| Plan Review Stops For Permit 04070518 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-12-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-12-13 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2004-12-13 |
Time |
10:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-11-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-11-01 |
Time |
|
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2004-11-01 |
Time |
12;00 |
Sent To |
|
|
| Notes |
| 2004-11-01 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 04070518 | | | ADD: 2471 OKEECHOBEE BLVD | | | CONT: G. T. MCDONALD ENT | | | TEL: (954)650-0022 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) REMOVE THE OLD SHEETS (VOID) FROM THE | | | PLANS AND SUBMIT ONE SET OLD SHEETS | | | PLUS | | | THE 2 SETS OF CORRECTED PLANS FOR | | | RESUBMITAL. | | | | | | 3) FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | QUESTIONS ABOUT THE OVERHEAD TRELLIS | | | WORK ARE: | | | A) PLANS INDICATE THE USE OF AIRCRAFT | | | CABLES TO HANG TRELLIS WORK FROM THE | | | BAR JOIST ABOVE.NO INFORMATION AS TO | | | THE | | | CABLE WIDTH, HOW MANY CLAMPS ARE TO BE | | | USED. ALSO PLANS DO NOT INDICATE HOW | | | OFTEN THE HEADER IS TO BE HUNG NOR HOW | | | LONG THE TIMBERS SHOULD BE. | | | B) PLANS DO NOT SPECIFY THE SIZE OF THE | | | | | | EYEBOLTS TO BE USED? | | | C) ENGINEER TO EVALUATE THE ADDITIONAL | | | | | | LOADING OF THE TRELLIS WEIGHT, ALSO TO | | | INDICATE WHERE THE ADDITIONAL WEIGHT IS | | | TO BE APPLIED TO THE BARJOIST, TOP OR | | | BOTTOM CHORD. | | | D)DETAIL# 1 INDICATE STEEL BUCKETS | | | ATTACHED TO THE BLOCK WALL BUT NO | | | ATTACHMENT NOR THICKNESS OF STEEL USED. | | | E) DETAIL# 5 NO INFORMATION ON WELD. | | | | | | 4) COMMENT #9 FROM PREVIOUS REVIEW, WAS | | | WHAT TYPE OF MATERIAL TO BE USED FOR | | | CROWN MOLDING. RESPONCE SEE CUT SHEETS. | | | THE FOAM TRIM CUT SHEETS DO NOT MEET THE | | | | | | CRITERIA SET FORTH IN 803.4. | | | 803.4 FOAM PLASTIC TRIM SHALL NOT BE | | | USED AS INTERIOR TRIM. SEE EXCEPTION: | | | A) THE MINIMUM DENSITY IS 20LBS/CU FT. | | | B) THE MAXIMUM THICKNESS OF THE TRIM IS | | | 1/2" AND THE MAXIMUM WIDTH IS 4".C) | | | THE TRIM CONSTITUTES NO MORE THAN | | | 10% OF THE WALL OR CEILING. | | | D) THE FLAMESPREAD RATING DOES NOT | | | EXCEED 75 WHEN TESTED PER ASTM E 84. | | | THE SMOKE DEVELOPMENT RATING IS | | | NOT LIMITED. | | | | | | 5) SHEET A-402 DETAIL# 1 INDICATES THE | | | USE OF CULTURED STONE FACING, PROVIDE | | | ADDITIONAL INFORMATION AS WHAT THIS | | | MATERIAL WILL BE. ALSO SHEET A-401 THE | | | INTERIOR ELEVATION# 6 HAS A NEW AREA | | | HIGHLIGHTED REVISION# 1, WHAT WILL THIS | | | MATERIAL ALSO BE MADE OF? | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-07-26 |
Time |
14:05 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2004-07-26 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2004-07-26 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04070518 | | | ADD: 2471 OKEECHOBEE BLVD | | | CONT: G. T. MC DONALD ENT. | | | TEL: (954)650-0022 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) PLANS, SPECIFICATIONS,REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | THIS MEANS ORIGINAL SIGNATURE!!!!!!!!!!! | | | | | | 3)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | PLANS INDICATE WHAT LOOKS LIKE (3) | | | FIREPLACES, OWNER SUPPLIED, PROVIDE | | | INFORMATION, TYPE OF MATERIALS, ETC. | | | | | | 4) SHEET A-2.01 STOREFRONT DOORS, EXIST- | | | ING NOTE(SF) WHAT TYPE OF DOOR HARDWARE | | | IS ON EXISTING DOORS? | | | | | | 5) SHEET CV-1 BUILDING CODE ANALYSIS: | | | TYPE IV CONSTRUCTED, UNPROTECTED AND | | | SPRINKLERED. TABLE 500 FOR MEWCANTILE | | | OCCUPANCY ONLY ALLOWS 27,000 SQ FT. | | | BUILDING WOULD HAVE TO BE 1-HR PROTECTED | | | FOR THIS AREA INCREASE TO 30,877. | | | | | | 6) SHEET A3.01 INDICATES THE USE OF A | | | WOOD TRELLIS SYSTEM WITH DETAILS ON | | | PAGE A-4.02 DETAILS 1 & 2. I BELIEVE | | | THERE IS A DISCREPANCY BETWEEN DETAILS. | | | DETAIL#1 WOULD INDICATE THE TREATMENT | | | WITH THE NEW OWNER SUPPLIED COLUMNS. | | | DETAIL#2 WOULD BE CORRECT, IF THERE IS A | | | COLUMN IN THIS POSITION? THE PLAN 3/A201 | | | DOES NOT PROVIDE SUPPORT AT EACH CON- | | | NECTION. | | | | | | 7) PLANS DO NOT PROVIDE CONNECTION FOR | | | 4"X12" TUBE STEEL AT EXTERIOR WALL. | | | | | | 8) OWNER SUPPLIED COLUMNS PROVIDE INFOR- | | | MATION? TYPE OF MATERIAL? SEE 803.4. | | | | | | 9) PROVIDE INFORMATION ALSO ON THE TYPE | | | OF MATERIAL TO BE USESD FOR THE CROWN | | | MOLDING? SEE 803.4. | | | | | | 10) PROVIDE THE ALLOWABLE LOADS FOR | | | 4"X12" TUBE STEEL FOR 32"-0" CLEAR SPAN? | | | | | | 11)TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2005-03-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-17 |
