| Plan Review Stops For Permit 04070725 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-07-25 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2005-04-25 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-04-25 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2005-04-25 00:00:00 | 1) A MINIMUM CLEAR AND UNOBSTRUCTED | | | WIDTH OF 20' MUST BE PROVIDED FOR | | | EMERGENCY VEHICLES. PLEASE INDICATE HOW | | | THE FIRE DEPARTMENT CONNECTION WILL BE | | | ACCESSED THROUGH THE STUDENT DROP OFF | | | AND PLAY AREA. | | | | | | 2) THE FDC SHALL BE LOCATED AT A | | | DISTANCE NOT FURTHER THAN 150' FROM THE | | | CLOSEST FIRE HYDRANT. | | | | | | 3) PLEASE PROVIDE FURTHER DETAILS | | | REGARDING THE BACK FLOW PREVENTOR. | | | | | | 4) THE BACK FLOW PREVENTOR SHALL BE | | | SECURED WITH A CHAIN AND LOCK IN | | | ADDITION TO ELECTRONIC SUPERVISION. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-04-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-22 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-22 |
Time |
10:16 |
Sent To |
FIRE |
|
| Notes |
| 2005-04-22 00:00:00 | TO "F" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-07-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-19 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-19 |
Time |
12:49 |
Sent To |
FIRE |
|
| Notes |
|
|
|