| Plan Review Stops For Permit 04070844 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2005-04-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-04-04 |
Time |
07:22 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2005-04-04 |
Time |
07:22 |
Sent To |
PC |
|
| Notes |
| 2005-04-04 00:00:00 | REVISIONS- 3/17/05JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2005-02-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-02-07 |
Time |
09:35 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2005-02-07 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2005-02-07 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04070844 | | | ADD: 818 SOUTHERN BLVD | | | CONT: RESTORATION TECHNOLOGIES | | | TEL: (954) 485-8600 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION DATED 1/27/05 REVIEW | | | | | | ACTION: DENIED | | | | | | 1) ARCHITECT INDICATES NO CHANGE TO | | | STRUCTURAL NOR MEANS OF EGRESS. PLANS | | | INDICATE THAT THE EXISTING STAIRS ARE | | | REMOVED, THE OVERHEAD DOOR REMOVED, | | | SIDE DOOR REMOVED, DRIVE UP WINDOW | | | REMOVED, AND A REPOSITIONED REAR DOOR, | | | PLANS ALSO SHOW EXISTING BATHROOMS WHERE | | | | | | THE STAIRS ARE BEING REMOVED! | | | | | | 2) WHAT IS HAPPENING TO THE AREA SERVED | | | BY THE STAIRWAY? | | | | | | 3) 1025.1 MERCANTILE THIS UNIT DOES NOT | | | CONFORM TO THE REQUIREMENTS OF A SINGLE | | | EGRESS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2004-12-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-12-16 |
Time |
14:44 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2004-12-16 |
Time |
14:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-12-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-12-02 |
Time |
12:08 |
Rev Time |
0.25 |
| Received By |
jwitmer |
Date |
2004-12-02 |
Time |
12:08 |
Sent To |
PC |
|
| Notes |
| 2004-12-02 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04070844 | | | ADD: 818 SOUTHERN BLVD | | | CONT: RESTORATION TECHNOLGIES | | | TEL: (954)583-9990 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 4THREVIEW | | | ACTION: REVIEWED | | | | | | BUILDING PANS ARE CODE COMPLIANT, SEE | | | COMMENTS FROM OTHER REVIEWERS | | | CONCERNING | | | REQUIRED INFORMATION IN THE TITLE | | | BLOCK. | | | | | | PLANS ARE MISSING THE LICENSE # OF THE | | | FIRM. FL S S 481.219 | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-10-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-10-06 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-11-24 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2004-10-06 00:00:00 | BUILDING PLANS ARE CODE COMPLIANT, SEE | | | ELEC COMMENTS ABOUT MISSING LICENSE# | | | FOR FIRM, FL SS 481.219. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-07-27 |
Time |
16:10 |
Rev Time |
1.77 |
| Received By |
jwitmer |
Date |
2004-07-27 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2004-07-27 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04070844 | | | ADD: 818 SOUTHERN BLVD. | | | CONT: RESTORATION TECHNOLOGIES OF | | | INDIANA, INC. | | | TEL: (954)485-8600 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) PLANS, SPECIFICATIONS,REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | " NO RUBBER STAMPS" | | | | | | 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 4) SHEET A-3 INDICATES THE USE OF | | | VARIOUS CEILING HUNG UNITS, DO THESE | | | CREATE AN ADDITIONAL LOADTO BE HUNG FROM | | | THE BAR JOIST? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
P |
Date |
2005-09-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-08 |
Time |
20:51 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-09-08 |
Time |
20:51 |
Sent To |
|
|
| Notes |
| 2005-09-08 00:00:00 | REVISED SHEET E-4 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2005-08-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-16 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-08-16 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2005-08-16 00:00:00 | RE-STAMPED FOR LOST PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2005-07-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-06 |
Time |
10:08 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-07-06 |
Time |
10:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2005-06-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-15 |
Time |
19:56 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-06-15 |
Time |
19:56 |
Sent To |
|
|
| Notes |
| 2005-06-15 00:00:00 | ******* UNSAT ******* | | | | | | 1)NOTE: PLEASE SEE NOTES FROM JULY 2004 | | | WHICH REQUESTED ALL CIRCUITING TO BE | | | SHOWN ON PLANS AND TO CORRELATE WITH A | | | PANEL SCHEDULE(S) TO BE SUBMITTED. | | | PLEASE SEE IN A CONDITION SET UP BY | | | ARCHITECT, A NOTE WAS PLACED ON PLANS TO | | | HAVE THIS INFORMATION SUBMITTED TO | | | ARCHITECT AND THEN SUBMITTED TO THE CITY | | | FOR PLAN REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESIATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2005-03-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-17 |
Time |
08:49 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-03-17 |
Time |
08:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-08 |
Time |
16:57 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-02-08 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2005-02-08 00:00:00 | ************ UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS | | | AS PLANS ARE SHOWN WITH SOME MAJOR | | | CHANGES. | | | | | | 2)NOTE: PLEASE SEE FIRST THREE ORIGINAL | | | REVIEWS REQUESTING ALL LICENSE | | | INFORMATION ON TITLE BLOCKS FOR ARCH | | | FIRM. | | | ON THE 4TH REVIEW THE THE FIRM WAS | | | REMOVED AND TITLE BLOCK WAS CHANGED OVER | | | TO THE INDIVIDUAL ARCH. | | | PLANS ARE NOW COMING BACK IN FOR | | | REVISIONAND TITLE BLOCKS ARE LISTING | | | THE ARCH FIRM ONCE AGAIN W/ OUT | | | PROVIDING LICENSE INFORMATION AS | | | REQUIRED UNDER FAC 61G1-16.004 AND FS | | | 481.219. ONE SET OF PLANS IS NOW BEING | | | RETAINED TO BE TURNED OVER TO DBPR AND | | | STATE BOARD OF ARCH FOR REIVEW. | | | | | | 3)NOTE: PLEASE SEE ALL REVISIONSARE TO | | | BE CLEARLY INDICATED WITH | | | CLOUDS/TRIANGLES AND LISTED IN TITLE | | | BLOCK. | | | | | | THE ABOVE COMMENTS ARE FOR ALL TRADES | | | AND FOR ALL SHEETS WHEATHER OR NOT | | | COMMENT IS MADE BY OTHER REVIEWER(S). | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-12-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-12-16 |
Time |
14:58 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-12-16 |
Time |
14:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-11-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-29 |
Time |
07:31 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2004-11-29 |
Time |
07:27 |
Sent To |
|
|
| Notes |
| 2004-11-29 00:00:00 | ************* UNSAT 3RD REVIEW ******** | | | | | | **PLEASE SEE THESE ARE THE SAME NOTES AS | | | PREVIOUS REVIEW. | | | | | | 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR | | | ALL REQUIRED INFORMATION IN TITLE | | | BLOCK. | | | PLEASE SEE PLANS ARE STILL MISSING | | | LICENSE # FOR FIRM. FS 481.219. | | | THIS REQUIRES A CERTIFICATE OF | | | AUTHORIZATION FOR FIRM. | | | THIS IS REQUIRED ON ALL SHEETS FOR ALL | | | TRADES WHEATHER OR NOT COMMENT IS MADE | | | BY OTHER REVIEWER(S). | | | | | | PLEASE SEE POSSIBLE COMMENTS FROM OTHER | | | TRADES WHICH MAY HAVE AN AFFECT ON | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS FOR | | | REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-09-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-09-21 |
Time |
17:24 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-09-21 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2004-09-21 00:00:00 | ******* UNSAT 2ND REVIEW ********** | | | | | | 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR | | | ALL REQUIRED INFORMATION IN TITLE | | | BLOCK. | | | PLEASE SEE PLANS ARE STILL MISSING | | | LICENSE # FOR FIRM. FS 481.219. | | | THIS IS REQUIRED ON ALL SHEETS FOR ALL | | | TRADES WHEATHER OR NOT COMMENT IS MADE | | | BY OTHER REVIEWER(S). | | | | | | PLEASE SEE POSSIBLE COMMENTS FROM OTHER | | | TRADES WHICH MAY HAVE AN AFFECT ON | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS FOR | | | REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-07-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-27 |
Time |
13:26 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-07-27 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2004-07-27 00:00:00 | ********** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE PLANS CONTAIN A | | | "RUBBER STAMP" FOR SIGNATURE OF ARCH. | | | PLEASE SEE FS 481.221 , PLANS ARE | | | REQUIRED TO HAVE AN ORIGINAL SIGNATURE. | | | | | | 2)NOTE: PLEASE SEE FAC 61G1-16.004 FOR | | | MISSING INFORMATION REQUIRED ON TITLE | | | BLOCK FOR ARCH/ARCH FIRM. | | | PLEASE ALSO SEE FS 481.219 FOR REQUIRED | | | FIRM LICENSE #. | | | | | | 3)NOTE: PLEASE SHOW MIN CIRCUITS FOR NEW | | | ITEMS SHOWN ON PLANS. PLEASE CORRELATE | | | CIRCUITS WITH PANEL SCHEDULE(S) TO BE | | | SUBMITTED. | | | | | | 4)NOTE: PLEASE SEE 210.62 FOR SHOW WIND- | | | -OW RECEPTS. | | | | | | 5)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | SIGN CIRCUIT PER 600.5 | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | ONE SET OF OLD SHEETS MAY BE SUBMITTED | | | FOR REFERENCE ONLY AND MAY BE REQUIRED | | | BY ONE OR MORE PLAN REVIEWERS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-03-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-03-31 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-03-31 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2005-03-31 00:00:00 | 1) PLEASE SEE LAST FIRE REVIEW FROM | | | 3/2/05. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-03-02 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-03-02 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-03-02 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2005-03-02 00:00:00 | PROVISO: | | | | | | DEMOLITION, RENOVATION, AND CONSTRUCTION | | | TO COMPLY WITH NFPA 241. ALL DEBRIS | | | SHALL BE REMOVED FROM THE STORE DAILY. | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-10-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-10-01 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-10-01 |
Time |
13:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-07-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-07-30 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-07-30 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2004-07-30 00:00:00 | 1) CONSTRUCTION, DEMOLITION, AND | | | RENOVATION TO COMPLY WITH NFPA 241. | | | | | | 2) WILL THE STORE REMAIN OPEN DURING | | | REMODELING. | | | | | | 3) GASOLINE POWERED EQUIPMENT SHALL | | | NOT BE USED WITHOUT PROPER | | | VENTILATION TO AVOID CARBON MONOXIDE | | | BUILD-UP. | | | | | | 4) IF STORE REMAINS OPEN ALL EXITS | | | SHALL REMAIN CLEAR AND UNOBSTRUCTED. | | | | | | 5) DEBRIS SHALL BE REMOVED FROM THE | | | STORE DAILY. | | | | | | 6) NON FIRE RETARDANT VISQUEEN SHALL | | | BE USED. | | | | | | 7) NO TRIPPING HAZARDS SHALL BE | | | ALLOWED DURING CONSTRUCTION. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2005-09-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-07 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-07 |
Time |
09:06 |
Sent To |
E |
|
| Notes |
| 2005-09-07 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2005-08-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-16 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-16 |
Time |
09:42 |
Sent To |
B |
|
| Notes |
| 2005-08-16 00:00:00 | TO "JWITMER" DESK/RESTAMP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2005-07-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-01 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-01 |
Time |
17:43 |
Sent To |
E |
|
| Notes |
| 2005-07-01 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2005-06-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-10 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-10 |
Time |
12:06 |
Sent To |
E |
|
| Notes |
| 2005-06-10 00:00:00 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-04-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-06 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-06 |
Time |
14:44 |
Sent To |
FIRE |
|
| Notes |
| 2005-04-06 00:00:00 | TO "F" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-03-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-16 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-16 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2005-03-16 00:00:00 | TO "COMM" BD#30 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-02-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-04 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-04 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2005-02-04 00:00:00 | TO COMM BOARD/ #27/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-12-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-09 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-09 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2004-12-09 00:00:00 | SENT TO COMM BD#5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-11-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-11-24 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-11-24 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2004-11-24 00:00:00 | SENT TP COMM BD#19 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-11-08 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-08 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-08 |
Time |
10:45 |
Sent To |
P |
|
| Notes |
| 2004-11-08 00:00:00 | TO KS BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-09-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-14 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-09-14 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2004-09-14 00:00:00 | TO COMM BD#14 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-08-06 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-08-06 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2004-07-21 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2004-07-21 00:00:00 | TO COMM BD#46 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
