
 THIS TIME. 110.9,215.5
  
 3)NOTE: NOTE #3, NO
  
 4)NOTE: NOTE#4 NO.
 PLEASE SEE NO PANEL SCHEDULE WAS SHOWN.
 ALSO 230.72,230.76,230.79
  
 5)NOTE: NOTE #5 NO
  
 6)NOTE: NOTE #6 NO
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE#9 NO. PLEASE SEE LEGEND
 SHOWN DOES NOT INCLUDE EQUIPMENT GROUD-
 -ING PER 250.122
 WRONG CODE REFERENCE. WE ARE UNDER 2002
 NEC. PLANS INDICATE 1996 CODE?
  
 10)NOTE: NOTE#10 OK
  
 11)NOTE: NOTE# 11 NO.
 2002 NEC 210.12
  
 12)NOTE:NOTE #12 NO
  
 13)NOTE: NOTE #13 NO
  
 14)NOTE: NOTE #14 NO
  
 15)NOTE: NOTE #15 OK
  
 16)NOTE: NOTE #16 NO
  
 17)NOTE: NOTE #17 OK
  
 18)NOTE: NOTE #18 OK
  
 19)NOTE: NOTE #19 OK
  
 20)NOTE: NOTE #20 OK
  
 21)NOTE: NOTE #21 OK
  
 22)NOTE: NOTE #22 OK
  
 23)NOTE: NOTE #23 OK
  
 24)NOTE: NOTE #24 OK
  
 NEW NOTE:
  
 1)NOTE: PLEASE SEE NOTICED ATTACHED PER
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
 PLEASE SEE ONE COPY OF EACH SET OF PLANS
 ARE NOW BEING RETAINED FOR FILE FOR
 POSSIBLE REVIEW BY DBPR/BOARD OF ARCH'S.
 THE ABOVE IS ONLY A NOTICE AT THIS TIME.
  
 2)NOTE: PLEASE SEE A 10% RE-SUB FEE WILL
 BE DUE UPON NEXT SUBMITTAL AND MUST BE
 PAID AT THE TIME OF RE-SUB.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-08-24 Time 15:34 Rev Time 2.50
Received By dpalmer Date 2004-07-22 Time 14:32 Sent To M
Notes
2004-07-22 00:00:00************ UNSAT ********************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004,
 PLEASE INCLUDE ALL LICENSE #'S AND
 PRINTED NAMES AS REQUIRED PER ABOVE.
 PLEASE SEE FS 481.219 FOR REQUIRED LICEN
 -SE # MISSING.
 PLEASE ALSO SEE FS 481.221, MUST CONTAIN
 SIGNATURE. PLEASE SEE THAT PLANS APPEAR
 TO BE INITIALED AT THIS TIME. IF THIS
 IS ACTUAL "LEGAL" SIGNATURE, PLEASE
 PROVIDE A SIGNED,SEALED AND NOTARIZED
 LETTER STATING IT IS YOUR LEGAL SIG.
 WE WILL PLACE IN OUR SIGNATURE FILE FOR
 FUTURE REFERENCE .
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE LABEL PANELS AND LABEL
 PANELS ON PLANS. MULTIPLE PANELS ARE
 SHOWN AS BEING LEFTSIDE AND OR RIGHTSIDE
  
 4)NOTE: PLEASE SEE RISER INDICATE A
 PANEL FOR GEN PANEL, YET THERE IS NO
 PANEL SCHEDULE FOR THIS. PLEASE ALSO
 IDENTIFY ON PLANS.
 215.5
  
 5) NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC.
  
 6) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 7)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 SOME ARE REDLINED ON PLANS.
  
 8) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 SOME AREA REDLINED ON PLANS.
  
 9 )NOTE: PLEASE SHOW /CLARIFY METHOD
 OF THE EQUIPMENT GROUNDING BETWEEN
 MAIN MEANS OOF DISC AND PANELS/GUTTERS.
 250.110,250.24
 PLEASE SIZE ALL EQUIPMENT GROUNDING
 CONDUCTORS PER 250.122
  
 10)NOTE: PLEASE INDICATE ALL A/C UNITS
 ON PLANS AND DISCONNECTS PER 440.11
  
 11)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 12)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 RECESSED FIX MAY ONLY BE FIGURED IN
 GENERAL LT IF LTS ARE MIN FOR EGRESS/
 GEN LT.
  
 13)NOTE: PLEASE CORRELATE AND LABEL
 A/C UNTIS ON PANEL SCHEDULE(S).
 PLEASE SEE A COUPLE SHOWN AS SAME ??
  
 14)NOTE: PLEASE SEE 424.3B FOR MIN OVER-
 -CURRENT PROTECTION TO BE 125%.
  
 15)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN
 ON PANEL SCHEDULE BUT GFI RECEPT NOT
 LOCATED OR INDICATED ON PLANS?680
 IS THIS MASTER BATH?
  
 16)NOTE: PLEASE SEE SOME A/C UNITS LOADS
 ARE SHOWN AS 20A'S AND OCP IS 20A'S,
 PLEASE SEE LOADING OF BRKR AT 80%?
 PLEASE ALSO VERIFY AHU #4 SHOWN AS 2P20A
 IS THERE NO HEAT FOR THIS UNIT?
 PLEASE CORRELATE TOTAL A/C KW IN LOAD
 CALCULATIONS AND WHAT IS INDICATED ON
 PANELS.
 215.5
 PLEASE SEE LOAD SHOWN FOR 15KW UNIT?
 PLEASE VERIFY THIS?
  
 17)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 -S ON PLANS.
  
 18)NOTE: PLEASE SEE PLANS INDICATED 3
 GDO'S ON RIGHT-SIDE HOWEVER ONLY TWO
 ARE INDICATED ON PANEL SCHEDULE? PLEASE
 VERIFY IF THESE ARE SHARED.
  
 19)NOTE: PLEASE ALSO SEE THERE APPEARS
 TO BE DEDICATED GOLF CART CHARGER RECEPT
 -S ON GARAGE WALLS, YET THESE ARE NOT
 INDICATED ON PANEL SCHEDULES?
 PLEASE VERIFY. 215.5
  
 20)NOTE: PLEASE SEE 210.52H FOR RECEPTS
 REQUIRED IN HALLS/HALL AREAS 10' OR MORE
  
 21)NOTE: PLEASE VERIFY WASH/DRYER SHOWN
 ON SECOND FLOOR APPEARS TO BE A SINGLE
 STACKABLE UNIT? PANEL SCHEDULE INDICATE
 UNITS AS BEING SEPARATE?
  
 22)NOTE: PLEASE SEE 210.52C1, APPEARS TO
 HAVE ONE RECEPT MISSING FOR KITCHEN
 COUNTERSPACE.
  
 23)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND STAMP-
 -ING. ONE SET OF OLD MAY BE SUBMITTED
 FOR REFERENCE ONLY.
  
 24)NOTE: PLEASE SEE THERE IS NO SYMBOL
 SCHEDULE/LIST SHOWN.
  
