Plan Review Details - Permit 04070034
Plan Review Stops For Permit 04070034
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 09:23 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 09:23 Sent To P
Notes
2004-08-30 00:00:00TO GAS/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:24 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 16:24 Sent To P
Notes
2004-07-01 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-09-22 Cont ID  
Sent By kstevens Date 2004-09-21 Time 18:34 Rev Time 0.50
Received By kstevens Date 2004-09-21 Time 18:34 Sent To  
Notes
2004-09-21 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) REVISION NOT CLEAR AND HARD TO READ.
 2) SIGNATURE AND PRINTED NAME OF PERSON
 THAT DESIGNED THE PLAN ORIGINALLY SHALL
 NEED TO BE RESIGNED IF DESIGNED BY THAT
 PERSON. IF NOT NEW NAME TO BE PRINTED
 ON PLAN AND NEW SIGNATURE REQUIRED,
 3) INDICATE SIZE OF EXISTING PE PIPE TO
 EXISTING GRILL LINE.
 4) GAS PRESSURE NOTED AS 8" WC, PLEASE
 CLARIFY AS ALL FBC-2001 CHARTS ARE FOR
 1/2 LB OR 12" TO 14" WC.
 5) INDICATE WHY THE 6" SLEEVE IS BEING
 USED. WHAT IS ABOVE THE SLEEVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-07-17 Cont ID  
Sent By csiegber Date 2004-08-30 Time 09:23 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***