| 2004-08-25 00:00:00 | *************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 3) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE SEE SOME MISSING. |
| | |
| | 5 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 6)NOTE: PLEASE SUBMIT PANEL SCHEDULES |
| | SHOWING MIN CIRCUITING REQ'D UNDER NEC |
| | 2002. |
| | |
| | 7)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN TO DETACH- |
| | -ED PANEL AT GARAGE. |
| | |
| | 8)NOTE: PLEASE SEE MAIN HOUSE HAS A NOTE |
| | FOR PANEL AT GROUND FLR YET THERE IS A |
| | PANEL ALSO SHOWN ON SECOND FLR?? |
| | |
| | 9 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 10)NOTE:PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 11)NOTE: PLEASE SHOWS REQ'D DISC'S FOR |
| | A/C EQUIPMENT. PER 440.11 |
| | PLEAS ALSO SHOWN A/C UNIT LOCATIONS. |
| | |
| | 12)NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210.70 AND LS-101 5-8 |
| | **DETACHED EGRESS TO OUTSIDE** |
| | |
| | 13)NOTE: PLEASE SEE MISSING RECEPTS TO |
| | BE W/IN 3' OF SINKS. 210.52D |
| | |
| | 14)NOTE: PLEASE SEE EXISTING GARAGE |
| | AREA WILL REQUIRE LT/ GFI. 210.70, |
| | 210.52G, 210.8 |
| | |
| | 15)NOTE: PLEASE ALSO SEE DEATCHED BLDG |
| | RMS WILL ALSO REQUIRE ARC FAULT. |
| | PLEASE SEE RM W/ ONLY ONE RECEPT SHOWN. |
| | /NOT SHOWN AS A CLOSET?? 210.52 |
| | |
| | 16)NOTE: PLEASE SHOW ROOM DESIGNATION |
| | ON PLANS. |
| | |
| | 17)NOTE: *** PLANS CAME IN AS A REVISION |
| | UNDER BLDG/DEMO/INT REMOD PERMIT. |
| | PLEASE SUBMIT PLANS UNDER AN ELECTRICAL |
| | PERMIT APPLICATION WITH VALUE AND |
| | COMPLETE SCOPE OF ELECTRICAL WORK. |
| | PLANS SHOW ALL ELECTRICAL BEING BROUGHT |
| | UP TO CODE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |