Plan Review Details - Permit 04070798
Plan Review Stops For Permit 04070798
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-11-15 Cont ID  
Sent By alange Date 2005-11-15 Time 13:54 Rev Time 1.00
Received By alange Date 2005-11-15 Time 13:54 Sent To  
Notes
2005-11-15 00:00:00FRAMING REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-08-02 Cont ID  
Sent By alange Date 2005-08-02 Time 11:17 Rev Time 0.50
Received By alange Date 2005-08-02 Time 11:17 Sent To  
Notes
2005-08-02 00:00:00REVISION FOR DOORS AND WINDOWS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-12-10 Cont ID  
Sent By alange Date 2004-12-10 Time 09:36 Rev Time 0.00
Received By alange Date 2004-12-10 Time 09:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-16 Cont ID  
Sent By alange Date 2004-11-16 Time 09:42 Rev Time 1.25
Received By alange Date 2004-11-16 Time 09:40 Sent To  
Notes
2004-11-16 00:00:00DENIED
 COMMENT FROM LAST REVIEW.
  
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED TO QUALITY
 ASSURANCE TEST (MIAMI-DADE) FOR
 EXAMPLE.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 CHECK NOTES FROM OTHER REVIEWERS THAT
 MIGHT EFFECT THE ISSUING OF A PERMIT.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-04 Cont ID  
Sent By pkrauss Date 2004-08-03 Time 14:06 Rev Time 3.75
Received By alange Date 2004-08-04 Time 09:16 Sent To  
Notes
2004-08-04 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS MISSING FOR
 MASONITE STEEL EDGE WOOD DOORS, SUBMIT
 2 COPIES.
  
 4.PRODUCT APPROVALS MISSING FOR ALL
 ARCHED WINDOWS. SUBMIT 2 COPIES.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.SEPERATE POOL PERMIT REQUIRED
  
 6.SUBMIT PRODUCT APPROVALS FOR
 ALL STRAPS AND TIEDOWNS.
  
 7. BUILDING VALUATION HAS BEEN REVISED
 TO $259,947 BASED ON SBCCI BUILDING
 VALUATION DATA.
 A/C 2995 SQ. FT. X $76.96 = $230,495
 OTHER 708 SQ.FT. X $41.60 = $29,452
  
 8.FBC 2309.6SHOW LOCATION AND SIZE
 OF ATTIC ACCESS.
  
 9. FIREPLACE DETAILS NOT READABLE,
 PLEASE SUBMIT NEW DETAILS.
  
 10.DOOR #13 NOT SHOWN ON NORTH
 ELEVATION,
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-03-17 Cont ID  
Sent By dpalmer Date 2006-03-17 Time 19:17 Rev Time 0.00
Received By dpalmer Date 2006-03-17 Time 18:53 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-10-20 Cont ID  
Sent By dpalmer Date 2005-10-20 Time 15:30 Rev Time 0.75
Received By dpalmer Date 2005-10-20 Time 15:30 Sent To  
Notes
2005-10-20 00:00:00********** PROVISO/REVISION ***********
  
 1)NOTE: PLEASE CORRELATERISER DIAGRAM
 ALONG WITH PANEL SCHEDULES FOR GARAGE
 PANEL.
 PER OWNER, #1 AWG IS INSTALLED.
 PLEASE SEE OCP IN MM AND RISER TO MATCH,
 SHOWS 70A AND 60A.
 PLEASE SEE RISER INDICATES SUB PANEL ON
 2ND FLR, HOWEVER PANEL IS LOCATED ON
 FIRST FLR RM.
 PLEASE INDICATE UTILITY RM UNDER STAIRS
 AS ELECTRICAL ROOM/ NO STORAGE.
 240.24D,408.7, 215.5, 240.4,310.16
  
 2)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 3)NOTE: PLEASE SEE MISSING SD LOCATED
 OUTSIDE MASTER BEDRM AT TOP OF STAIRS.
 THIS WAS REDLINED ON PREVIOUS PLANS.
 NFPA-72 8-1.4.1.6.2
  
 4)NOTE:PLEASE SEE MISSING GFI AT
 PENINSULAR. PER OWNER, THIS WILL BE IN
 CABINETS AND ONLY TO STUB OUT AT THIS
 TIME.
 210.52C3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND STAMPING BEFORE FINAL
 ELECTRICAL INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-23 Cont ID  
Sent By dpalmer Date 2004-11-23 Time 07:08 Rev Time 0.25
Received By dpalmer Date 2004-11-23 Time 07:08 Sent To M
Notes
2004-11-23 00:00:00REDLINED SD LOCATION ON SECOND FLR, MAY
 BE ONE IN CENTRAL AREA OUTSIDE BEDRMS.
 REDLINED MISSING RECPT FOR 2' OF WALL
 SECOND FLR BEDRM.210.52
 BATH GFI IN GARAGE REDLINED ON ONE SET.
  
