Plan Review Details - Permit 04070082
Plan Review Stops For Permit 04070082
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-08-11 Cont ID  
Sent By jwitmer Date 2005-08-11 Time 12:08 Rev Time 0.55
Received By jwitmer Date 2005-08-11 Time 12:08 Sent To PC
Notes
2005-08-11 00:00:00REVISION STORM SHUTTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-08-17 Cont ID  
Sent By lsmith Date 2004-08-17 Time 12:06 Rev Time 1.00
Received By lsmith Date 2004-08-17 Time 12:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-23 Cont ID  
Sent By pkrauss Date 2004-08-17 Time 11:20 Rev Time 1.00
Received By lsmith Date 2004-07-23 Time 15:40 Sent To  
Notes
2004-07-23 00:00:00BUILDING PLAN REVIEW (2ND REVIEW) FAILED
  
 1. THERE ARE CHANGES TO THE SIGNED &
 SEALED PLANS WITHOUT THE ARCHITECT'S
 SIGNING OFF.NO CHANGES CAN BE MADE TO
 APPROVED PLANS WITHOUT THE ARCHITECT
 SIGNING THE CHANGES THAT ARE MADE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-07-12 Cont ID  
Sent By dpalmer Date 2004-07-23 Time 14:22 Rev Time 2.00
Received By lsmith Date 2004-07-12 Time 12:57 Sent To  
Notes
2004-07-12 00:00:00A SEPARATE PERMIT IS REQUIRED FOR THE
 STORM PANELS.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-03-28 Cont ID  
Sent By btrobaug Date 2006-03-28 Time 10:26 Rev Time 0.50
Received By btrobaug Date 2006-03-28 Time 10:26 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-03-23 Cont ID  
Sent By btrobaug Date 2006-03-23 Time 10:15 Rev Time 0.50
Received By btrobaug Date 2006-03-23 Time 10:15 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-08 Cont ID  
Sent By btrobaug Date 2006-03-08 Time 15:16 Rev Time 0.50
Received By btrobaug Date 2006-03-08 Time 15:15 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-08-10 Cont ID  
Sent By dpalmer Date 2004-08-10 Time 16:30 Rev Time 0.33
Received By dpalmer Date 2004-08-10 Time 16:18 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-23 Cont ID  
Sent By csiegber Date 2004-08-03 Time 16:14 Rev Time 0.50
Received By dpalmer Date 2004-07-23 Time 14:03 Sent To B
Notes
2004-07-23 00:00:00********* UNSAT **************
  
 1)NOTE: PLEASE SEE SOME NOTES FROM
 FIRST REVIEW NEED TO BE FULLY ADDRESSED.
  
 2)NOTE: PLEASE SEE NOTE #4 FROM FIRST
 REVIEW. ARC FAULT IS NOTED, HOWEVER BOTH
 PANEL SCHEDULES INDICATESD'S TO KIT
 AND BATH CIRCUITS??
  
 3)NOTE: PLEASE SEE CLEARENCE FOR A/C
 REQUIRED PER 110.26. A/C UNITS HAVE
 MOVED AND NOW HAVE WALLS. PLEASE SEE
 PLANS.
  
 4)NOTE: PLEASE SEE NOTE #10 FIRST REVIEW
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE SEE LOAD CALCS ON PANEL SCHEDULES
 DO NOT CORREALATE WITH NEW NOTES ADDED
 TO PLANS FOR LT LOADS.
  
 5)NOTE: PLEASE SEE THAT WHITE OUT AND
 CORRECTION MAY NOT BE ADDED TO SIGNED
 AND SEALED PLANS. THIS COMMENT IS PER
 FS 481.221.
 PLEASE MUST BE ORIG. ANY AND ALL CHANGES
 TO SIGNED AND SEALED PLANS MUST HAVE
 EACH ITEM , SIGNED AND DATED BY THE
 ARCH OF RECORD.
  
 PLEASE SEE NOTES 1,2, FROM FIRST REVIEW,
 SUB-PANEL ARE STILL SHOWN AS MCB ALONG
 WITH MAINS ON OUTSIDE OF HOUSE?
 150A PANEL STILL SHOWS 2/0'S,310.15 AND
 GROUNDING ELECTRODE CONDUCTOR IS NOW
 SHOWN AS 2/0?250.66
 THE ABOVE IS PERMITTED BUT IF SHOWN
 THIS WAY ON PLANS, THEN THEY WILL BE
 REQUIRED TO BE INSTALLED UNLESS REVISED
 PLANS ARE SUBMITTED AND PAY REVISION
 FEES AT A LATER DATE. THIS IS ONLY A
 NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-07 Cont ID  
Sent By csiegber Date 2004-07-21 Time 10:19 Rev Time 0.75
Received By dpalmer Date 2004-07-07 Time 09:40 Sent To M
Notes
2004-07-07 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE RISER AND PANEL
 -S. PANELS ARE SHOWN AS MCB AND RISER
 SHOWS MLO?
  
