| Plan Review Stops For Permit 04061232 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
14 |
Status |
P |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-29 |
Time |
10:08 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-08-29 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2005-08-29 00:00:00 | REVISED A2, 2.1, 3.2 DATED 8/17/05 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
13 |
Status |
F |
Date |
2005-08-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-19 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-08-19 |
Time |
16:43 |
Sent To |
PC |
|
| Notes |
| 2005-08-19 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)SEE FBC106.4.2.THIS WAS A PROVISO | | | ON THE PLAN.PLEASE READ AND PROVIDE AN | | | AFFIDAVIT AND COMPUTATIONS. | | | | | | 2.)THE LETTER SUBMITTED STATES A | | | DESIGN FLOOR LOAD OF 50PSF.SEE FBC | | | TABLE 1604.1.THIS IS EITHER LIGHT OR | | | HEAVY STORAGE, 125 OR 250 PSF.STATE | | | WHETHER IT IS LIGHT OR HEAVY STORAGE, | | | DESIGN LOAD, AND PROVIDE AN AFFIDAVIT | | | AND CALCULATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
P |
Date |
2005-05-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-20 |
Time |
08:58 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-05-20 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2005-05-20 00:00:00 | ****PROVISO**** | | | | | | ***PROVIDE AFFIDAVIT***FBC106.4.2 (RE | | | STORAGE OCCUPANCY). IT SHALL BE THE | | | RESPONSIBILITY OF THE OWNER, AGENT, | | | PROPIETOR OR OCCUPANT OF GROUP S AND | | | GROUP F OCCUPANCIES, OR ANY OCCUPANCY | | | WHERE EXCESSIVE FLOOR LOADING IS LIKELY | | | TO OCCUR, TO EMPLOY A COMPETENT | | | ARCHITECT OR ENGINEER IN COMPUTING THE | | | SAFE FLOOR LOAD CAPACITY. ALL SUCH | | | COMPUTATIONS SHALL BE ACCOMPANIED BY AN | | | AFFADAVIT FROM THE ARCHITECT OR ENGINEER | | | STATING THE SAFE ALLOWABLE FLOOR LOADS | | | ON EACH FLOOR IN POUNDS PER SQ FT.THE | | | COMPUTATIONS & AFFADAVIT SHALL BE FILED | | | AS A PERMANENT RECORD OF THE BLDG DEPT. | | | | | | ***PROVIDE SIGNAGE***FBC106.4.3.SIGNS | | | REQUIRED. IN EVERY BUILDING OR PART OF A | | | BUILDING USED FOR STORAGE, INDUSTRIAL OR | | | HAZARDOUS PURPOSES, THE SAFE FLOOR | | | LOADS, AS REVIEWED BY THE BUILDING | | | OFFICIAL ON THE PLAN, SHALL BE MARKED ON | | | PLATES OF APPROVED DE SIGN WHICH SHALL | | | BE SUPPLIED & SECURELY AFFIXED BY THE | | | OWNER OF THE BUILDING IN A CONSPICUOUS | | | PLACE IN EACH STORY TO WHICH THEY | | | RELATE. SUCH PLATES SHALL NOT BE REMOVED | | | OR DEFACED, & IF LOST, REMOVED THE OWNER | | | OF THE BUILDING SHALL REPLACE THEM. | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
F |
Date |
2005-05-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-19 |
Time |
13:11 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2005-05-19 |
Time |
11:42 |
Sent To |
PC |
|
| Notes |
| 2005-05-19 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)TWO SETS OF PLANS SUBMITTED. | | | PLEASE COLLATE SHEETS INTO ONE SET FOR | | | REVIEW/ISSUANCE. | | | | | | 2.)THE UL DETAIL REQUESTED HAS NOT | | | BEEN INCORPORATED INTO THE PLAN AS | | | REQUESTED BY THE PREVIOUS REVIEW.A | | | PHOTOCOPY OF THE UL ASSEMBLY HAS BEEN | | | PROVIDED FOR YOU; PLEASE STAPLE INTO THE | | | PLAN.HOWEVER IN THE FUTURE A FIRE | | | SEPARATION IS TO INCLUDE A DETAIL, NOT | | | JUST A UL REFERENCE NUMBER. | | | | | | | | | | | | ****PROVISO**** | | | | | | ***PROVIDE AFFIDAVIT***FBC106.4.2 (RE | | | STORAGE OCCUPANCY). IT SHALL BE THE | | | RESPONSIBILITY OF THE OWNER, AGENT, | | | PROPIETOR OR OCCUPANT OF GROUP S AND | | | GROUP F OCCUPANCIES, OR ANY OCCUPANCY | | | WHERE EXCESSIVE FLOOR LOADING IS LIKELY | | | TO OCCUR, TO EMPLOY A COMPETENT | | | ARCHITECT OR ENGINEER IN COMPUTING THE | | | SAFE FLOOR LOAD CAPACITY. ALL SUCH | | | COMPUTATIONS SHALL BE ACCOMPANIED BY AN | | | AFFADAVIT FROM THE ARCHITECT OR ENGINEER | | | STATING THE SAFE ALLOWABLE FLOOR LOADS | | | ON EACH FLOOR IN POUNDS PER SQ FT.THE | | | COMPUTATIONS & AFFADAVIT SHALL BE FILED | | | AS A PERMANENT RECORD OF THE BLDG DEPT. | | | | | | ***PROVIDE SIGNAGE***FBC106.4.3.SIGNS | | | REQUIRED. IN EVERY BUILDING OR PART OF A | | | BUILDING USED FOR STORAGE, INDUSTRIAL OR | | | HAZARDOUS PURPOSES, THE SAFE FLOOR | | | LOADS, AS REVIEWED BY THE BUILDING | | | OFFICIAL ON THE PLAN, SHALL BE MARKED ON | | | PLATES OF APPROVED DE SIGN WHICH SHALL | | | BE SUPPLIED & SECURELY AFFIXED BY THE | | | OWNER OF THE BUILDING IN A CONSPICUOUS | | | PLACE IN EACH STORY TO WHICH THEY | | | RELATE. SUCH PLATES SHALL NOT BE REMOVED | | | OR DEFACED, & IF LOST, REMOVED THE OWNER | | | OF THE BUILDING SHALL REPLACE THEM. | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-09 |
Time |
08:21 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-05-09 |
Time |
08:21 |
Sent To |
PC |
|
| Notes |
| 2005-05-09 00:00:00 | REVISION PREPARED BY BIJAN PARSSI, PE, | | | A/C CURB PLAN AND OPENING DETAIL FOR | | | DOOR |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
F |
Date |
2005-05-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-05 |
Time |
09:59 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2005-05-05 |
Time |
09:59 |
Sent To |
PC |
|
| Notes |
| 2005-05-05 00:00:00 | REVISION DATED 3/30/05 | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.) SHEET A1.1 SHOWS THE FREIGHT LIFT AS | | | REMAINING, S1 SHOWS THE LIFT REMOVED. | | | STRUCTURALS AND ARCHITECTURALS SHOULD BE | | | CONSISTENT. | | | | | | 2.)PROVIDE STAIR WIDTHS, FBC1004. | | | | | | 3.)DECLARE AN OCCUPANT LOAD, FBC TABLE | | | 1003.1. | | | | | | 4.)THE PRODUCT APPROVAL FOR THE | | | EXTERIOR DOOR AND THE ENERGY CALC HAVE | | | BEEN STAMPED AND A COPY RETAINED. | | | | | | 5.)SEE PREVIOUS LIST IN REGARDS TO | | | VERTICAL ACCESSIBILITY, FBC11-4.1.3. | | | HOW IS THIS BEING ADDRESSED? | | | | | | 6.)A 1 HR PROTECTED STAIR IS SHOWN | | | A1.0.PLEASE EXPLAIN HOW 1 HR IS | | | MAINTAINED THROUGH THE SECOND FLOOR. | | | SEE FBC1006.1.3.1, 705.1.2.OPENINGS | | | ARE SHOWN WITHOUT FIRE RESISTANCE | | | INFORMATION. | | | | | | 7.)A1.2, STAIR DETAILS HAS TWO DETAILS | | | WHICH ARE ILLEGIBLE. | | | | | | 8.)A HANDRAIL IN COMPLIANCE WITH | | | FBC1007.5 IS REQUIRED ON BOTH SIDES OF | | | THE STAIRS FBC1007.5.2.ONLY ONE IS | | | SHOWN. | | | | | | 9.)SHEET A1.2, AN EXIT CORRIDOR IS | | | SHOWN.WHERE IS THIS ON THE PLAN?IT | | | REFERS TO UL-U465; PROVIDE THIS DETAIL | | | ON THE PLAN. | | | | | | 10.) WHEN RESUBMITTING, PLEASE PROVIDE A | | | TRANSMITTAL SHEET EXPLAINING HOW THESE | | | ITEMS ARE BEING ADDRESSED. | | | | | | 11.)NOTE - STRUCTURALS SUBMITTED | | | SEPARATELY REVIEWED AGAIN AND PUT WITH | | | ARCHITECTURAL REVISION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2005-04-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-04-29 |
Time |
10:43 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-04-29 |
Time |
10:43 |
Sent To |
PC |
|
| Notes |
| 2005-04-29 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE PREVIOUS REVISION WAS DENIED | | | WITH COMMENTS REGARDING EGRESS, VERTICAL | | | ACCESSIBILITY AND BUILDING TYPE. THERE | | | IS A CONFLICT BETWEEN THE DENIED | | | ARCHITECTURALS AND THE STRUCTURAL PLANS | | | SUBMITTED.AS THESE STRUCTURALS DO NOT | | | CORRELATE WITH ANYTHING APPROVED IN OUR | | | FILE, PLEASE SUBMIT EITHER WITH THE | | | REVISED ARCHITECTURALS OR AFTER THEY | | | HAVE BEEN REVIEWED FOR CODE COMPLIANCE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2005-04-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-04-22 |
Time |
10:43 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-04-22 |
Time |
10:43 |
Sent To |
PC |
|
| Notes |
| 2005-04-22 00:00:00 | SEALED LETTER FROM JIM PAYNE; BOTKIN | | | PARSSI IS EOR FOR JOB (ONLY ONE COPY | | | SUBMITTED) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2005-04-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-04-06 |
Time |
10:25 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-04-06 |
Time |
10:25 |
Sent To |
PC |
|
| Notes |
| 2005-04-06 00:00:00 | ****CORRECTIONS**** | | | VARIOUS DETAILS PREPARED BY BIJAN | | | PARSSI, PE | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE FORMER ARCHITECT AND ENGINEER | | | HAVE SUBMITTED LETTERS STATED THAT THEY | | | ARE NO LONGER DOR/EOR OF THE PROJECT. | | | JIM PAINE, ARCHITECT, HAS SUBMITTED NEW | | | PLANS.IS BIJAN PARSSI, PE THE NEW EOR | | | FOR THIS PROJECT?OR IS THIS DELEGATED | | | ENGINEERING?IF THIS IS DELEGATED | | | ENGINEERING, THE DETAILS ARE TO BE | | | REVIEWED BY DOR.IF HE IS THE NEW EOR, | | | SUBMIT A LETTER STATING THIS AS ALL | | | STRUCTURALS TO DATE HAVE BEEN SUBMITTED | | | BY JIM PAINE. | | | | | | 2.)THE COLUMN CONNECTION PLAN IS NOT | | | SEALED. | | | | | | 3.)AS PER CONVERSATION WITH THE | | | CONTRACTOR, THE COLUMN CONNECTION PLAN | | | IS SHOWING A C CHANNEL AND A STEEL | | | COLUMN.THE DIMENSION 4X4X4 IS | | | CONFUSING, IMPLIES A HEIGHT OF 4" RATHER | | | THAN A COLUMN THE FULL HEIGHT.THE C | | | CHANNEL IS SHOWN GRAPHICALLY BUT NOT | | | SPECIFIED, WHAT SIZE?THE ANCHORING OF | | | THE STEEL COLUMN AND C CHANNEL IS NOT | | | SPECIFIED.ANCHORING AT THE BOTTOM OF | | | THE COLUMN IS SPECIFIED, ASSUMING TO | | | EXISTING SLAB ON 1ST FLOOR AS A CONCRETE | | | ANCHOR IS SPECIFIED.IS THERE A BASE | | | PLATE FOR THE COLUMN?SPECIFY WHERE | | | THIS DETAIL IS TO BE USED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2005-03-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-03-24 |
Time |
13:26 |
Rev Time |
5.00 |
| Received By |
shill |
Date |
2005-03-23 |
Time |
15:15 |
Sent To |
P |
|
| Notes |
| 2005-03-24 00:00:00 | PERMIT #04061232 | | | | | | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)TYPE IV IS DECLARED ON THE COVER | | | SHEET.WOOD COLUMNS ARE SHOWN ON A1.0. | | | ALSO A1.0 STATES THAT THE FLOOR FINISH | | | IS WOOD, BUT A1.1 NOTES AN EXISTING WOOD | | | DECK.IS THE WOOD FLOOR NOTED A FLOOR | | | FINISH OR THE FLOOR FRAMING?OUR PLANS | | | CURRENTLY ON FILE SHOW WOOD JOISTS FOR | | | THE FLOOR FRAMING.SEE FBC606 REGARDING | | | DEFINITION OF TYPE IV BUILDING. | | | | | | 2.)THE COVER SHEET SHOWS 5739 SF FOR | | | FIRST FLOOR TWICE.PLEASE NOTE SECOND | | | FLOOR SQUARE FOOTAGE. | | | | | | 3.)SHEET A1.0 HAS A NOTE REGARDING A 1 | | | HOUR SEPARATION.WHAT IS THE PURPOSE OF | | | THIS SEPARATION?HOW WILL THE 1 HOUR | | | SEPARATION BE MAINTAINED WHERE THE WOOD | | | COLUMNS MEET THE BOTTOM OF THE FLOOR | | | CEILING ASSEMBLY?A FREIGHT LIFT IS | | | SHOWN ON A1.0; PROVIDE 1 HR FIRE RATING | | | INFORMATION. | | | | | | 4.)SHEET A1.0 BOTTOM RIGHT CORNER OF | | | PLAN SHOWS 1HR ENCLOSURE (SEE DETAIL). | | | NO DETAIL PROVIDED AND IT IS UNCLEAR HOW | | | THE 1 HR SEPARATION IS MAINTAINED | | | BETWEEN THE FIRST AND SECOND FLOORS AS | | | THE FLOOR PLAN SHOWS A WALL WHICH DOES | | | NOT ENCLOSE THE STAIRS. | | | | | | 5.)THERE IS A NOTE ON SHEET A1.3 THAT | | | ALL EXTERIOR OPENINGS ARE EXISTING. | | | OPENINGS AFFECTED BY THE SCOPE OF WORK | | | ON THIS PERMIT ARE TO BE CODE COMPLIANT | | | AND SHOW COMPLIANCE ON THE PLAN.ALSO | | | THERE IS A NEW DOOR SHOWN. | | | | | | 6.)PLEASE SEE FBC1006.1.3.2.IF THIS | | | BUILDING IS A TYPE V, THE STAIRWAY AT | | | THE TOP LEFT IS TO HAVE 3 HR PROTECTION. | | | | | | 7.)BASED ON PROPERTY APPRAISER?S | | | VALUATION, THIS IS AN OVER 50% | | | IMPROVEMENT, FBC3401.7.2.6. | | | | | | 8.)OPENINGS IN THE EXIT STAIR ARE | | | PROHIBITED EXCEPT AS NOTED IN | | | FBC1006.1.3.1 (WINDOW SHOWN IN | | | STAIRWAY). | | | | | | 9.)SHOW OPENING PROTECTIVES FOR THE | | | STAIRS AS REQUIRED BY FBC TABLE 705.1.2. | | | | | | 10.)DOOR 2, 1ST FLOOR, DOES NOT APPEAR | | | TO LEAD ANYWHERE.IF IT IS AN