Plan Review Details - Permit 04070391
Plan Review Stops For Permit 04070391
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-14 Cont ID  
Sent By alange Date 2004-07-14 Time 16:30 Rev Time 1.60
Received By alange Date 2004-07-14 Time 16:30 Sent To E
Notes
2004-07-14 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.WEST PALM BEACH AMMENDMENTS TO THE
 FBC 104.2.1SUBMIT 2 OR MORE COPIES OF
 SPECIFICATIONS AND DRAWINGS, DRAWN TO
 SCALE AND SUFFICIENT CLARITY AND DETAIL
 TO INDICATE THE NATURE OF THE WORK.
  
 4.I THE EXISTING SHED BUILDING TO
 BE REMAINING. IT IS ON SURVEY BUT NOT
 THE SITE PLAN.
  
 5.SUBMIT 2 COPIES OF PRODUCT
 APPROVALS FOR ROOFING, WINDOWS, IMPACT
 PROTECTION AND STRAPS USED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6. FBC 1005.4WINDOWS IN BEDROOMS DO
 NOT MEET MINIMUM OPENINGS FOR EMERGENCY
 ESCAPE RESCUE OPENINGS.
  
 7.SUBMIT A SOILS REPORT.
  
 8.VALUATION IS TOO LOW BASED ON
 SBCCI BUILDING VALUATION DATA.
 856 SQ FT. X 76.96 = $65,897 ADDITIONAL
 PERMIT FEES OF $876.12 ARE DUE.
  
 9.SUBMIT ENERGY CALCS.
  
 10.ROOF SHEATHING NAILING SCHEDULE
 DOES NOT MEET FBC REQUIREMENTS.
  
 11.FBC 3401.7.1.2.1 EXISTING BUILDING
 SHALL COMPLY WITH THIS SECTION.SHOW
 ON PLANS.
  
 12.FBC 905.2.1 SMOKE DETETORS SHALL
 COMPLY WITH THIS SECTION, SHOW ON PLAN.
  
 13.SHOW ON PLAN EXISTION ROOMS ON
 SOUTH SIDE AND SHOW LOCATION OF
 EXISTING WINDOWS FOR THE BEDROOMS IN
 THAT AREA.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-15 Cont ID  
Sent By alange Date 2004-07-14 Time 16:50 Rev Time 0.75
Received By btrobaug Date 2004-07-15 Time 13:10 Sent To P
Notes
2004-07-15 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE SERVICE REQUIRES A DISCONNECT PER
 230.70 NEC AND PROBABLY LOCATED OUTSIDE
 PER 230.70 WPB AMMENDMENTS.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 4} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 5} ADD NEW LOADS TO THE CALCULATION FOR
 A TOTAL DEMAND PER 215.15.
  
 6} SMOKE DETECTORS ARE REQUIRED PER 8-1.
 4.1.6 NFPA-72.
  
 7} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 8} PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6',12' RULE.
  
 9} PLEASE NOTE THAT 2(TWO) SETS OF PLANS
 ARE REQUIREDFOR REVIEW PER 104.2.1 FBC.
  
 PLEASE NOTE THAT THE SIGNATURE OF THE EN
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE
 INITIALS ARE NOT ACCEPTABLE PER F.B.P.E.
 ALSO A TITLE BLOCK IS REQUIRED, SAME COD
 E.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-29 Cont ID  
Sent By jleech Date 2004-07-20 Time 16:24 Rev Time 0.25
Received By hmoser Date 2004-07-29 Time 18:49 Sent To  
Notes
2004-07-29 00:00:00NO PLANS OR MANUAL (J)
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-20 Cont ID  
Sent By btrobaug Date 2004-07-15 Time 15:07 Rev Time 0.50
Received By jleech Date 2004-07-20 Time 16:24 Sent To M
Notes
2004-07-20 00:00:00DENIED;
 1.TWO SETS OF PLANS ARE REQUIRED.
 2.SIRNATURE OF ENGIEER IS REQUIRED OVER
 SEAL, NOT INITIALS. ALSO TITLE BLOCK
 WITH REQUIRED INFORMATION IS REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-30 Cont ID  
Sent By mmclean Date 2004-07-30 Time 16:42 Rev Time 0.00
Received By mmclean Date 2004-07-30 Time 16:42 Sent To I
Notes
***NONE***