N |
Date |
2004-12-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-12-17 |
Time |
12:35 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-12-17 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2004-12-17 00:00:00 | NO MECHANICAL WORK REQUIRED AT THIS | | | LOCATION PER ARCHITECT/ENGINEER. | | | MECHANICAL PLANS WERE INADVERTENTLY | | | SUBMITTED, DO NOT BELONG WITH THIS | | | PROJECT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2004-12-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-12-01 |
Time |
07:54 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-12-01 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2004-12-01 00:00:00 | DENIED: | | | 1.PREVIOUS COMMENTS FROM REVIEW DATED | | | 10-6-04 WERE NOT ADDRESSED.SEE | | | ATTACHED. | | | | | | 2.M-1 SHEET WAS REMOVED FROM THE | | | LATEST SUBMITTAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2004-10-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-10-06 |
Time |
17:53 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2004-10-06 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2004-10-06 00:00:00 | DENIED: | | | SEE COMMENT #1 BY DEWEY PALMER, | | | ELECTRICAL PLAN REVIEW.SHOW COMPLIANCE | | | WITH FS 481.219AND THE FAC 61G1-16.004 | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-08-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2004-08-02 |
Time |
09:33 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2004-08-02 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2004-08-02 00:00:00 | PASS PRIVISO | | | 1) PLEASE REFER TO SECTION 601.4 | | | FLORIDA BUILBING CODE M BALANCED | | | RETURN AIR. | | | PLAN REVIEW BY HAROLD MOSER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-01-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-01-07 |
Time |
10:04 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2005-01-07 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2004-12-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-12-28 |
Time |
10:10 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-12-28 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2004-12-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | FROM PREVIOUS REVIEWS: | | | SUBMIT A DETAIL FOR THE WATER HEATER | | | SHOWING THERMAL EXPANSION CONTROL PER | | | SECTION 607.3.2 | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-11-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-24 |
Time |
16:19 |
Rev Time |
0.60 |
| Received By |
kstevens |
Date |
2004-11-24 |
Time |
16:19 |
Sent To |
I |
|
| Notes |
| 2004-11-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEW: SUBMIT A DETAIL | | | FOR THE WATER HEATER SHOWING THERMAL | | | EXPANSION CONTROL PER SECTION 607.3.2. | | | | | | FROM PREVIOUS REVIEW: | | | FAC 61G1-16.004(2) FIRM LICENSE NUMBER, | | | (CERTIFICATE OF AUTHORIZATION), IS | | | REQUIRED ON THE TITLE BLOCK ON EACH | | | SHEET. FS 481.2055 & FS 481.219 | | | | | | NEW COMMENT: | | | WATER RISER DIAGRAM/WATER HEATER DETAIL, | | | COLD WATER DROP REQUIRES A VALVE PER | | | SECTION 606.1(4). ALSO COLD WATER TO | | | SINK THEN TURNS TO HOT WATER. PLEASE | | | CLARIFY. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-10-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-10-09 |
Time |
10:48 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2004-10-09 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2004-10-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) A SANITARY & A WATER RISER DIAGRAM IN | | | ISOMETRIC FORM ARE REQUIRED SHOWING ALL | | | PIPE SIZES ECT. SECTION 104.3.1.1. | | | 2) MINIMUM SIZE DRAINAGE PIPE FOR SANT. | | | OF A SINK IS 1-1/2" - THERE ARE NO 1" | | | SANT. FITTINGS, ONLY PRESSURE FITTINGS. | | | 3) A GATE VALVE LOCATED ON THE DISCHARGE | | | SIDE OF THE CHECK VALVE SHALL BE IN- | | | STALLED IN THE PUMP DISCHARGE PIPING BE- | | | TWEEN THE PUMP AND THE GRAVITY DRAINAGE | | | SYSTEM. | | | 4) VENT REQUIRED FOR PUMP TANK, EITHER A | | | VENT THROUGH THE ROOF OR TIE INTO EXIST- | | | ING VENT SYSTEM. | | | 5) SUBMIT A DETAIL FOR THE WATER HEATER | | | SHOWING THERMAL EXPANSION CONTROL, P/T | | | RELIEF VALVER DISCHARGE, AND PAN DRAIN | | | DISCHARGE (IF APPLICABLE), PER SECTIONS | | | 607.3.2, 504.7.1, &504.8.1.2. | | | 6) FAC 61G1-16.004(2) FIRM LICENSE NUM- | | | BER, (CERTIFICATE OF AUTHORIZATION), IS | | | REQUIRED ON THE TITLE BLOCK ON EACH | | | SHEET. FS 481.2055. - FAC 61G1-16.004(6) | | | PRINTED NAME OF PERSON SEALING THE DOCU- | | | MENT REQUIRED. FS 481.2055 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|