OPENING | | | INTO THE STAIR, INDICATE OPENING | | | PROTECTIVE REQUIREMENT. | | | | | | 11.) PROVIDE TEST REPORTS AND FLORIDA | | | STATE OR LOCAL PRODUCT APPROVAL FOR THE | | | NEW EXTERIOR DOOR. | | | | | | 12.) PROVIDE GUARDRAIL AND HANDRAIL | | | DETAILS.NOTE DESIGN CRITERIA IN | | | COMPLIANCE WITH FBC1608.1.1 (HANDRAIL) | | | AND FBC 1608.2.2 (GUARDRAIL).COMPLY | | | WITH ALL REQUIREMENTS OF FBC CHAPTERS 10 | | | AND 11. | | | | | | 13.) PROVIDE ACCESSIBILITY DETAILS; | | | ACCESSIBLE ENTRY, BATHROOM DETAILS | | | INCLUDING DIMENSIONS FOR GRAB BARS, LAV, | | | WC FBC CHAPTER 11. | | | | | | 14.) PROVIDE LOADING INFORMATION FOR | | | ROOFTOP MECHANICAL EQUIPMENT, DESIGN | | | LOAD LIMITATIONS OF EXISTING ROOF. | | | | | | 15.) ENERGY CALCS REQUIRED, FBC13. | | | | | | 16.) VERTICAL ACCESSIBILITY REQUIRED, | | | FBC11-4.1.3. | | | | | | 17.) PROVIDE DESIGN PRESSURES FOR THE | | | EXTERIOR DOOR AND DESIGN CRITERIA | | | FBC1606.1.7. | | | | | | 18.) DMP REVIEW REQUIRED.WHEN | | | RESUBMITTING, PLEASE INDICATE THAT A | | | ZONING REVIEW IS REQUIRED ON THE | | | RESUBMITTAL SHEET TO HELP EXPEDITE PLAN | | | REVIEW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2004-12-23 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-12-23 |
Time |
09:57 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
2004-12-23 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2004-12-23 00:00:00 | BUILDING PLAN REVIEW: PROVISO | | | | | | 1. SUBMIT MFGRS. SPECS ON STAIR SYSTEM. | | | | | | 2. SUBMIT MFGRS. SPECS. ON ELEVATOR | | | | | | 3. THE NOTICE OF COMMENCEMENT HAS | | | EXPIRED. A NEW NOTICE OF COMMENCEMENT | | | MUST BE FILED AT THE COUNTY CLERK OFFICE | | | & SUBMITTED BEFORE A PERMIT CAN BE | | | ISSUED. | | | | | | NOTE: DRAWING SHEET INDEX SHOWS SHEETS | | | S1, S2, & S3.THESE PLANS ARE NOT | | | ATTACHED. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLAN REVIEWER | | | 805-6713 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-11-19 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-11-19 |
Time |
08:12 |
Rev Time |
1.50 |
| Received By |
lsmith |
Date |
2004-11-19 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2004-11-19 00:00:00 | BUILDING PLAN REVIEW FAILED: | | | | | | 1. SUBMIT MFGRS. SPECS ON STAIR | | | SYSTEMS. | | | | | | 2. SUBMIT MFGRS. SHEETS ON ELEVATOR. | | | | | | 3. SUBMIT FLORIDA PRODUCT APPROVAL FOR | | | THE NEW DOOR ON THE WEST ELEVATION OF | | | BUILDING. | | | | | | 4. PER SEC. 481.221 ALL PLANS SIGNED BY | | | ARCHITECT MUST BE DATED. | | | | | | 5. | | | SUBMIT DETAIL FOR PENATRATIONS THROUGH | | | 2ND FLOOR & ROOF FOR EXHAUST SYSTEM. | | | SEE MECHANICAL COMMENTS. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-08-30 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-08-30 |
Time |
13:38 |
Rev Time |
1.50 |
| Received By |
lsmith |
Date |
2004-08-30 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2004-08-30 00:00:00 | BUILDING PLAN REVIEW: PROVISO | | | | | | 1. SUBMIT MFGRS. SHEETS ON STAIR SYSTEM | | | | | | 2. SUBMIT MFGRS. SHEETS ON ELEVATOR | | | | | | 3. SUBMIT DETAIL FOR PENATRATIONS THROUG | | | H 2ND FLOOR & ROOF FOR EXHAUST SYSTEM. | | | SEE SHEETS M1 & M2 & MECHANICAL NOTES. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-15 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-06-30 |
Time |
14:41 |
Rev Time |
1.50 |
| Received By |
lsmith |
Date |
2004-06-30 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2004-07-15 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | | | 1. SEE ELEC & MECH NOTES ON SIGNATURE | | | ON PLANS. | | | | | | 2. SUBMIT PRODUCT APPROVALS FOR SKYLIGHT | | | (FLORIDA & DADE COUNTY) | | | | | | 3. SUBMIT SHOP DRAWINGS FOR METAL STAIRS | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
P |
Date |
2005-08-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-18 |
Time |
19:16 |
Rev Time |
0.60 |
| Received By |
dpalmer |
Date |
2005-08-18 |
Time |
18:47 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-18 |
Time |
10:02 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-05-18 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2005-05-18 00:00:00 | REDLINED 250.122 FOR SIZING OF EQUIPMENT | | | GROUNDS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
F |
Date |
2005-05-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-17 |
Time |
07:04 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-05-17 |
Time |
07:04 |
Sent To |
B |
|
| Notes |
| 2005-05-17 00:00:00 | ********* UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE ELECTRICAL REVSIONS | | | SUBMITTED WITHOUT ANY REVSIONS BEING | | | MADE. | | | PLEASE SEE THESE PLANS ARE THE SAME | | | ELECTRICAL PLANS REVIEWED AND STAMPED ON | | | PREVIOUS SUBMITTAL WHICH WERE REVIEWED | | | AND STAMPED ON MAY 11TH. | | | IF REVISIONS ARE TO BE MADE, PLEASE | | | REVISE,IDENTIFY WITH CLOUDS/TRIANGKE AND | | | CORRELATE WITH REV'S DATED AND SHOWN IN | | | TITLE BLOCK AREA. | | | | | | *** NOTE** | | | PLEASE SEE EQUIPMENT GROUNDING CONDUCTOR | | | FROM MAIN DISCONNECT TO PANEL STILL | | | BEING SHOWN AS 1/0? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2005-05-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-11 |
Time |
11:40 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-05-11 |
Time |
11:37 |
Sent To |
I |
|
| Notes |
| 2005-05-11 00:00:00 | PLANS REMOVED FROM INCOMING, REVIEWED | | | FOR ELECTRICAL , STAMPED ELECTRICAL AND | | | SENT BACK TO INCOMING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2005-04-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-05 |
Time |
