Plan Review Details - Permit 04070294
Plan Review Stops For Permit 04070294
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-20 Cont ID  
Sent By btrobaug Date 2004-08-20 Time 11:46 Rev Time 0.75
Received By btrobaug Date 2004-08-20 Time 11:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-15 Cont ID  
Sent By csiegber Date 2004-07-08 Time 16:52 Rev Time 1.00
Received By btrobaug Date 2004-07-09 Time 14:19 Sent To  
Notes
2004-07-15 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE COMPUTED LOAD EXCEEDS THE
 SERVICE SIZE. PLEASE CHECK THE EXISTING
 SERVICE
 TO VERIFY RATING.IF THE SERVICE IS TO
 BE INCREASED PROVIDE A RISER DIAGRAM PER
 215.5.
  
 2} THE SMALL APPLIANCE CIRCUITS MUST
 COMPLY WITH 220.16(A).2@1500VA EACH,
 MIN.
  
 3} THE OVEN CALCULATION MUST COMPLY WITH
 220.19.8000VA MIN.
  
 4} THE PANEL LOCATED IN THE PANTRY IS IN
 VIOLATION OF THE CLEARANES IN ART. 110.
 26.
  
 5} PLEASE INDICATE THE LOCATION OF THE
 METER WITH REGARD TO THE PANELS SO THAT
 COMPLIANCE WITH 230.72 CAN BE
 DETERMINED.
  
 6}: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8(A)(6).
  
 7} PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6',12'. SEE REVIEWED PLANS.
  
 8} PLEASE SEE MISSING RECEPTACLES
 FRONT AND/OR REAR OF DWELLING.
 210.52(E).
  
 9) PLEASE SEE RECEPTACLES SERVING THE
 KITCHEN COUNTERSPACE TO MEET 210.52(C)
 SEC'S 1,2,3,4 AND 5.
  
 10} A RECEPTACLE IS REQUIRED IN THE POWD
 ER ROOM PER 210.52(D).
  
 11} THE RECEPTACLE ON THE PATIO MUST BE
 GFI PER 210.8(A)(3).
  
 12} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 13} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 14}PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPON-
 SIBLE FOR THE DESIGN. SECTION 104.2.1
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-08 Cont ID  
Sent By csiegber Date 2004-07-08 Time 16:52 Rev Time 0.00
Received By csiegber Date 2004-07-08 Time 16:52 Sent To E
Notes
***NONE***