 *** NOTE***
 PLEASE SEE NO OTHER LV IS SHOWN ON PLANS
 ONLY CATV AND PHONE AT THIS TIME.
 PLEASE KNOW IF THERE IS GOING TO BE ANY
 OTHER LV EXCLUDING LV FOR ALARM SYSTEM,
 IT MAY BE INCLUDED ON THESE PLANS. (IE)
 SOUND LV, ETC. IF NOT SHOWN ON THESE
 PLANS, SEPARATE PLANS AND PERMIT WILL
 BE REQUIRED. IF SHOWN: IT WILL BE PART
 OF ELECTRICAL CONTRACTOR'S PERMIT WHICH
 IS SIGNED ON THIS PERMIT APPLICATION.
 **THIS IS ONLY A NOTE***
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-01-04 Cont ID  
Sent By adarroug Date 2006-01-04 Time 09:50 Rev Time 0.00
Received By adarroug Date 2006-01-04 Time 09:49 Sent To Z
Notes
2006-01-04 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 09:01 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 09:01 Sent To E
Notes
2005-12-29 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-12-19 Cont ID  
Sent By adarroug Date 2005-12-19 Time 14:06 Rev Time 0.00
Received By adarroug Date 2005-12-19 Time 14:06 Sent To Z
Notes
2005-12-19 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 11:22 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 11:22 Sent To E
Notes
2005-11-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 08:36 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 08:36 Sent To B
Notes
2005-08-08 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-07-25 Cont ID  
Sent By adarroug Date 2005-07-25 Time 13:31 Rev Time 0.00
Received By adarroug Date 2005-07-25 Time 13:31 Sent To P
Notes
2005-07-25 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-11-02 Cont ID  
Sent By csiegber Date 2004-11-02 Time 08:31 Rev Time 0.00
Received By csiegber Date 2004-11-02 Time 08:31 Sent To Z
Notes
2004-11-02 00:00:00TO MM RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-18 Cont ID  
Sent By csiegber Date 2004-10-18 Time 15:41 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 15:41 Sent To E
Notes
2004-10-18 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-05 Cont ID  
Sent By mmclean Date 2004-10-15 Time 16:46 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 11:06 Sent To Z
Notes
2004-10-05 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 15:34 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 15:34 Sent To E
Notes
2004-08-24 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-23 Cont ID  
Sent By mmclean Date 2004-08-24 Time 11:43 Rev Time 0.00
Received By csiegber Date 2004-08-23 Time 16:41 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-09 Cont ID  
Sent By mmclean Date 2004-07-21 Time 12:30 Rev Time 0.00
Received By lsmith Date 2004-07-21 Time 09:09 Sent To  
Notes
2004-07-22 00:00:00TO SFD RACK/E
2004-07-21 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-10-27 Cont ID  
Sent By pkrauss Date 2004-10-27 Time 09:19 Rev Time 0.35
Received By pkrauss Date 2004-10-27 Time 07:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-09-20 Cont ID  
Sent By kstevens Date 2004-10-22 Time 07:59 Rev Time 0.30
Received By pkrauss Date 2004-09-20 Time 11:41 Sent To  
Notes
2004-09-20 00:00:00DENIED:
 SEE COMMENTS FROM 1ST REVIEW.NOTHING
 ADDRESSED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-08-07 Cont ID  
Sent By dpalmer Date 2004-07-22 Time 15:25 Rev Time 1.25
Received By rregueir Date 2004-08-07 Time 08:53 Sent To P
Notes
2004-08-07 00:00:00-----------------DENIED-----------------
 1.SHOW AREAS BEING SERVED BY MINI-SPLIT
 A/C SYSTEMS, SHOW EQUIP. ON SCHEDULE
 2.MASTER BATH: EF REQUIRED AT EACH WATER
 CLOSET AND SHOWER/BATH AREA
 3.AHU'S IN ATTIC TO BE MIN 6' FROM ATTIC
 ACCESS PER FBC CH 13 SEC
 610.1.ABC.3.5.2
 4.DRYER EXHAUST AND WATER HEATER VENTS
 REQUIRED (NOT SHOWN ON PLAN).
 5.COMBUSTION AIR REQUIRED IN LAUNDRY
 IF DRYER IS GAS (NOT INDICATED ON
 PLAN).
 6.BEDROOM #2 SUPPLY DUCT SIZE NOT SHOWN.
  
 ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561-805-6734

Review Stop P PLUMBING
Rev No 6 Status P Date 2005-12-10 Cont ID  
Sent By kstevens Date 2005-12-10 Time 13:55 Rev Time 1.00
Received By kstevens Date 2005-12-10 Time 13:55 Sent To B
Notes
2005-12-10 00:00:00REVISION OK - VENT REQUIRED FOR FUTURE
 WASH MACHINE

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-08-06 Cont ID  
Sent By jleech Date 2005-08-06 Time 11:30 Rev Time 0.75
Received By jleech Date 2005-08-06 Time 11:30 Sent To B
Notes
2005-08-06 00:00:00DENIED;
 1.RISER DIAGRAM IS NOT TO CODE AND
 DOESNOT MATCH FLOOR PLAN. SEE ONE PLAN
 MARKED IN RED.
 2.W/M REQUIRED TO TIE INTO STACK BELOW
 L/T. MISSING BIDET AND W/C IN MASTER
 BATHROOM,1/2 BATH IS NOT NEXT TO MASTER
 BATH.HORIZONTAL DRY VENT ARE NOT
 PERMITED SEC.905.3 . MANY FIXTURES ARE
 NOT VENTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-11-05 Cont ID  
Sent By kstevens Date 2004-11-05 Time 14:07 Rev Time 0.50
Received By kstevens Date 2004-11-05 Time 14:06 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-10-22 Cont ID  
Sent By kstevens Date 2004-10-22 Time 07:12 Rev Time 1.25
Received By kstevens Date 2004-10-21 Time 19:03 Sent To M
Notes
2004-10-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 PLUMBING
  