 2)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR
 150A DISC'S AND PANELS ARE SHOWN AS
 2/0'S. THIS IS PERMITTED AND IS ONLY A
 NOTE.
  
 3)NOTE: PLEASE SEE 250.50 FOR MISSING
 FOOTER STEEL AS PART OF THE GE SYSTEM.
  
 4 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE SEE SD'S ARE NOTED AS BEING
 WIRED INTO KIT/BATH LT CIRCUITS.
  
 5)NOTE: PLEASE SEE MISSING REQUIRED
 RECEPT FOR BATH RM. TO BE W/IN 3' OF
 SINK. 210.52D/210.11C3
  
 6)NOTE: PLEASE SEE 210.52 FOR SOME
 RECEPTSMISSING.
  
 7)NOTE: PLEASE CORRELATE LOADS SHOWN
 FOR AHU'S / AND LOAD CALCULATIONS ALONG
 WITH OCP.
 SHOWS 8KW AND 5KW ON ONE .
 LOADS IN LOAD CALCS?
  
 8)NOTE: PLEASE SEE AN ELECTRICAL WATER
 HEATER IS SHOWN ON PANEL SCHEDULE AND
 LOAD CALCS, HOWEVER PLANS ARE SHOWING
 WH AS GAS??
  
 9)NOTE: PLEASE SEE 110.26 FOR MIN SPACE
 FOR A/C CU'S. #'S 1&2."REDLINE ITEM".
  
 10)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 11)NOTE: PLEASE PROVIDE RM DESIGNATION
 ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 15:09 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 15:09 Sent To P
Notes
2006-04-10 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 11:00 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 11:00 Sent To B
Notes
2005-08-08 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 16:14 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 16:14 Sent To E
Notes
2004-08-03 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 10:19 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 10:19 Sent To E
Notes
2004-07-21 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-16 Cont ID  
Sent By mmclean Date 2004-07-20 Time 16:17 Rev Time 0.00
Received By csiegber Date 2004-07-16 Time 16:22 Sent To Z
Notes
2004-07-16 00:00:00TO MM BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-12 Cont ID  
Sent By mmclean Date 2004-07-06 Time 12:21 Rev Time 0.00
Received By lsmith Date 2004-07-02 Time 11:34 Sent To  
Notes
2004-07-06 00:00:00TO SFD RACK/E
2004-07-02 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-17 Cont ID  
Sent By pkrauss Date 2004-08-17 Time 11:20 Rev Time 0.00
Received By pkrauss Date 2004-08-17 Time 11:21 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-07-07 Cont ID  
Sent By dpalmer Date 2004-08-10 Time 16:30 Rev Time 0.25
Received By pkrauss Date 2004-07-07 Time 16:28 Sent To  
Notes
2004-07-07 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW/ENERGY & MANUAL J CALCULATIONS
 ONLY.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-04-11 Cont ID  
Sent By pschmitz Date 2006-04-11 Time 12:13 Rev Time 0.00
Received By pschmitz Date 2006-04-11 Time 12:12 Sent To  
Notes
2006-04-11 00:00:00REVISION REMOVE ICE MAKER

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-07-12 Cont ID  
Sent By lsmith Date 2004-07-12 Time 12:56 Rev Time 0.33
Received By lsmith Date 2004-07-10 Time 07:21 Sent To  
Notes
2004-07-12 00:00:00PER JL 7/10/04 LS

Review Stop Z ZONING
Rev No 2 Status P Date 2004-07-20 Cont ID  
Sent By mmclean Date 2004-07-20 Time 16:17 Rev Time 0.00
Received By mmclean Date 2004-07-20 Time 16:17 Sent To I
Notes
2004-07-20 00:00:00DENIED, 2ND REVIEW STILL OVER THE HEIGHT
 OF 33FT.CALLED CONTR.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-07-06 Cont ID  
Sent By csiegber Date 2004-07-16 Time 16:22 Rev Time 0.00
Received By mmclean Date 2004-07-06 Time 12:21 Sent To I
Notes
2004-07-06 00:00:00DENIED, HOUSE IS OVER THE HEIGHT
 REQUIRMENT OF 33FT.CALLED CONTR.
  
 MUST PULL A SEPARATE PERMIT FOR POOL AND
 CBS WALL WITH UTILITY APPROVAL.