Plan Review Details - Permit 04070844
Plan Review Stops For Permit 04070844
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-04-04 Cont ID  
Sent By jwitmer Date 2005-04-04 Time 07:22 Rev Time 1.11
Received By jwitmer Date 2005-04-04 Time 07:22 Sent To PC
Notes
2005-04-04 00:00:00REVISIONS- 3/17/05JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-02-07 Cont ID  
Sent By jwitmer Date 2005-02-07 Time 09:35 Rev Time 0.77
Received By jwitmer Date 2005-02-07 Time 09:35 Sent To  
Notes
2005-02-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04070844
 ADD: 818 SOUTHERN BLVD
 CONT: RESTORATION TECHNOLOGIES
 TEL: (954) 485-8600
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION DATED 1/27/05 REVIEW
  
 ACTION: DENIED
  
 1) ARCHITECT INDICATES NO CHANGE TO
 STRUCTURAL NOR MEANS OF EGRESS. PLANS
 INDICATE THAT THE EXISTING STAIRS ARE
 REMOVED, THE OVERHEAD DOOR REMOVED,
 SIDE DOOR REMOVED, DRIVE UP WINDOW
 REMOVED, AND A REPOSITIONED REAR DOOR,
 PLANS ALSO SHOW EXISTING BATHROOMS WHERE
  
 THE STAIRS ARE BEING REMOVED!
  
 2) WHAT IS HAPPENING TO THE AREA SERVED
 BY THE STAIRWAY?
  
 3) 1025.1 MERCANTILE THIS UNIT DOES NOT
 CONFORM TO THE REQUIREMENTS OF A SINGLE
 EGRESS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-12-16 Cont ID  
Sent By jwitmer Date 2004-12-16 Time 14:44 Rev Time 0.50
Received By jwitmer Date 2004-12-16 Time 14:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-12-02 Cont ID  
Sent By jwitmer Date 2004-12-02 Time 12:08 Rev Time 0.25
Received By jwitmer Date 2004-12-02 Time 12:08 Sent To PC
Notes
2004-12-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04070844
 ADD: 818 SOUTHERN BLVD
 CONT: RESTORATION TECHNOLGIES
 TEL: (954)583-9990
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4THREVIEW
 ACTION: REVIEWED
  
 BUILDING PANS ARE CODE COMPLIANT, SEE
 COMMENTS FROM OTHER REVIEWERS
 CONCERNING
 REQUIRED INFORMATION IN THE TITLE
 BLOCK.
  
 PLANS ARE MISSING THE LICENSE # OF THE
 FIRM. FL S S 481.219
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-10-06 Cont ID  
Sent By jwitmer Date 2004-10-06 Time 09:21 Rev Time 0.00
Received By mjacobs Date 2004-11-24 Time 16:47 Sent To  
Notes
2004-10-06 00:00:00BUILDING PLANS ARE CODE COMPLIANT, SEE
 ELEC COMMENTS ABOUT MISSING LICENSE#
 FOR FIRM, FL SS 481.219.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-27 Cont ID  
Sent By jwitmer Date 2004-07-27 Time 16:10 Rev Time 1.77
Received By jwitmer Date 2004-07-27 Time 16:10 Sent To  
Notes
2004-07-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04070844
 ADD: 818 SOUTHERN BLVD.
 CONT: RESTORATION TECHNOLOGIES OF
 INDIANA, INC.
 TEL: (954)485-8600
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 " NO RUBBER STAMPS"
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) SHEET A-3 INDICATES THE USE OF
 VARIOUS CEILING HUNG UNITS, DO THESE
 CREATE AN ADDITIONAL LOADTO BE HUNG FROM
 THE BAR JOIST?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2005-09-08 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 20:51 Rev Time 0.30
Received By dpalmer Date 2005-09-08 Time 20:51 Sent To  
Notes
2005-09-08 00:00:00REVISED SHEET E-4

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2005-08-16 Cont ID  
Sent By dpalmer Date 2005-08-16 Time 12:34 Rev Time 0.00
Received By dpalmer Date 2005-08-16 Time 12:33 Sent To  
Notes
2005-08-16 00:00:00RE-STAMPED FOR LOST PLANS.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 10:08 Rev Time 0.50
Received By dpalmer Date 2005-07-06 Time 10:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-06-15 Cont ID  
Sent By dpalmer Date 2005-06-15 Time 19:56 Rev Time 0.25
Received By dpalmer Date 2005-06-15 Time 19:56 Sent To  
Notes
2005-06-15 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE SEE NOTES FROM JULY 2004
 WHICH REQUESTED ALL CIRCUITING TO BE
 SHOWN ON PLANS AND TO CORRELATE WITH A
 PANEL SCHEDULE(S) TO BE SUBMITTED.
 PLEASE SEE IN A CONDITION SET UP BY
 ARCHITECT, A NOTE WAS PLACED ON PLANS TO
 HAVE THIS INFORMATION SUBMITTED TO
 ARCHITECT AND THEN SUBMITTED TO THE CITY
 FOR PLAN REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESIATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-03-17 Cont ID  
Sent By dpalmer Date 2005-03-17 Time 08:49 Rev Time 0.25
Received By dpalmer Date 2005-03-17 Time 08:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-02-08 Cont ID  
Sent By dpalmer Date 2005-02-08 Time 16:57 Rev Time 0.30
Received By dpalmer Date 2005-02-08 Time 16:57 Sent To  
Notes
2005-02-08 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS PLANS ARE SHOWN WITH SOME MAJOR
 CHANGES.
  
 2)NOTE: PLEASE SEE FIRST THREE ORIGINAL
 REVIEWS REQUESTING ALL LICENSE
 INFORMATION ON TITLE BLOCKS FOR ARCH
 FIRM.
 ON THE 4TH REVIEW THE THE FIRM WAS
 REMOVED AND TITLE BLOCK WAS CHANGED OVER
 TO THE INDIVIDUAL ARCH.
 PLANS ARE NOW COMING BACK IN FOR
 REVISIONAND TITLE BLOCKS ARE LISTING
 THE ARCH FIRM ONCE AGAIN W/ OUT
 PROVIDING LICENSE INFORMATION AS
 REQUIRED UNDER FAC 61G1-16.004 AND FS
 481.219. ONE SET OF PLANS IS NOW BEING
 RETAINED TO BE TURNED OVER TO DBPR AND
 STATE BOARD OF ARCH FOR REIVEW.
  
 3)NOTE: PLEASE SEE ALL REVISIONSARE TO
 BE CLEARLY INDICATED WITH
 CLOUDS/TRIANGLES AND LISTED IN TITLE
 BLOCK.
  
 THE ABOVE COMMENTS ARE FOR ALL TRADES
 AND FOR ALL SHEETS WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-12-16 Cont ID  
Sent By dpalmer Date 2004-12-16 Time 14:58 Rev Time 0.25
Received By dpalmer Date 2004-12-16 Time 14:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-11-29 Cont ID  
Sent By dpalmer Date 2004-11-29 Time 07:31 Rev Time 0.30
Received By dpalmer Date 2004-11-29 Time 07:27 Sent To  
Notes
2004-11-29 00:00:00************* UNSAT 3RD REVIEW ********
  
 **PLEASE SEE THESE ARE THE SAME NOTES AS
 PREVIOUS REVIEW.
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 ALL REQUIRED INFORMATION IN TITLE
 BLOCK.
 PLEASE SEE PLANS ARE STILL MISSING
 LICENSE # FOR FIRM. FS 481.219.
 THIS REQUIRES A CERTIFICATE OF
 AUTHORIZATION FOR FIRM.
 THIS IS REQUIRED ON ALL SHEETS FOR ALL
 TRADES WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWER(S).
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 TRADES WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 17:24 Rev Time 0.25
Received By dpalmer Date 2004-09-21 Time 17:24 Sent To  
Notes
2004-09-21 00:00:00******* UNSAT 2ND REVIEW **********
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 ALL REQUIRED INFORMATION IN TITLE
 BLOCK.
 PLEASE SEE PLANS ARE STILL MISSING
 LICENSE # FOR FIRM. FS 481.219.
 THIS IS REQUIRED ON ALL SHEETS FOR ALL
 TRADES WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWER(S).
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 TRADES WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-27 Cont ID  
Sent By dpalmer Date 2004-07-27 Time 13:26 Rev Time 0.33
Received By dpalmer Date 2004-07-27 Time 13:26 Sent To  
Notes
2004-07-27 00:00:00********** UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS CONTAIN A
 "RUBBER STAMP" FOR SIGNATURE OF ARCH.
 PLEASE SEE FS 481.221 , PLANS ARE
 REQUIRED TO HAVE AN ORIGINAL SIGNATURE.
  
 2)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 MISSING INFORMATION REQUIRED ON TITLE
 BLOCK FOR ARCH/ARCH FIRM.
 PLEASE ALSO SEE FS 481.219 FOR REQUIRED
 FIRM LICENSE #.
  
 3)NOTE: PLEASE SHOW MIN CIRCUITS FOR NEW
 ITEMS SHOWN ON PLANS. PLEASE CORRELATE
 CIRCUITS WITH PANEL SCHEDULE(S) TO BE
 SUBMITTED.
  
 4)NOTE: PLEASE SEE 210.62 FOR SHOW WIND-
 -OW RECEPTS.
  
 5)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600.5
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS MAY BE SUBMITTED
 FOR REFERENCE ONLY AND MAY BE REQUIRED
 BY ONE OR MORE PLAN REVIEWERS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-03-31 Cont ID  
Sent By mwennerg Date 2005-03-31 Time 11:12 Rev Time 0.00
Received By mwennerg Date 2005-03-31 Time 11:12 Sent To  
Notes
2005-03-31 00:00:001) PLEASE SEE LAST FIRE REVIEW FROM
 3/2/05.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-03-02 Cont ID  
Sent By nmccray Date 2005-03-02 Time 13:20 Rev Time 0.00
Received By nmccray Date 2005-03-02 Time 13:16 Sent To  
Notes
2005-03-02 00:00:00PROVISO:
  
 DEMOLITION, RENOVATION, AND CONSTRUCTION
 TO COMPLY WITH NFPA 241. ALL DEBRIS
 SHALL BE REMOVED FROM THE STORE DAILY.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-10-01 Cont ID  
Sent By mcarsill Date 2004-10-01 Time 13:47 Rev Time 0.00
Received By mcarsill Date 2004-10-01 Time 13:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-07-30 Cont ID  
Sent By mcarsill Date 2004-07-30 Time 09:48 Rev Time 0.00
Received By mcarsill Date 2004-07-30 Time 09:30 Sent To  
Notes
2004-07-30 00:00:001) CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2) WILL THE STORE REMAIN OPEN DURING
 REMODELING.
  
 3) GASOLINE POWERED EQUIPMENT SHALL
 NOT BE USED WITHOUT PROPER
 VENTILATION TO AVOID CARBON MONOXIDE
 BUILD-UP.
  
 4) IF STORE REMAINS OPEN ALL EXITS
 SHALL REMAIN CLEAR AND UNOBSTRUCTED.
  
 5) DEBRIS SHALL BE REMOVED FROM THE
 STORE DAILY.
  
 6) NON FIRE RETARDANT VISQUEEN SHALL
 BE USED.
  
 7) NO TRIPPING HAZARDS SHALL BE
 ALLOWED DURING CONSTRUCTION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 09:06 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 09:06 Sent To E
Notes
2005-09-07 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 09:42 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 09:42 Sent To B
Notes
2005-08-16 00:00:00TO "JWITMER" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-07-01 Cont ID  
Sent By adarroug Date 2005-07-01 Time 17:43 Rev Time 0.00
Received By adarroug Date 2005-07-01 Time 17:43 Sent To E
Notes
2005-07-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 12:06 Rev Time 0.00
Received By shill Date 2005-06-10 Time 12:06 Sent To E
Notes
2005-06-10 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-04-06 Cont ID  
Sent By adarroug Date 2005-04-06 Time 14:44 Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 14:44 Sent To FIRE
Notes
2005-04-06 00:00:00TO "F" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-16 Cont ID  
Sent By adarroug Date 2005-03-16 Time 14:51 Rev Time 0.00
Received By adarroug Date 2005-03-16 Time 14:51 Sent To  
Notes
2005-03-16 00:00:00TO "COMM" BD#30

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-02-04 Cont ID  
Sent By adarroug Date 2005-02-04 Time 08:36 Rev Time 0.00
Received By adarroug Date 2005-02-04 Time 08:36 Sent To  
Notes
2005-02-04 00:00:00TO COMM BOARD/ #27/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-12-09 Cont ID  
Sent By mjacobs Date 2004-12-09 Time 11:44 Rev Time 0.00
Received By mjacobs Date 2004-12-09 Time 11:44 Sent To  
Notes
2004-12-09 00:00:00SENT TO COMM BD#5

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-24 Cont ID  
Sent By mjacobs Date 2004-11-24 Time 16:48 Rev Time 0.00
Received By mjacobs Date 2004-11-24 Time 16:48 Sent To  
Notes
2004-11-24 00:00:00SENT TP COMM BD#19

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-08 Cont ID  
Sent By csiegber Date 2004-11-08 Time 10:45 Rev Time 0.00
Received By csiegber Date 2004-11-08 Time 10:45 Sent To P
Notes
2004-11-08 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-09-14 Time 16:01 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 16:01 Sent To  
Notes
2004-09-14 00:00:00TO COMM BD#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-06 Cont ID  
Sent By alange Date 2004-08-06 Time 14:53 Rev Time 0.00
Received By alange Date 2004-07-21 Time 09:44 Sent To  
Notes
2004-07-21 00:00:00TO COMM BD#46

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2004-12-17 Cont ID  
Sent By pkrauss Date 2004-12-17 Time 12:35 Rev Time 0.35
Received By pkrauss Date 2004-12-17 Time 12:35 Sent To  
Notes
2004-12-17 00:00:00NO MECHANICAL WORK REQUIRED AT THIS
 LOCATION PER ARCHITECT/ENGINEER.
 MECHANICAL PLANS WERE INADVERTENTLY
 SUBMITTED, DO NOT BELONG WITH THIS
 PROJECT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-12-01 Cont ID  
Sent By pkrauss Date 2004-12-01 Time 07:54 Rev Time 0.35
Received By pkrauss Date 2004-12-01 Time 07:42 Sent To  
Notes
2004-12-01 00:00:00DENIED:
 1.PREVIOUS COMMENTS FROM REVIEW DATED
 10-6-04 WERE NOT ADDRESSED.SEE
 ATTACHED.
  
 2.M-1 SHEET WAS REMOVED FROM THE
 LATEST SUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-10-07 Cont ID  
Sent By pkrauss Date 2004-10-06 Time 17:53 Rev Time 0.50
Received By pkrauss Date 2004-10-06 Time 17:49 Sent To  
Notes
2004-10-06 00:00:00DENIED:
 SEE COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.SHOW COMPLIANCE
 WITH FS 481.219AND THE FAC 61G1-16.004
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-02 Cont ID  
Sent By hmoser Date 2004-08-02 Time 09:33 Rev Time 0.50
Received By hmoser Date 2004-08-02 Time 09:32 Sent To  
Notes
2004-08-02 00:00:00PASS PRIVISO
 1) PLEASE REFER TO SECTION 601.4
 FLORIDA BUILBING CODE M BALANCED
 RETURN AIR.
 PLAN REVIEW BY HAROLD MOSER

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-01-07 Cont ID  
Sent By jleech Date 2005-01-07 Time 10:04 Rev Time 0.25
Received By jleech Date 2005-01-07 Time 10:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-12-28 Cont ID  
Sent By kstevens Date 2004-12-28 Time 10:10 Rev Time 0.50
Received By kstevens Date 2004-12-28 Time 10:10 Sent To  
Notes
2004-12-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 FROM PREVIOUS REVIEWS:
 SUBMIT A DETAIL FOR THE WATER HEATER
 SHOWING THERMAL EXPANSION CONTROL PER
 SECTION 607.3.2
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-24 Cont ID  
Sent By kstevens Date 2004-11-24 Time 16:19 Rev Time 0.60
Received By kstevens Date 2004-11-24 Time 16:19 Sent To I
Notes
2004-11-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW: SUBMIT A DETAIL
 FOR THE WATER HEATER SHOWING THERMAL
 EXPANSION CONTROL PER SECTION 607.3.2.
  
 FROM PREVIOUS REVIEW:
 FAC 61G1-16.004(2) FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS
 REQUIRED ON THE TITLE BLOCK ON EACH
 SHEET. FS 481.2055 & FS 481.219
  
 NEW COMMENT:
 WATER RISER DIAGRAM/WATER HEATER DETAIL,
 COLD WATER DROP REQUIRES A VALVE PER
 SECTION 606.1(4). ALSO COLD WATER TO
 SINK THEN TURNS TO HOT WATER. PLEASE
 CLARIFY.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 10:48 Rev Time 0.75
Received By kstevens Date 2004-10-09 Time 10:48 Sent To  
Notes
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A SANITARY & A WATER RISER DIAGRAM IN
 ISOMETRIC FORM ARE REQUIRED SHOWING ALL
 PIPE SIZES ECT. SECTION 104.3.1.1.
 2) MINIMUM SIZE DRAINAGE PIPE FOR SANT.
 OF A SINK IS 1-1/2" - THERE ARE NO 1"
 SANT. FITTINGS, ONLY PRESSURE FITTINGS.
 3) A GATE VALVE LOCATED ON THE DISCHARGE
 SIDE OF THE CHECK VALVE SHALL BE IN-
 STALLED IN THE PUMP DISCHARGE PIPING BE-
 TWEEN THE PUMP AND THE GRAVITY DRAINAGE
 SYSTEM.
 4) VENT REQUIRED FOR PUMP TANK, EITHER A
 VENT THROUGH THE ROOF OR TIE INTO EXIST-
 ING VENT SYSTEM.
 5) SUBMIT A DETAIL FOR THE WATER HEATER
 SHOWING THERMAL EXPANSION CONTROL, P/T
 RELIEF VALVER DISCHARGE, AND PAN DRAIN
 DISCHARGE (IF APPLICABLE), PER SECTIONS
 607.3.2, 504.7.1, &504.8.1.2.
 6) FAC 61G1-16.004(2) FIRM LICENSE NUM-
 BER, (CERTIFICATE OF AUTHORIZATION), IS
 REQUIRED ON THE TITLE BLOCK ON EACH
 SHEET. FS 481.2055. - FAC 61G1-16.004(6)
 PRINTED NAME OF PERSON SEALING THE DOCU-
 MENT REQUIRED. FS 481.2055
  
 REVIEW BY KEN STEVENS