08:50 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-04-05 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2005-04-05 00:00:00 | ********* UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS | | | REVIEW AND REVIEW ON 11/29/04 | | | | | | 2)NOTE: PLEASE SEE AS REQUESTED ON | | | PREVIOUS REVIEW: LETTERS FROM BOTH THE | | | ORIGINAL ARCHITECT AND ENGINEER WERE | | | REQUESTED TO RELEASE THEM FROM DESIGNERS | | | OF RECORD. THIS REQUEST WAS TO EACH HAVE | | | SIGNED, DATED, SEALED AND NOTORIZED | | | LETTERS. | | | PLEASE SEE ENGINEER'S LETTER WAS NOT | | | NOTORIZED AND ARCH'S LETTER WAS NOT | | | SEALED, DATED OR NOTORIZED. | | | | | | 3)NOTE: PLEASE SEE THE FOLLOWING EXCERPT | | | TAKEN DIRECTLY FROM NOTES ON 11/29/04 | | | FOR REDLINED PLANS. | | | | | | ***** PLANS REDLINED ****** | | | | | | 1)NOTE: PLEASE SEE GROUNDING ELECTRODE | | | CONDUCTOR STILL NOT SHOWN PER 250.66. | | | TWO SETS OF 3/0'S,,,, 1/0 MIN GEC. | | | | | | | | | 2)NOTE: PLEASE ALSO SEE AN EQUIPMENT | | | GROUNDING CONDUCTOR IS NOW ADDED FROM | | | METER TO MAIN? AN EQUIPMENT GRND IS NOT | | | INSTALLED UNTIL AFTER THE FIRST MEANS OF | | | DISCONNECT. | | | 250.6, 250.24 | | | | | | | | | ** BOTH OF THE ABOVE WERE REDLINED ON | | | PLANS. IF ANY REV'S ARE MADE TO PLANS, | | | PLEASE ALSO CORRECT THE ABOVE AT THAT | | | TIME. *** | | | | | | 4)NOTE: PLEASE SEE 700.12E FOR | | | CIRCUITING OF EM/EXT LTS. THIS WAS NOTED | | | ON ALL PREVIOUS REVIEWS AND SOME | | | CIRCUITING IS STILL NOT SHOWN AND SOME | | | NOT PER 700.12E. | | | | | | PLEASE SEE FS 553.80(2)(B) WITH RESPECT | | | TO DESIGN PROFESSIONAL. THIS IS ONLY A | | | NOTICE GIVEN AT THIS TIME. | | | | | | PLEASE MAKE THE ABOVE CORRECTIONS AND | | | SUBMIT REVISED PLANS FOR REVIEW. ONCE | | | AGAIN, IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL TO GO | | | OVER ANY COMMENTS. | | | THIS WAS STATED ON ALL 5 PREVIOUS | | | REVIEWS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2005-03-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-01 |
Time |
06:20 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-03-01 |
Time |
06:14 |
Sent To |
|
|
| Notes |
| 2005-03-01 00:00:00 | *********UNSAT******* | | | | | | PLEASE SEE PREVIOUS REVIEW NOTES FOR | | | ITEMS REDLINED REQUESTING," IF THERE ARE | | | ANY REVISIONS, PLEASE MAKE CORRECTIONS | | | TO PLANS AT THAT TIME". PLEASE SEE NOTES | | | FROM PREVIOUS REVIEW BELOW. | | | | | | | | | | | | 1)NOTE: PLEASE SEE PLANS NOW HAVE A NEW | | | ARCHITECT OF RECORD. | | | PLEASE SUBMIT A SIGNED/SEALED NOTORIZED | | | LETTER FOR CHANGING ARCH AND ENGINEER | | | FROM EACH PERSON. | | | PLEASE SEE NEW ARCHITECT MUST SUBMIT | | | COMPLETE SETS OF PLANS SIGNED AND SEALED | | | FOR COMPLETE SCOPE OF WORK. | | | | | | | | | PLEASE SEE BELOW WAS REDLINED ON | | | ORIGINAL PLANS AND SHOULD BE ADDRESSED | | | AT THIS TIME WHEN PLANS ARE DONE. | | | | | | 1)NOTE: PLEASE SEE GROUNDING ELECTRODE | | | CONDUCTOR STILL NOT SHOWN PER 250.66. | | | TWO SETS OF 3/0'S,,,, 1/0 MIN GEC. | | | | | | | | | 2)NOTE: PLEASE ALSO SEE AN EQUIPMENT | | | GROUNDING CONDUCTOR IS NOW ADDED FROM | | | METER TO MAIN? AN EQUIPMENT GRND IS NOT | | | INSTALLED UNTIL AFTER THE FIRST MEANS OF | | | DISCONNECT. | | | 250.6, 250.24 | | | | | | | | | 3)NOTE: PLEASE SEE REDLINED EM/EXT LT | | | PER | | | 700.12E. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-11-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-29 |
Time |
06:36 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-11-29 |
Time |
06:28 |
Sent To |
|
|
| Notes |
| 2004-11-29 00:00:00 | ***** PLANS REDLINED ****** | | | | | | 1)NOTE: PLEASE SEE GROUNDING ELECTRODE | | | CONDUCTOR STILL NOT SHOWN PER 250.66. | | | TWO SETS OF 3/0'S,,,, 1/0 MIN GEC. | | | | | | | | | 2)NOTE: PLEASE ALSO SEE AN EQUIPMENT | | | GROUNDING CONDUCTOR IS NOW ADDED FROM | | | METER TO MAIN? AN EQUIPMENT GRND IS NOT | | | INSTALLED UNTIL AFTER THE FIRST MEANS OF | | | DISCONNECT. | | | 250.6, 250.24 | | | | | | | | | ** BOTH OF THE ABOVE WERE REDLINED ON | | | PLANS. IF ANY REV'S ARE MADE TO PLANS, | | | PLEASE ALSO CORRECT THE ABOVE AT THAT | | | TIME. *** | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-10-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-10-25 |
Time |
12:02 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2004-10-25 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2004-10-25 00:00:00 | ********* UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE NOTE#4 FROM PREVIOUS | | | REVIEW. A GROUNDING ELECTRODE SYSTEM | | | IS NOW SHOWN, HOWEVER SIZING OF GEC IS | | | TO BE SIZED FOR THE PARALLEL 4/0'S | | | PER 250.66. SHOWS A #3, WHICH IS NOT | | | LARGE ENOUGH. | | | | | | 2)NOTE : PLEASE SEE NOTE # 5FROM | | | PREVIOUS REVIEW. PLEASE SEE MISSING | | | LICENSE # FOR FIRM ONA-SHEETS. | | | PLEASE SEE FAC 61G1-16.004 AND FS 481.- | | | .219. | | | THIS IS REQUIRED, WHEATHER OR NOT | | | COMMENT IS MADE BY OTHER REVIEWER(S). | | | | | | 3)NOTE: PLEASE SEE LOAD FOR WASHER/DRYER | | | IS SHOWN AS 7KW ON A 2P-30A BRKR FOR | | | OCP. | | | PLEASE ALSO SEE 11KW LOAD SHOWN ON A | | | 2P-30A BRKR FOR ELEVATOR. | | | | | | 4)NOTE: PLEASE CLARIFY MISSING EQUIPMENT | | | GROUNDING CONDUCTORS FROM MAIN TO PANEL | | | AND FROM PANEL A TO B. | | | 250.110,250.122 | | | | | | 5)NOTE: PLEASE SEE MAIN DISCONNECT IS | | | SHOWN AS MLO. APPEARS TO BE A MISPRINT?? | | | | | | | | | PLEASE SEE POSSIBLE COMMENTS FROM OTHER | | | REVIEWERS WHICH MAY HAVE AN AFFECT ON | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS | | | AND INSERT NEW SHEETS INTO COMPLETED | | | SETS FOR REVIEW AND STAMPING. | | | ONE COPY OF OLD SHEETS SHOULD BE SUBMITT | | | -ED FOR REFERENCE ONLY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-09-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-09-01 |
Time |
12:57 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-09-01 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2004-09-01 00:00:00 | ********* UNSAT ************* | | | | | | PLEASE SEE THE FOLLOWING FOR SOME NOTES | | | FROM FIRST REVIEW WERE NOT ADDRESSED. | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATEW/ PANEL SCHEDULE. | | | PLEASE SEE EM LTS/700.12E | | | | | | 2)NOTE: PLEASE SEE 210.63 AND VERIFY | | | GFI LOCATION FOR RTU. | | | | | | 3)NOTE: PLEASE SEE LOAD CALCS ARE NOW | | | SUBMITTED HOWEVER, ALL CONTINUOUS LOADS | | | ARE TO BE SHOWN AT 125%. | | | 215.3,230.42,ETC | | | | | | 4)NOTE: PLEASE SEE 250.50 FOR GROUNDING | | | ELECTRODE SYSTEM. | | | NOT SHOWN. | | | | | | 5)NOTE: PLEASE SEE FS 481.219 AND FAC | | | 61G1-16.004. | | | PLEASE INCLUDE ALL REQUIRED LICENSE | | | #'S ON TITLE BLOCKS. | | | THIS IS REQUIRED ON ALL SHEETS WHEATHER | | | OR NOT COMMENT IS MADE BY OTHER REVIEWER | | | 'S. | | | | | | 6)NOTE: PLEASE SEE ATTACHED COPY OF | | | FS553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONAL. | | | THIS IS ONLY A NOTICE AT THIS TIME. | | | | | | ***PLEASE REMOVE ALL OLD/VOIDED SHEETS | | | AND ONLY INSERT NEW SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | DO NOT ATTACH OLD SHEETS TO PLANS. | | | THESE MAY BE PLACE IN A SEPARATE ROLL | | | FOR REFERENCE ONLY. | | | | | | PLEASE SEE OTHER COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-06-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-25 |
Time |
16:02 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-06-25 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2004-06-25 00:00:00 | ************* UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE ELECTRICAL PLANS | | | APPEAR TO BE SHOWN ON A-SHEETS LABELED | | | AS REFLECTED CEILING PLANS?? | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW PER | | | 220.3,220.10,220.11,220.13 ETC. | | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | | AT 125% PER 215.3,230.42 | | | | | | 4)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE. 215.5 | | | PLEASE ALSO SEE 700.12E | | | | | | 5)NOTE: PLEASE SEE PLANS MUST CONTAIN | | | LEGAL SIGNATURE AS SHOWN ON SEAL. | | | PLANS APPEAR TO CONTAIN INITIALS. | | | IF THIS IS INDEED "LEGAL" SIGNATURE, | | | PLEASE PROVIDE A COMPLETED SIGNED, DATED | | | AND SEALED NOTORIZED LETTER. PLEASE BE | | | SURE NOTORY INCLUDES ALL INFORMATION AS | | | REQUIRED. | | | PLEASE SEE FS 481.221, WHICH REQUIRES | | | SIAGNTURE. | | | | | | 6)NOTE: PLEASE SEE FAC 61G1-16.004, | | | AND FS 481.219. | | | PLEASE INCLUDE ALL LICENSE #'S ON TITLE | | | BLOCK AS REQUIRED PER ABOVE. | | | | | | 7)NOTE: PLEASE INCLUDE GROUNDING ELEC- | | | -TRODE SYSTEM. 250.50. NO DETAIL GIVEN. | | | | | | 8)NOTE: PLEASE SHOW A/C EQUIPMENT ON | | | PLANS AND DISC'S PER 440.11 | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | AS THEY MAY AFFECT ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
N |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-09-01 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-09-01 |
Time |
14:12 |
Sent To |
P |
|
| Notes |
| 2005-09-01 00:00:00 | NO REVISIONS FOR FIRE OR LIFE SAFETY. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2005-05-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-19 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-05-02 |
Time |
16:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2005-03-23 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-03-23 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-03-23 |
Time |
14:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
N |
Date |
2004-12-23 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2004-12-23 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2004-12-23 00:00:00 | SEE NOTES FROM PREVIOUS REVIEWLM |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-11-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-11-05 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-11-05 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2004-11-05 00:00:00 | 1) SEPARATE PLANS AND PERMITS | | | FOR FIRE SPRINKLER REMODEL. | | | | | | 2) FIRE ALARM SYSTEM MUST BE UL | | | LISTED FOR CENTRAL STATION SERVICE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2004-09-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-09-15 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-09-15 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2004-09-15 00:00:00 | 1) DOOR # 31 IS NOT LABELED PER THE | | | DOOR SCHEDULE. THIS DOOR IS LOCATED | | | IN A RATED ENCLOSURE. PLEASE REVISE | | | DOOR SCHEDULE AS NECESSARY. | | | | | | 2) NEW FIRE ALARM SYSTEM SHALL BE | | | UL LISTED FOR "CENTRAL STATION | | | SERVICE" AND BE THIRD PARTY | | | CERTIFICATED. | | | | | | 3) DUCT SMOKE DETECTORS SHALL CAUSE | | | AN ALARM NOT A SUPERVISORY SIGNAL | | | AS NOTED IN 2 C) ON PAGE FA3-3. | | | SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE NEW FIRE ALARM SYSTEM. | | | | | | 4) SEPARATE PLANS AND PERMITS | | | REQUIRED FOR FIRE SPRINKLER REMODEL. | | | THE NEW FDC IS TO BE LOCATED WITHIN | | | 150 FEET OF A FIRE HYDRANT. | | | | | | 5) COULD NOT LOCATE ANY FIRE | | | EXTINGUISHER LOCATIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-07-22 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2004-07-22 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2004-07-22 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2004-07-22 00:00:00 | 1) ADDRESS NUMBER MUST BE AT LEAST 6" | | | IN HEIGHT AND CONTRAST WITH BACKGROUND. | | | 2) PLEASE SUBMIT SEPERATE SHOP DRAWINGS | | | FOR FIRE SPRINKLER AND ALARM SYSTEM. | | | 3) PLEASE SUBMIT DETAILS ON STAIRS. | | | 4) PLEASE SUBMIT INTERIOR FINISH | | | INFORMATION. | | | 5) PLEASE PROVIDE INFORMATION REGARDING | | | FIRE DEPARTMENT ACCESS AND HYDRANT | | | LOCATION. | | | | | | A/CAPT. MIKE WENNERGREN | | | WPBFR (561) 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2005-09-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-28 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-28 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2005-10-03 00:00:00 | TO "COMM" BD#21 | | 2005-09-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2005-08-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-22 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-22 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2005-08-22 00:00:00 | TO "COMM" BD#35 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2005-08-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-19 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-19 |