Time |
12:18 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-03-17 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2005-03-17 00:00:00 | REDLINED PANEL "L", AS 200A MLO ON RISER | | | PER ELECTRICAL CONT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-12-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-12-15 |
Time |
10:25 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-12-15 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2004-12-15 00:00:00 | PLANS GIVEN TO LM FOR PROCESSING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-12-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-12-13 |
Time |
09:54 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-12-13 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2004-12-13 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE TWO OF THE SETS NOW | | | HAVE THREE NEW ELECTRICAL SHEETS IN | | | EACH. | | | PLEASE SEE OLD ELECTRICAL SHEETS WHICH | | | WERE STAMPED BY ELECTRICAL ON PREVIOUS | | | REVIEW ARE NOW NOT IN SETS. | | | PLEASE ALSO SEE SHEET E4.01 IS NOW | | | MISSING FROM TWO OF THE SETS.?? | | | | | | PLEASE SUBMIT COMPLETE SETS FOR REVIEW | | | AND STAMPING. | | | | | | IF NO CHANGES WERE MADE TO PLANS, PLEASE | | | INSERT PREVIOUS STAMPED ELECTRICAL | | | SHEETS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-10-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-10-21 |
Time |
14:07 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-10-21 |
Time |
14:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-07-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-21 |
Time |
13:32 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-07-21 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2004-07-21 00:00:00 | ************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE CERT OF AUTH # ON | | | TITLE BLOCK IS NOT VISABLE. | | | FS 471.023,FAC 61G15-23.002 | | | | | | 2)NOTE: PLEASE PROVIDE LOAD CALCULATION | | | FOR EXISTING DP2. | | | | | | 3)NOTE: PLEASE SEE 220.12B FOR LOADS | | | TO BE INDICATED FOR TRK LTING. | | | | | | 4)NOTE: PLEASE VERIFY IF NEW OR EXISTING | | | SHOW WINDOW RECEPTS ARE PRESENT. 210.62 | | | SOME RECEPTS ARE SHOWN BUT NOT CLEAR FOR | | | WHAT.? | | | | | | 5)NOTE: PLEASE VERIFY NEW OR EXSIT SIGN | | | CIRCUIT PER 600.5 | | | | | | PLEASE SEE A-SHEETS CONTAIN A "STAMP" | | | FOR REQUIRED ORIGINAL SIGNATURE. | | | FS 481.221 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-12-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-11-19 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2004-11-19 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2004-12-14 00:00:00 | | | | | | | OK PER MIKE CARSILLO 12/14/04 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2004-11-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-11-05 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-11-19 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2004-11-05 00:00:00 | 1) HANDRAILS REQUIRED ON BOTH SIDES | | | OF EXISTING STAIR OUTSIDE OF EXISTING | | | DOOR FROM RECEIVING IF NOT ALREADY | | | PRESENT. | | | | | | 2) FLAME SPREAD DATA REQUIRED ON | | | TRELLIS. | | | | | | 3) TACTILE SIGNAGE REQUIRED AT EXIT | | | DOORS. | | | | | | 4) BUILDING ADDRESS REQUIRED. A | | | MINIMUM OF AT LEAST 6" HIGH | | | NUMBERS ARE REQUIRED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-08-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-08-10 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-08-10 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2004-08-10 00:00:00 | 1) DEMOLITION, RENOVATION AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) DEBRIS SHALL BE REMOVED FROM THE | | | SITE DAILY. | | | | | | 3) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 4) HANDRAILS NOT SHOWN FOR EXISTING | | | STAIRS IN REAR. | | | | | | 5) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER REMODEL. | | | | | | 6) PLEASE INDICATE INTERIOR FINISH | | | FOR CEDAR TRELLIS. | | | | | | 7) TACTILE SIGNAGE REQUIRED AT ALL | | | EXIT DOORS. | | | | | | 8) A KNOX-BOX WILL BE REQUIRED IF ONE | | | IS NOT PRESENT. | | | | | | 9) A SEPARATE PLAN AND PERMIT REQUIRED | | | FOR THE FIRE ALARM SYSTEM. | | | | | | 10) PLEASE EXPLAIN NOTE # 3 ON PAGE | | | E-2.01. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-03-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-17 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-17 |
Time |
09:11 |
Sent To |
E |
|
| Notes |
| 2005-03-17 00:00:00 | TO "DPALMER" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-11-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-11-30 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-11-30 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2004-11-30 00:00:00 | SENT TO COMM BD#32/RERSUB. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-10-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-12 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-12 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2004-10-12 00:00:00 | TO COMM BD#33 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-08-10 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-12 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-14 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2004-07-14 00:00:00 | SENT TO "COMM" BOARD # 13 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-10-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-10-26 |
Time |
09:42 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-10-26 |
Time |
09:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-07-22 |
Time |
10:55 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2004-07-22 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2004-07-22 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) 403.3. | | | | | | 2.PLEASE NOTE, SHOULD RETURN AIR BE | | | A PLENUM ABOVE THE CEILING, NO | | | COMBUSTIBLES ALLOWED IN THE THE RETURN | | | AIR PLENUM PER 2001 FBC(M) 602.2.1. | | | | | | 3.PLANS ARE TO BE SIGNED NOT INITIALED | | | BY THE ENGINEER IN ACCORDANCE WITH FS | | | 471.025 AND FAC 61G15-23.002. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2004-12-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-12-13 |
Time |
09:18 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-12-13 |
Time |
09:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-11-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-01 |
Time |
16:13 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-11-01 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2004-11-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | FROM PREVIOUS REVIEW: | | | 3) SHT P-2.01 DOMESTIC WATER RESER | | | DIAGRAM, WATER HAMMER ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURE | | | IN AN "EFFECTIVE RANGE" NOT IN THE | | | CEILING AS SHOWN. PDI-WH 201 AND | | | MANUF. INSTALLATION INSTRUCTIONS. | | | NO RESPONSE NOTED. | | | 4) SHT A-3.01 SECTION 11-4.24.5 A | | | CLEAR FLOOR SPACE AT LEAST 30"X48" | | | COMPLYING WITH 11-4.2.4 SHALL BE | | | PROVIDED IN FRONT OF A SINK TO | | | ALLOW FORWARD APPROACH. THE CLEAR | | | FLOOR SPACE SHALL BE ON AN ACCESSIBLE | | | ROUTE AND SHALL EXTEND A MAXIMUM OF | | | 19" UNDERNEATH THE SINK. (SEE FIG.32) | | | THIS IS FOR THE EMPLOYEE ROOM SINK | | | NOT THE LAVS. THE SPACE UNDER THE | | | SINK SHALL NOT HAVE DOORS AS THEY | | | ARE A HINDERENCE PER BLDG OFFICIAL. | | | 5) SHOW KNEE CLEARANCE 11-4.24.3, | | | EXPOSED PIPES AND SURFACES 11-4.24.6, | | | *****NEW COMMENT***** | | | 1B) SEE ATTACHED SHEET CONCERNING | | | FS 553.80(2)(B) | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-11-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-07-29 |
Time |
14:58 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-07-29 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2004-07-29 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHTS D-2.01 & P-1.01 DEMO NOTES #'S 4 | | | AND 10, AND ITEM #2, SECTION 704.5 IN | | | THE INSTALLATION OR REMOVAL OF ANY PART | | | OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE | | | PROHIBITED. | | | 2) SHTS P-1.01 & P-2.01 UNABLE TO READ | | | THE CERTIFICATE OF AUTHORIZATION REQUIR- | | | ED BY FAC 61G15-23.002(2) & FS 471.025. | | | 3) SHT P-2.01 DOMESTIC WATER RISER DIAG- | | | RAM, WATER HAMMER ARRESTORS SHALL BE LO- | | | CATED NEAR THE FIXTURE IN AN "EFFECTIVE | | | RANGE" NOT IN THE CEILING AS SHOWN. PDI- | | | WH 201 AND MANUF. INSTALLATION INSTRUCT- | | | IONS. | | | 4) SHT A-301, SECTION 11-4.24.5 A CLEAR | | | FLOOR SPACE AT LEAST 30"X48" COMPLYING | | | WITH 11-4.2.4 SHALL BE PROVIDED IN FRONT | | | OF A SINK TO ALLOW FORWARD APPROACH. THE | | | CLEAR FLOOR SPACE SHALL BE ON AN ACCESS- | | | IBLE ROUTE AND SHALL EXTEND A MAXIMUM OF | | | 19" UNDERNEATH THE SINK. (SEE FIG. 32). | | | 5) SHOW KNEE CLEARANCE 11-4.24.3, EXPOS- | | | ED PIPES AND SURFACES 11-4.24.6, AND | | | THE SINK SPECIFIED ON PLANS DOES NOT | | | MEET THE DEPTH REQUIREMENTS OF SECTION | | | 11-4.24.4 OF 6-1/2" (SEE ATTACHED SHEET) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|