 1) SHT A8 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) MASTER BATH CROSS FITTING NOT APPRO-
 VED AT WATER CLOSET. SECTION 706.1
 B) SINK SHALL DISCHARGE DOWNSTREAM OF
 THE HORIZONTAL DRY VENT FOR THE POWDER
 ROOM. SECTION 909.1
 C) WASH MACHINE AND LAUNDRY SINK SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT FOR BATH #3. SECTION 909.1
 D) WASH MACHINE SHALL CONNECT TO THE
 STACK BELOW THE TUB AT THE SECOND FLOOR.
 SECTION 901.2
 2) SEE ATTACHED SHEETS SHOWING EXAMPLE
 OF RISER DIAGRAM SECTIONS THAT MEET CODE
 REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-09-15 Cont ID  
Sent By dpalmer Date 2004-10-19 Time 15:06 Rev Time 0.50
Received By jleech Date 2004-09-15 Time 20:02 Sent To B
Notes
2004-09-15 00:00:00DENIED;
 SEE ELECTRICAL PLAN REVIEW NOTE# 1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-10 Cont ID  
Sent By dpalmer Date 2004-08-27 Time 13:41 Rev Time 0.75
Received By jleech Date 2004-08-10 Time 17:18 Sent To  
Notes
2004-08-10 00:00:00DENIED;
 RISER DIAGRAM IS NOT TO CODE SEE CORREC-
 TION MARKED IN RED.
 SEE ELECTRICAL NOTE # 1
 PLUMBING PLANN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 5 Status P Date 2005-12-14 Cont ID  
Sent By gjoyce Date 2005-12-14 Time 10:34 Rev Time 0.00
Received By gjoyce Date 2005-12-14 Time 10:34 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2004-11-05 Cont ID  
Sent By mmclean Date 2004-11-05 Time 16:58 Rev Time 0.00
Received By mmclean Date 2004-11-05 Time 13:03 Sent To B
Notes
2004-11-05 00:00:00SPOKE WITH MITCH MILLER REGARDING NEW
 RIGHT & LEFT ELEVATION TO BE PROVIDED
 SHOWING THE REDUCTION OF CHIMENY/HOUSE.
 CALLED MR. MILLER, WILL FAX INFORMATION
 DO NOT ISSUE UNTIL ZONING SIGNS OFF &
 INFORMATION PROVIDED.PLANS GIVEN TO
 LUIS MARTINEZ MM
 GIVEN TO LEA SMITH

Review Stop Z ZONING
Rev No 3 Status F Date 2004-10-15 Cont ID  
Sent By mmclean Date 2004-10-15 Time 16:46 Rev Time 0.00
Received By mmclean Date 2004-10-15 Time 16:46 Sent To I
Notes
2004-10-15 00:00:00DENIED, CHIMNEY IS OVER THE HEIGHT REQ
 THE HEIGHT MUST BE 33FT AND PLANS SHOWS
 35FT IN HEIGHT.CALLED MARK LEFT MSG
 ON VOICE MAIL. MM

Review Stop Z ZONING
Rev No 2 Status F Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-10-05 Time 11:06 Rev Time 0.00
Received By mmclean Date 2004-08-24 Time 11:43 Sent To I
Notes
2004-08-24 00:00:00DENIED, OVER THE HEIGHT OF 33FT. CALLED
 MARK LEFT MSG ON VOICE MAIL.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-08-23 Time 16:41 Rev Time 0.00
Received By mmclean Date 2004-07-21 Time 12:30 Sent To I
Notes
2004-07-21 00:00:00DENIED, OVER THE HEIGHT REQUIREMENT OF
 33FT. CALLED CONTR NO ANSWER, NO VOICE
 MAIL 2X.
  
 MUST PULL SEPARATE PERMIT FOR POOL &
 WALL.