Time |
08:41 |
Sent To |
B |
|
| Notes |
| 2005-08-19 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2005-05-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-13 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-13 |
Time |
15:59 |
Sent To |
E |
|
| Notes |
| 2005-05-13 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2005-05-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-10 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-10 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2005-05-10 00:00:00 | IN INCOMING AWAITING SPACE ON "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2005-05-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-05 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-05 |
Time |
12:33 |
Sent To |
B |
|
| Notes |
| 2005-05-05 00:00:00 | TO "SHILL" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2005-04-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-22 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-22 |
Time |
10:46 |
Sent To |
B |
|
| Notes |
| 2005-04-22 00:00:00 | TO "SHILL" DESK/REVISION | | | TO "SHILL" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-04-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-21 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-21 |
Time |
14:13 |
Sent To |
B |
|
| Notes |
| 2005-04-21 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-04-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-05 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-05 |
Time |
10:12 |
Sent To |
B |
|
| Notes |
| 2005-04-05 00:00:00 | TO "LSMITH" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-03-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-31 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-31 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2005-03-31 00:00:00 | TO "COMM" BD#2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-02-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-28 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-28 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2005-02-28 00:00:00 | TO "COMM" BD#4 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-11-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-11-24 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-11-24 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2004-11-24 00:00:00 | SENT TO COMM BD#23 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-10-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-19 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-19 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2004-10-19 00:00:00 | TO COMM BD#35 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-08-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-23 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-23 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2004-08-23 00:00:00 | TO COMM BD#63 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-07-23 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2004-07-23 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2004-06-25 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2004-06-25 00:00:00 | TO COMM BD#18 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2005-11-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-11-15 |
Time |
08:29 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2005-11-15 |
Time |
08:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2005-05-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-05-04 |
Time |
14:25 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2005-05-04 |
Time |
14:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2005-03-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-03-16 |
Time |
07:24 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2005-03-16 |
Time |
06:43 |
Sent To |
|
|
| Notes |
| 2005-03-16 00:00:00 | DENIED: | | | 1. REVISION SHEET SUBMITTED INDICATES A | | | CHANGE IN ARCHITECT.PROVIDE A | | | CERTIFIED LETTER FROM THE FORMER | | | ARCHITECT OR OWNER STATING THE RELEASE | | | OF THE FORMER ARCHITECT AND THE | | | ASSIGNING OF THE NEW ARCHITECT.PLEASE | | | NOTE, MECHANICAL PLANS WERE PREVIOUSLY | | | DONE BY AN ENGINEER.WILL HE NO LONGER | | | BE RESPONSIBLE FOR THE PLANS? | | | | | | 2. PROVIDE A COMPLETE SET OF PLANS. | | | | | | 3. INDICATE CONDENSATE. NOTE ON PLAN | | | SHEET A3.3 THE CONDENSATE P-TRAP DETAIL | | | (A) SLOPE TO NEAREST STORM DRAIN. | | | PLEASE INDICATE CONDENSATE LINE SIZE, | | | MATERIAL AND LAYOUT ON THE PLAN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2004-12-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-12-06 |
Time |
07:36 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2004-12-06 |
Time |
07:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2004-11-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-11-16 |
Time |
10:17 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-11-16 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2004-11-16 00:00:00 | DENIED: | | | PROVISO ON REVIEW DATED 8-30-04 WAS NOT | | | ADDRESSED.PLEASE PROVIDE A DETAIL FOR | | | PENETRATIONS THROUGH THE FIRE RATED | | | ASSEMBLIES INDICATED ON PLAN SHEET | | | A4-01. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @ (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2004-09-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-08-30 |
Time |
10:39 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2004-08-30 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2004-08-30 00:00:00 | DENIED: | | | PLEASE NOTE, TITLE BLOCK INDICATES | | | "METRO DESIGN GROUP" WHICH REQUIRES A | | | CERTIFICATE OF AUTHORIZATION #.PLEASE | | | CORRECT TITLE BLOCK FOR COMPLIANCE WITH | | | 61G15-23.002 OF THE FAC. | | | | | | PROVISO: | | | PLEASE NOTE, PLANS SHEET M-1 & M-1.1 | | | INDICATE 8" EXHAUST FROM THE FIRST FLOOR | | | THROUGH THE ROOF. THE ARCHITECTURAL | | | PLANS DO NOT ADDRESS PENETRATIONS | | | THROUGH THE RATED FLOOR/CEILNG ASSEMBLY | | | INDICATED ON PLAN SHEET A4-01.PLEASE | | | PROVIDE A DETAIL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-07-15 |
Time |
08:25 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2004-07-15 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2004-07-15 00:00:00 | DENIED: | | | PROVIDE SIGNATURE NOT INITIALS ON PLANS | | | FOR COMPLIANCE WITH FS 471.025 & FAC | | | 61G15-23.002.PLAN ARE OTHERWISE CODE | | | COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
F |
Date |
2005-10-15 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-10-15 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-10-15 |
Time |
06:11 |
Sent To |
|
|
| Notes |
| 2005-10-15 00:00:00 | PAUL SCHMITZ | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY PLAN REVIEW | | | DENIED | | | 1)PREVIOUS NOTE: | | | SHT A0-00 DRINK FOUNTAIN NOTE. | | | | | | *****NEW COMMENT***** | | | SHT AO-00 INDICATES THAT A WATER COOLER | | | AND CUPS ARE PROVIDED IN THE LAUNDRY | | | ROOM. PLEASE SHOW LOCATION OF WATER | | | COOLER ON THE PLANS. SECTION 104.2.1 | | | A SINK IS NOT ACCEPTABLE EXCHANGE FOR A | | | DRINKING FOUNTAIN, OR WATER COOLER. | | | END OF COMMENTS, QUESTION 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2005-09-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-09-10 |
Time |
08:28 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-09-10 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2005-09-10 00:00:00 | REVISION OR - ADDED ONE LAV IN EACH | | | TOILET ROOM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2005-05-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-05-24 |
Time |
08:14 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-05-24 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2005-05-24 00:00:00 | PASSED/PROVISO | | | | | | | | | REV REQD FOR SUPPORTS FOR CONDENSATE ON | | | ROOF SHOWING 4' ON CENTER SUPPORTS. - | | | CONTRACTOR SAID HE WILL SUBMIT WHEN | | | ARCHITECT IN TOWN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2005-04-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-23 |
Time |
17:53 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-04-23 |
Time |
17:53 |
Sent To |
|
|
| Notes |
| 2005-04-23 00:00:00 | REVISION DENIED | | | | | | FROM PREVIOUS REVIEW: | | | 5) CONDENSATE PIPING SUPPORTS ON SHEET | | | A4.0 SHOWN AS EVERY 10 FEET. TABLE 408.5 | | | INDICATES THAT PVC WILL BE SUPPORTED | | | EVERY 4 FEET. - ALSO INDICATE THAT PVC | | | SHALL BE PROTECTED FROM U.V. RAYS PER | | | MANUF. INSTRUCTIONS. SECTION 104.2.1. | | | 6) LETTERS FROM ARCHITECT AND ENGINEER | | | SHALL BE SIGNED/SEALED/DATED/NOTOIZED | | | AND HAVE TITLE BLOCK INFORMATION | | | REQUIRED BY FLORIDA ADMINISTRATIVE CODE | | | AND FLORIDA STATUTES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2005-03-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-03-17 |
Time |
11:36 |
Rev Time |
3.25 |
| Received By |
kstevens |
Date |
2005-03-17 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2005-03-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | FBC-2001 BUILDING | | | | | | 1) SUBMIT A DETAIL FOR ACCESSIBLE BATH- | | | ROOMS PER SECTIONS 11-4.16, 11-4.19, 11- | | | 4.21, 11-4.22 AND ALL SUBSECTIONS. | | | 2) SHT A3.2 THE SANITARY RISER DIAGRAM | | | DOES NOTMEET CODE REQUIREMENTS. THE | | | SERVICE SINK SHALL DISCHARGE DOWNSTREAM | | | OF THE BATHROOM FIXTRUES. SECTION 909.1 | | | 3) AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE. SECTION 608.13.2. | | | 4) A DRINKING FOUNTAIN IS REQUIRED PER | | | TABLE 403.1. SUBMIT DETAIL SHOWING | | | COMPLIANCE WITH 11-4.15 AND ALL | | | SUBSECTIONS. | | | 5) SUBMIT DETAIL FOR CONDENSATE PIPING. | | | SHOW PIPE SIZE, MATERIAL, SUPPORT DETAIL | | | & TERMINATION POINT. SECTION 104.3.1.1. | | | 6) PLANS NOT HAVE A NEW ARCHITECT OF | | | RECORD, AND PLANS PREVIOUSLY SUBMITTED | | | FOR PLUMBING WERE SIGNED/SEALED/DATED BY | | | AN ENGINEER. PLEASE SUBMIT A | | | SIGNED/SEALED/DATED NOTORIZED LETTER FOR | | | CHANGING ARCHITECTS AND REMOVING THE | | | ENGINEER OF RECORD FROM THIS JOB. PLEASE | | | SUBMIT TWO COMPLETE SETS OF PLANS FOR | | | REVIEW AND FOR PUBLIC RECORD. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2004-12-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-12-13 |
Time |
18:55 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-12-13 |
Time |
18:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2004-11-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-08 |
Time |
10:42 |
Rev Time |
0.66 |
| Received By |
kstevens |
Date |
2004-11-08 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2004-11-08 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A) FROM PREVIOUS REVIEW: | | | 1) FAC 61G1-16.00E THE SIGNATURE AND | | | DATE ARE REQUIRED ON THE PERSONAL SEAL | | | OF THE ARCHITECT. - NO DATE SHOWN. FS | | | 481.2055 | | | 2) FAC 61G1-16.004(2) THE FIRM LICENSE | | | (CERTIFICATE OF AUTHORIZATION) NUMBER IS | | | REQUIRED IN THE TITLE BLOCK OF EACH | | | SHEET. FS 481.219 | | | *****NEW COMMENT***** | | | SHT AO-00 INDICATES THAT A WATER COOLER | | | AND CUPS ARE PROVIDED IN THE LAUNDRY | | | ROOM. PLEASE SHOW LOCATION OF WATER | | | COOLER ON THE PLANS. SECTION 104.2.1 | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-10-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-10-09 |
