Plan Review Details - Permit 04070725
Plan Review Stops For Permit 04070725
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-07-25 Cont ID  
Sent By csiegber Date 2005-04-25 Time 12:49 Rev Time 0.00
Received By mwennerg Date 2005-04-25 Time 15:34 Sent To  
Notes
2005-04-25 00:00:001) A MINIMUM CLEAR AND UNOBSTRUCTED
 WIDTH OF 20' MUST BE PROVIDED FOR
 EMERGENCY VEHICLES. PLEASE INDICATE HOW
 THE FIRE DEPARTMENT CONNECTION WILL BE
 ACCESSED THROUGH THE STUDENT DROP OFF
 AND PLAY AREA.
  
 2) THE FDC SHALL BE LOCATED AT A
 DISTANCE NOT FURTHER THAN 150' FROM THE
 CLOSEST FIRE HYDRANT.
  
 3) PLEASE PROVIDE FURTHER DETAILS
 REGARDING THE BACK FLOW PREVENTOR.
  
 4) THE BACK FLOW PREVENTOR SHALL BE
 SECURED WITH A CHAIN AND LOCK IN
 ADDITION TO ELECTRONIC SUPERVISION.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 10:16 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 10:16 Sent To FIRE
Notes
2005-04-22 00:00:00TO "F" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-19 Time 12:49 Rev Time 0.00
Received By csiegber Date 2004-07-19 Time 12:49 Sent To FIRE
Notes
***NONE***