| 2004-07-19 00:00:00 | ************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SUBMIT PANEL SCHEDULE |
| | SHOWING ALL MIN REQUIRED CIRCUITS PER |
| | 210.52,210.11,220 |
| | |
| | 2)NOTE: PLEASE PROVIDE CONN OF SWITCHES |
| | TO LTS. |
| | |
| | 3) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | TO BE W/IN 3'FROM LAV.EDGE. |
| | |
| | 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE SEE OFFICE IS CONSIDERED AN |
| | ADAPTABLE SLEEPING RM AND WILL REQUIRE |
| | SD'S INSIDE AND OUT. |
| | |
| | 5 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 6)NOTE: PLEASE SEE 410.8 FOR CLOSET LTS. |
| | FIX NOT SHOWN. |
| | |
| | 7)NOTE: PLEASE PROVIDE INFORMATION AS |
| | TO WHEATHER OR NOT A NEW PANEL OR |
| | SERVICE IS BEING INSTALLED.?? |
| | IF NEW PROVIDE INFORMATION ON RISER |
| | DIAGRAM. 215.5,310.16,110.9,240,230.70 |
| | ETC. |
| | |
| | 8)NOTE: PLEASE SHOW MEANS OF DISCONNECT |
| | REQUIRED FOR A/C UNITS PER 440.11 |
| | |
| | 9 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 10)NOTE: PLEASE SUBMIT LOAD CALCULATION |
| | ANDCLARIFY SIZE OF SERVICE. NEW OR |
| | EXISTING.? |
| | |
| | 11)NOTE: PLEASE SEE 210.70 FOR MISSING |
| | CONTROL FOR REGRESS LT. (OFFICE) |
| | |
| | 12)NOTE: PLEASE SEE FBC 104.2.1, PLANS |
| | ARE REQUIRED TO HAVE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | PLANS. |
| | |
| | 13)NOTE: PLEASE SEE VALUE MUST BE ADJUST |
| | -ED TO INCLUDE ALL LABOR AND MATERIALS |
| | EVEN IF OWNER SUPPLIED. VALUE MAY BE |
| | ADJUSTED PER MARSHALLS & SWIFT. FBC 104. |
| | 6.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |