Plan Review Details - Permit 04070859
Plan Review Stops For Permit 04070859
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-04 Cont ID  
Sent By pkrauss Date 2004-08-02 Time 15:55 Rev Time 2.66
Received By alange Date 2004-08-04 Time 14:39 Sent To  
Notes
2004-08-04 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 4.PRODUCT APPROVALS REQUIRED FOR
 STRAPS AND TIEDOWNS, AND EXTERIOR DOORS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.FBC 2309.6 SHOW ATTIC ACCESS SIZE.
  
 6.BUILDING IS IN A FLOOD ZONE.
 SUBMIT AN ELEVATION CERTIFICATE AND
 SHOW ELEVATION OF FINISH FLOOR.
  
 7.ENERGY CALCS "R" VALUES DONT MATCH
 THAT ON PLANS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-30 Cont ID  
Sent By csiegber Date 2004-07-22 Time 09:39 Rev Time 0.50
Received By btrobaug Date 2004-07-29 Time 15:50 Sent To P
Notes
2004-07-29 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE PER 210.11C3.
  
 2} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 3} A RECEPTACLE IS REQUIRED IN BEDROOM
 #4 PER 210.52(A)(1).
  
 4} PLEASE SEE MISSING RECEPT REQUIRED
 FOR A/C EQUIPMENT PER 210.63.
  
 5} THE DISCONNECTS FOR THE CONDENSING
 UNITS ARE NOT IN CLEARANCE REQUIREMENTS
 OF ATRICLE 110.26.
  
 ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPON-SIBLE FOR THE DESIGN. SECTION
 104.2.1.
 SEE ELECTRICAL PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 09:39 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 09:39 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-21 Cont ID  
Sent By mmclean Date 2004-07-21 Time 14:40 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 09:06 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-02 Cont ID  
Sent By jleech Date 2004-07-31 Time 10:22 Rev Time 0.40
Received By pkrauss Date 2004-08-02 Time 15:13 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-07-31 Cont ID  
Sent By btrobaug Date 2004-07-30 Time 10:56 Rev Time 0.25
Received By jleech Date 2004-07-31 Time 10:22 Sent To M
Notes
2004-07-31 00:00:00NO RISER DIAGRAM, UNABLE TO DO PLAN
 REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 09:06 Rev Time 0.00
Received By mmclean Date 2004-07-21 Time 14:40 Sent To I
Notes
2004-07-21 00:00:00DENIED, NEED TO SHOW THE ADDITION ON
 SURVEY WITH SETBACKS.CALLED MARK &
 LEFT MSG