Time |
05:28 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2004-10-08 |
Time |
19:02 |
Sent To |
|
|
| Notes |
| 2004-10-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | FBC-2001 CHAPTER 1 | | | | | | 1) FAC 61G1-16.003 THE SIGNATURE AND | | | DATE ARE REQUIRED ON THE PERSONAL SEAL | | | OF THE ARCHITECT. - NO DATE SHOWN. FS | | | 481.2055 | | | 2) FAC 61G1-16.004(2) THE FIRM LICENSE | | | (CERTIFICATE OF AUTHORIZATION) NUMBER IS | | | REQUIRED IN THE TITLE BLOCK OF EACH | | | SHEET. FS 481.219 | | | 3) ARE BOTH FLOORS A SINGLE OCCUPANCY OF | | | ONE TENANT? IF NOT A DRINKING FOUNTAIN | | | OR BOTTLED WATER COOLER SHALL BE REQUIR- | | | ED IN EACH SPACE. TABLE 403.1 | | | 4) REMOVE ALL VOIDED SHEETS AND SUBMIT | | | TWO COMPLETE SETS OF PLANS FOR REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-07-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-07-14 |
Time |
10:46 |
Rev Time |
2.50 |
| Received By |
kstevens |
Date |
2004-07-10 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2004-07-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | FBC-2001 BUILDING | | | | | | 1) SUBMIT CALCULATIONS FOR MINIMUM FAC- | | | ILITIES FOR FIXTURES PER TABLES 1103.1 | | | (BLDG.) AND 403.1 (PLUMB.) SHOW SQUARE | | | FOOTAGE FOR EACH OCCUPANCY, BUSINESS, | | | INDUSTRIAL, & STORAGE. | | | 2) INDICATE TYPE AND AMOUNT OF MATERIALS | | | TO BE STORED. RESPONSE MAY CREATE NEW | | | COMMENTS. SECTION 104.2.1 | | | 3) WHAT TYPE OF BUSINESS/WORK WILL BE | | | DONE IN THIS SPACE? | | | 4) PRIVATE BATHROOM SHALL BE ADAPTABLE. | | | SUBMIT A DETAIL SHOWING BACKING FOR W/C | | | GRAB BARS, SIZE OF OPENING FOR W/C, THE | | | BACKING FOR GRAB BARS FOR THE SHOWER, | | | CONTROL AREA FOR SHOWER, HEIGHT OF SEAT | | | AND BACKING FOR SEAT, & CURB HEIGHT. | | | SECTION 11-4.1.3(11).- ALSO INDICATE | | | TURNING AREA IN ADAPTABLE BATHROOM. | | | 5) SUBMIT A DETAIL FOR ACCESSIBLE BATH- | | | ROOMS PER SECTIONS 11-4.16, 11-4.19, 11- | | | 4.21 AND ALL SUBSECTIONS. | | | 6) DOORS REQUIRED TO BE ACCESSIBLE SHALL | | | COMPLY WITH THE REQUIREMENTS OF 11-4.13. | | | AND 11-4.13.5. THE CLEAR WIDTH OF 32" | | | CAN NOT BE ACHIEVED WITH A 2'8" DOOR. | | | 7) LUNCH ROOM SINK SHALL BE ACCESSIBLE | | | PER SECTION 11-4.24. SUBMIT A DETAIL | | | SHOWING COMPLIANCE WITH THIS SECTION AND | | | ALL SUBSECTIONS. | | | 8) SHT PO-01 WATER RISER DIAGRAM & NOTES | | | AIR CHAMBERS ARE NOT APPROVED. DELETE | | | FROM RISER AND NOTES. WATER HAMMER ARR- | | | ESTORS REQUIRED BY SECTION 604.9, (AT | | | ICE MAKERS, WASH MACHINES, & DISHWASHERS | | | SHALL BE LOCATED NEAR THE FIXTURES IN AN | | | "EFFECTIVE RANGE PER PDI-WH 201 AND | | | MANUF. - RISER DIAGRAM DOES NOT REFLECT | | | THE FLOOR PLAN. THERE ARE FIXTURES NOT | | | SHOWN ON FLOOR PLAN, (TUB & LAV). | | | 9) SHT P0-01 THE SANITARY RISER DIAGRAM | | | DOES NOT REFLECT THE FLOOR PLAN, NOT | | | DOES IT MEET CODE REQUIREMENTS. W/C'S | | | (A) W/C'S SHALL NOT BE DOUBLE TRAPPED. | | | SECTION 1002.1. W/C'S HAVE AN INTEGRAL | | | TRAP. SEE EXCEPTION (1). | | | (B) SANITARY CROSS FITTINGS ARE NOT | | | APPROVED FOR UNDERGROUND USE. SECTION | | | 706.3. | | | (C) HORIZONTAL DRY VENTS ARE NOT APPRO- | | | VED PER SECTION 905.3 | | | (D) TEE FITTINGS ARE NOT APPROVED FOR | | | USE AS SHOWN AT THE TOP OF RISER WITH | | | DRAINAGE FROM BOTH DIRECTIONS. TABLE | | | 706.3. | | | (E) NO BATH TUB IN ROOM 206 SHOWN ON | | | THE FLOOR PLAN. SECTION 104.2.1 | | | (F) 2 LAVS SHOWN ON RISER, BUT ONLY ONE | | | SHOWN ON FLOOR PLAN. SECTION 104.2.1. | | | (G) WASH MACHINE REQUIRES A TRAP AND A | | | STANDPIPE. SECTIONS 1002.1, & 802.4. | | | (H) DISHWASHERS REQUIRE AN AIR GAP FIT- | | | TING ABOVE THE FLOOR RIM LEVEL OF THE | | | SINK. | | | (I) WHAT IS THE FIXTURE BETWEEN THE | | | DISHWASHER AND THE SINK IN THE LUNCHROOM | | | WHAT IS THE USAGE OF THIS FIXTURE. SECT- | | | ION 104.2.1. | | | (J) THE RISER DIAGRAM SHALL REFLECT THE | | | LAYOUT OF THE FIXTURES ON THE FLOOR PLAN | | | AND THE ACTUAL INSTALLATION OF THE PIP- | | | ING. SEE RED LINE CORRECTIONS AND EXAMP- | | | LE. | | | 10) AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE. SECTION 608.13.2 | | | 11) THERMAL EXPANSION CONTROL IS REQUIR- | | | ED PER SECTION 607.3.2 | | | 12) A PROFESSIONAL ENGINEER SHALL SIGN | | | HIS NAME AND AFFIX HIS SEAL TO ALL PLANS | | | SPECIFICATIONS, REPORTS AND FINAL BID | | | DOCUMENTS PROVIDED TO THE OWNER OR THE | | | OWNER'S REPRESENTATIVE, OR OTHER DOCU- | | | MENTS PREPARED OR ISSUED BY SAID REGIS- | | | TRANT AND BEING FILED FOR PUBLIC RECORD. | | | THE DATE THAT THE SIGNATURE AND SEAL IS | | | AFFIXED AS PROVIDED HEREIN SHALL BE EN- | | | TERED ON SAID PLANS, SPECIFICATIONS, RE- | | | PORTS, OR OTHER DOCUMENTS IMMEDIATELY | | | UNDER THE SIGNATURE OF THE PROFESSIONAL | | | ENGINEER, FAC 61G15-23.002(1) | | | FS 471.025 | | | EACH SHEET OF PLANS AND PRINTS WHICH | | | MUST BE SEALED UNDER THE PROVISIONS OF | | | CHAPTER 471 SHALL BE SEALED, SIGNED AND | | | DATED BY THE PROFESSIONAL ENGINEER IN | | | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) | | | FS 471.025 | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. IF PRACTICING THROUGH A DULY | | | AUTHORIZED ENGINEERING BUSINESS, ENGIN- | | | EERS, ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME AND LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. A TITLE BLOCK | | | WILL SATISFY THIS REQUIREMENT. FAC | | | 61G15-23.002(2) - FS 471.025 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-05-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-05 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-05-05 |
Time |
09:58 |
Sent To |
PC |
|
| Notes |
| 2005-05-05 00:00:00 | OK PER AA (RE: DMP REVIEW) |
|
|