 HAND DRAWN CHANGE FOR 70A SUB-PANEL FEED
 OK.
  
 THESE ITEMS ARE REDLINED ON PLANS AND DO
 NOT NEED TO BE SUBMITTED FOR A
 REVISION.
  
 IF THERE ARE ANY OTHER REV'S AS THE
 PROJECT IS FURTHER ALONG, PLEASE MAKE
 THESE HARD CHANGES AT THAT TIME.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-10-23 Cont ID  
Sent By dpalmer Date 2004-10-23 Time 06:30 Rev Time 0.50
Received By dpalmer Date 2004-10-23 Time 06:07 Sent To P
Notes
2004-10-23 00:00:00IN ELEC FOR REVIEW.
 ************* UNSAT **************
  
 1)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 ARE ALSO REQUIRED TO BE SIGNED BY THE
 PERSON RESPONSIBLE FOR PLANS.
  
 2)NOTE: PLEASE SEE MECHANICAL PLANS ARE
 DRAWN OVER ELECTRICAL PLANS. THESE
 CONTAIN AN ARCH'S TITLE BLOCK.
 IF TITLE BLOCK IS PRESENT, THEN PLANS
 ARE REQUIRED TO BE SIGNED DATED AND
 SEALED BY THE ARCH. FS481.221
 PLEASE ALSO EITHER REMOVE ELECTRICAL
 FROM PLANS.
  
 3)NOTE: PLEASE SEE ELECTRICAL RISER SHOW
 'S A PANEL FOR SEOND FLR AND SHOWS A
 70A DISC, YET THERE IS NO INDICATION
 WHERE THIS PANEL IS FED FROM?
 PLEASE SEE 200A PANEL DOES NOT INDICATE
 THIS BEING FED.
  
 4)NOTE: PLEASE VERIFY WATER HEATER SIZE,
 SEEMS TO BE TOO SMALL FOR A HOUSE THIS
 SIZE. PLEASE SEE PLUMB CODE FOR MIN
 SIZE REQUIRED.
  
 5)NOTE: PLEASE SEE MISSING GFI IN BATH
 RM AT GARAGE. 210.52D, 210.11C3
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-02 Cont ID  
Sent By csiegber Date 2004-10-15 Time 09:50 Rev Time 0.75
Received By dpalmer Date 2004-08-02 Time 13:39 Sent To M
Notes
2004-08-02 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAMS.
 TWO SUBMITTED??
 PLEASE ALSO CORRELATE WITH PANEL SCHED-
 -ULES.
  
 2)NOTE: PLEASE SEE 310.16 FOR SIZING
 OF FEEDERS AND SEC'S. SHOWS 1/0'S FOR
 200A SERVICE? ETC.
  
 3)NOTE: PLEASE SEE 30A OCP FOR WASHER?
  
 4)NOTE: PLEASE SHOW LOCATION OF PANELS /
 SERVICE EQUIPMET ON PLANS.
  
 5)NOTE: PLEASE SEE 250.50 FOR REQUIRED
 CWP FOR GROUNDING ELECTRODE.
  
 6)NOTE: PLEASE SEE "NOTE" MENTIONS SD'S
 ATTACHED TO KITCHEN LT CIRCUIT.
 PLEASE SEE 210.12 2002 NEC SD'S ARE
 REQUIRED TO HAVE ARC FAULT PROTECTION.
  
 7)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 ARE REQUIRED TO HAVE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS.
 THIS IS REQUIRED ON ALL SHEETS,WHEATHER
 OR NOT COMMENT IS MADE BY OTHER REVIEW-
 -ERS.
  
 8)NOTE: PLEASE ALSO SEE PLANS MENTIONS
 BEDRM RECEPTS TO BE ARC FAULT PROT.
 PLEASE SEE 2002 NEC 210.12.
 LTS/FANS/RECEPT, SD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-03-16 Cont ID  
Sent By adarroug Date 2006-03-16 Time 10:27 Rev Time 0.00
Received By adarroug Date 2006-03-16 Time 10:27 Sent To E
Notes
2006-03-16 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 09:35 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 09:35 Sent To M
Notes
2005-10-22 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-20 Cont ID  
Sent By adarroug Date 2005-10-20 Time 10:03 Rev Time 0.00
Received By adarroug Date 2005-10-20 Time 10:03 Sent To E
Notes
2005-10-20 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 14:55 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 14:55 Sent To B
Notes
2005-07-29 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2005-07-26 Time   Rev Time 0.00
Received By lmartine Date 2005-07-26 Time 13:01 Sent To  
Notes
2005-07-26 00:00:00GAVE TO ART

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-19 Cont ID  
Sent By csiegber Date 2004-11-19 Time 14:33 Rev Time 0.00
Received By csiegber Date 2004-11-19 Time 14:30 Sent To E
Notes
2004-11-19 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-15 Cont ID  
Sent By csiegber Date 2004-10-15 Time 09:50 Rev Time 0.00
Received By csiegber Date 2004-10-15 Time 09:49 Sent To E
Notes
2004-10-15 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-04 Cont ID  
Sent By jroach Date 2004-07-29 Time 13:25 Rev Time 0.00
Received By alange Date 2004-07-21 Time 08:56 Sent To  
Notes
2004-07-29 00:00:00TO SFD RACK/E
2004-07-21 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-11-09 Cont ID  
Sent By tgordon Date 2005-11-09 Time 12:40 Rev Time 0.30
Received By tgordon Date 2005-11-09 Time 12:40 Sent To B
Notes
2005-11-09 00:00:0011-9-05 MECH. REV. TO PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-12-09 Cont ID  
Sent By pkrauss Date 2004-12-09 Time 06:45 Rev Time 0.30
Received By pkrauss Date 2004-12-09 Time 06:27 Sent To  
Notes
2004-12-09 00:00:00PROVISO ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-11-16 Cont ID  
Sent By pkrauss Date 2004-11-16 Time 06:31 Rev Time 0.35
Received By pkrauss Date 2004-11-15 Time 17:45 Sent To B
Notes
2004-11-16 00:00:00DENIED:
 MECHANICAL PLANS SUBMITTED HAVE A TITLE
 BLOCK INDICATED ON THE PLAN.WHEN THE
 TITLE BLOCK IS PRESENT, PLANS ARE
 REQUIRED TO BE SIGNED, SEALED AND DATED
 BY THE ARCHITECT IN ACCORDANCE WITH FS
 481.221.PLEASE HAVE ARCHITECTECT
 COMPLY OR REMOVE THE TITLE BLOCK.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-08-03 Cont ID  
Sent By kstevens Date 2004-10-28 Time 18:36 Rev Time 0.20
Received By pkrauss Date 2004-08-03 Time 14:04 Sent To B
Notes
2004-08-03 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.ENERGY AND MANUAL J CALCS
 SUBMITTED WITH BUILDING PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-10-28 Cont ID  
Sent By kstevens Date 2004-10-28 Time 18:36 Rev Time 0.50
Received By kstevens Date 2004-10-28 Time 18:36 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-31 Cont ID  
Sent By dpalmer Date 2004-10-23 Time 06:30 Rev Time 0.50
Received By jleech Date 2004-07-31 Time 08:30 Sent To E
Notes
2004-07-31 00:00:00RISER DIAGRAM NOT TO CODE AND FIXTURES
 ARE MISSING.
 1/2 BATH MISSING FROM RISER DIAGRAM.
 BATHROOM ON FIRST FLOOR IS NOT VENTED
 RISER FOR SECOND FLOOR PLUMBING MUST
 DISCHARGE DOWN STREAM OF BATHROOM GROUP.
 W/M NOT VENTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-18 Cont ID  
Sent By jroach Date 2004-10-18 Time 10:03 Rev Time 0.00
Received By jroach Date 2004-10-18 Time 10:03 Sent To  
Notes
2004-10-18 00:00:0010/18/04 ***PASSED***
  
 THE WING WALL ON THE SE CORNER OF THE
 BUILDING SHALL NOT EXCEED 6' IN HEIGHT.
  
 REFER TO ENCLOSED SURVEY FOR APPROVED
 SITE PLAN.SITE PLAN WITH THE PLANS
 DOES NOT HAVE A SCALE.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-07-29 Cont ID  
Sent By csiegber Date 2004-07-21 Time 08:56 Rev Time 0.00
Received By jroach Date 2004-07-29 Time 13:19 Sent To I
Notes
2004-07-29 00:00:007/29/04 - FAILED.
  
 1) PLEASE PROVIDE A SCALED DRAWING OF
 THE SITE PLAN.
  
 2) THE POOL WILL NEED TO BE 10' FROM THE
 PROPOSED PROPERTY LINE...UNTIL TEXT
 CHANGE HAS BEEN APPROVED (DATE UNKNOWN).
  
 3) THE TOWER ON THE GARAGE MAY NOT
 EXCEED 30' IN HEIGHT.HEIGHT IS
 MEASURED FROM GRADE, NOT FINISHED FLOOR
 ELEVATION.
  
 4) THE WING WALL ON THE SOUTHEAST CORNER
 OF THE HOUSE MUST BE SHOWN ON THE SITE
 PLAN.MAXIMUM HEIGHT MAY NOT EXCEED 6'
 IN HEIGHT.
  
 5) THE EXTERIOR DOOR TO THE GARAGE
 BATHROOM IS NOT SHOWN ON THE NORTH
 ELEVATION.
  
 PLEASE CONTACT JOHN ROACH, PLANNER FOR
 ANY QUESTIONS.(561) 822.1435