Plan Review Details - Permit 04070099
| Plan Review Stops For Permit 04070099 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2004-07-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-07-09 |
Time |
16:52 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2004-07-08 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-07 |
Time |
15:38 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2004-07-08 |
Time |
09:17 |
Sent To |
P |
|
| Notes |
| 2004-07-08 00:00:00 | | | | PLEASE SUBMIT PLANS FOR THE ELECTRICAL | | | INSTALLATION OF THE PUMP, FEEDER AND | | | OCP SIZE, CONDUIT TYPE, BURIAL DEPTH ETC | | | | | | ALSO NOTE THERE WAS NO SIGNATURE FOR THE | | | ELECTRICAL CONTRACTOR ON THE | | | APPLICATION THEREFORE THE ELECTRICAL | | | PERMIT NEEDS TO BE APPLIED FOR | | | SEPARATELY. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-07-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-07 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-07 |
Time |
15:38 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-07-02 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-07-07 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-02 |
Time |
13:22 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2004-07-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-07-08 |
Time |
09:21 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-07-09 |
Time |
16:41 |
Sent To |
B |
|
| Notes |
| 2004-07-09 00:00:00 | | | | | | | | | | PASSED/PROVISO | | | | | | PRESSURE TESTS | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. | | | JOINTS AND CONNECTIONS | | | FBC PLMG SEC 605.21, PURPLE PRIMER REQ- | | | UIRED ON PVC PIPING. | | | PUMPS AND EQUIPMENT | | | SHALL BE MOUNTED ON A SUBSTANTIAL BASE | | | IN A MANNER THAT WILL ELIMINATE STRAIN | | | ON PIPING. SLAB SHALL BE A NOMINAL 4" | | | THICK. | | | NOTES) | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | Z |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2004-07-13 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2004-07-13 |
Time |
11:38 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-07-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-02 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-07-07 |
Time |
12:42 |
Sent To |
I |
|
| Notes |
| 2004-07-07 00:00:00 | DENIED, NEED TO PROVIDE SETBACKS FOR | | | THE WORK AND PROVIDE TWO COPY OF SITE | | | PLAN SHOWING THE WORK.CALLED OWNER | | | LEFT MSG WITH WIFE. |
|
|
|