Plan Review Details - Permit 04061202
Plan Review Stops For Permit 04061202
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-01-26 Cont ID  
Sent By alange Date 2006-01-26 Time 09:32 Rev Time 0.50
Received By alange Date 2006-01-26 Time 09:26 Sent To  
Notes
2006-01-26 00:00:00REVISED PAGE 2 OK FOR KITCHEN

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-08-30 Cont ID  
Sent By alange Date 2004-08-30 Time 09:58 Rev Time 1.00
Received By alange Date 2004-08-30 Time 09:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-08-26 Cont ID  
Sent By rbrown Date 2004-08-26 Time 17:30 Rev Time 0.00
Received By rbrown Date 2004-08-26 Time 11:18 Sent To  
Notes
2004-08-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 1606.1.4THE SUBMITTED WINDOW
 AND FRENCH DOOR PRODUCT APPROVALS ARE
 FOR PRODUCTS WITH NO IMPACT RATING.
 SUBMIT PRODUCT APPROVAL FOR HURRICANE
 MISSILE IMPACT PROTECTION SHUTTERS OR
 FOR IMPACT RATED DOORS AND WINDOWS.
  
 2) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS.TWO
 BLANK COPIES OF FORM 600C HAVE BEEN
 SUPPLIED FOR COMPLETION AND SUBMITTAL.
  
 3) FBC 1403.2.2.1CROSS-SECTION A-A
 DOES NOT SHOW ANY SUPPORT FOR THE
 MASONRY VENEER.ANCHORED MASONRY VENEER
 SHALL BE VERTICALLY SUPPORTED ON
 FOOTINGS, FOUNDATION WALLS OR OTHER
 APPROVED NON-COMBUSTIBLE STRUCTURAL
 ELEMENTS.AMEND/ANNOTATE THE PLANS.
  
 4) FBC 1403.2.4THE NOTE, ON CROSS-
 SECTION A-A, ABOUT MASONRY VENEER TIES
 SHALL BE AMENDED TO STATE THE TYPE AND
 SPACING OF THE TIES.MASONRY VENEER
 ANCHORED TO WOOD FRAMING SHALL BE
 ATTACHED WITH METAL TIES EMBEDDED IN THE
 MORTAR JOINT A MINIMUM OF ONE-HALF OF
 THE VENEER THICKNESS.EACH METAL TIE
 SHALL SUPPORT NOT MORE THAN 3 SQFT OF
 WALL AREA WITH A MAXIMUM SPACING OF 18"
 VERTICALLY AND 32" HORIZONTALLY.ALSO,
 A MINIMUM OF 1" AIR SPACE SHALL BE
 MAINTAINED BETWEEN THE ANCHORED VENEER
 AND THE EXTERIOR FACE OF THE SHEATHING.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-08-11 Cont ID  
Sent By dpalmer Date 2004-08-24 Time 11:19 Rev Time 0.75
Received By alange Date 2004-08-11 Time 15:37 Sent To  
Notes
2004-08-11 00:00:00DENIED
 SUBMIT 2 COPIES OF ALL PRODUCT
 APPROVALSDEPARTMENT OF COMMUNITY
 AFFAIRSAPPROVAL SHEETS ARE EITHER WRONG
 OR
 INCOMPLETE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 IF YOU HAVE QUETIONS OR WOULD LIKE TO
 MEET WITH ME GIVE ME A CALL.
  
 ART LANGE
 BUILDING PLAN REVIEW
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-21 Cont ID  
Sent By dpalmer Date 2004-08-10 Time 14:38 Rev Time 0.50
Received By alange Date 2004-07-21 Time 10:26 Sent To  
Notes
2004-07-21 00:00:00DENIED
 SAME NOTES AS LAST REVIEW:
  
 SUBMMIT 2 COPIES OF PRODUCT APPROVALS
 FOR EXTERIOR DOORS AND WINDOWS. IMPACT
 PROTECTION AND ROOFING.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-12 Cont ID  
Sent By dpalmer Date 2004-07-19 Time 17:58 Rev Time 1.25
Received By alange Date 2004-07-12 Time 14:17 Sent To  
Notes
2004-07-12 00:00:00DENIED
 1.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR EXTERIOR DOORS AND WINDOWS.
 IMPACT PROTECTION AND ROOFING.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-05-02 Cont ID  
Sent By dpalmer Date 2006-05-02 Time 12:39 Rev Time 0.00
Received By dpalmer Date 2006-05-02 Time 12:31 Sent To PC
Notes
2006-05-02 00:00:00********* UNSAT ***********
  
 1) NOTE: PLEASE SEE TWO SEPARATE
 ELECTRICAL RISERS ARE NOW BEING
 SUBMITTED.
 ONE INDICATES BEING FOR 626 FRANKLIN AND
 THE OTHER FOR 826 FRANKLIN.
 PLEASE ONLY SUBMIT ONE FOR REVIEW.
 PLEASE SEE ONE RISER SHOWS #6 FOR GEC
 AND #4, PLEASE SEE 250.66, AS THE #4 IS
 REQUIRED AT A MIN.
  
 2) NOTE: PLEASE ALSO EACH RISER CONTAINS
 DIFFERENT PERSONS RESPONSIBLE FOR DESIGN
 PLEASE SEE THE ORIGINAL PERSON
 RESPONSIBLE FOR DESIGN SHOULD BE THE
 PERSON OF RECORD , UNLESS ALL PLANS ARE
 BEING CHANGED TO THE NEW DESIGN
 PROFESSIONAL OF RECORD.
 FBC104.2.1
 PLEASE SEE IN ANY CASE ALL PLANS, WHEN
 NOT ORIGINALLY DONE BY AN ARCHITECT OR
 ENGINEER, SHALL CONTAIN THE PRINTED NAME
 AND SIGNATURE.
  
 3) NOTE: PELASE SEE PREVIOUS NOTE
 MENTIONED THE DEDICATE BATH CIRCUIT
 SHALL BE 20A AND #12, THIS WAS CORRECTED
 TO #12, HOWEVER IS NOW ALSO PENCILED AS
 #14?
 PLEASE KNOW, ONLY 20A AND #12 IS
 PERMITTED.
  
 4) NOTE: PLEASE SEE ONE PLANS INDICATES
 ELECTRICAL FOR ALL APPLIANCES, WHERE THE
 OTHER SHOWS GAS FOR SOME.
 PLEASE CORRELATE AND SUBMIT ONLY ONE.
 215.5
  
 5) NOTE; PLEASE SEE THE PLANS CAME IN AS
 A SUBMITTIAL WHEN INDEED IT WAS A
 REVISION. PLEASE SEE A FEE IS OWED FOR
 THIS REVIEW AND ALSO FOR REVISION WHEN
 PLANS ARE BROUGHT BACK.
 PLEASE BE SURE TO ADDRESS ALL COMMENTS
 AND IF THERE ARE ANY QUESTIONS, PLEASE
 DO NOT HESITATE IN CONTACTING THIS
 OFFICE TO HELP ALLEAVIATE ANY FURTHER
 DELAYS/REVIEWSOR FEES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-01-17 Cont ID  
Sent By dpalmer Date 2006-01-17 Time 10:05 Rev Time 0.00
Received By dpalmer Date 2006-01-17 Time 08:17 Sent To P
Notes
2006-01-17 00:00:00*********UNSAT **********
  
  
 1)NOTE: PLEASE SEE PLANS HAVE HAD ALL
 REQUIRED SMOKE DETECTORS AND GFI'S FOR
 EXISTING DWELLING REMOVED.????
 PLEASE SEE ORIGINAL PLANS WHICH
 INDICATED THIS.
 FBC CHAPTER 34 FOR ADDTIONS TO EXISTING
 DWELLINGS.
 PLEASE CORRECT PLANS.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 ALONG WITH LOAD CALCUALTIONS SUBMITTED.
 PLEASE SEE DRYER SHOWN AS 5KW ON A
 1-POLE 20 ETC.
 PLEASE SEE AHU #2 AS 30A OCP #10 AWG
 WITH 10 KW RATING ON CALCS.(424.3).
 PLEASE SEE MISSING MICROWAVE.
 ETC.
 215.5
  
 3)NOTE: PLEASE SEE MIN OCP FOR DOUBLE
 OVEN AND COOKTOP SHALL BE BASED ON MIN
 OCP FOR KW RATINGS. PLEASE SEE A 10KW
 LOAD IS BEING SHOWN ON 40A OCP WHICH
 EXCEEDS MIN RATINGS OF DEVICE AND BRKR.
 240.4, 215.5
  
 4)NOTE: PLEASE SEE 210.52D,210.11C3
 WHICH REQUIRES BATH RECEPT(S) TO BE ON A
 MIN 20A, #12 AWG CIRCUIT.
  
 5)NOTE: PLEASE INDICATE THE REQUIRED GFI
 PROTECTION FOR THE JACUZZI TUB,680.71
  
 6)NOTE: PLEASE SEE 210.52C1 FOR WHAT
 APPEARS TO BE A MISSING KITCHEN
 COUNTERSPACE RECEPT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-08-24 Cont ID  
Sent By dpalmer Date 2004-08-24 Time 11:19 Rev Time 0.33
Received By dpalmer Date 2004-08-24 Time 11:18 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-08-10 Cont ID  
Sent By csiegber Date 2004-08-19 Time 10:43 Rev Time 0.33
Received By dpalmer Date 2004-08-10 Time 14:37 Sent To B
Notes
2004-08-10 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE PLANS ARE NOW BEING
 SUBMITTED WITH REFERENCE TO SERVICE AS
 BEING A NEW 200A SERVICE. PLEASE SEE
 NOTE #4 FROM PREVIOUS REVIEW WHICH
 REQUESTED AIC RATING FOR NEW SERVICE
 MAIN/EQIPMENT. PER 110.9/215.5
 PLEASE SHOW LOCATION OF NEW PANEL.
  
 2)NOTE: PLEASE SEE PLANS ARE ALSO NOW
 BEING SUBMITTED SHOWING ALL NEW ELECTR-
 -ICAL IN REMAINDER OF HOUSE?
 IF ELECTRICAL NOW SHOWN FOR EXISTING
 DWELLINGIS EXISTING, PLEASE LABEL W/
 AN "E" OR NOTE. AS SHOWN, EXISTING
 DWELLING IS BEING REWIRED?
  
 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 4)NOTE: PLEASE SEE PANEL/LOAD CALCS
 INDICATE TWO A/C SYSTEMS YET PLANS ONLY
 SHOW ONE COND UNIT AND AHU?
  
 PLEASE SEE SOME NOTES ARE NEW DUE TO
 PLANS BEING CHANGED TO SHOW NEW ITEMS.
 AIC RATING WAS REQUESTED ON PREVIOUS
 REVIEW FOR SERVICE (IF NEW).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-08-03 Time 13:43 Rev Time 0.50
Received By dpalmer Date 2004-07-19 Time 17:57 Sent To B
Notes
2004-07-19 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 AND LOAD CALCULATIONS. THERE ARE MANY
 ITEMS THAT DO NOT MATCH.
 PLEASE SEE AHU KW RATING SHOWN AS 10KW
 W/60OCP AND 30A OCP? 424.3B
 PLEASE SEE WATER HEATER, DISP,DISHW ETC.
  
 2)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 MUST BE 20A #12.
  
 NOTE: OK
  
  
  
 4)NOTE: PLEASE CLARIFY IF SERVICE IS
 NEW OR EXSITING? METER IS SHOWN AS EXIST
 -ING BUT PANEL DO NOT INDICATE. IF NEW
 SUBMIT AIC RATING FOR EQUIPMENT PER
 110.9.
 PLEASE ALSO SEE MISSING EQUIPMENT GROUND
 -ING CONDUCTOR PER 250.110,250.24,
 250.122
  
 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS TO EXISTING DWELLINGS.
 PLEASE PROVIDE LAYOUT FOR NEW OR EXIST-
 -ING SD'S , GFI'S ETC.
 3401.7.1.2.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-07-15 Time 16:02 Rev Time 0.45
Received By jleahy Date 2004-06-30 Time 10:37 Sent To M
Notes
2004-06-30 00:00:001)NEED LOAD CALCULATION
  
 2)ALL OUTLETS IN THE BEDROOMS TO ARC
 FAULT PROTECTED
  
 3)NEED A PANEL SCHEDULE
  
 4)SMOKE DETECTORS ARE TO BE ALEAST 3'
 FROM BATH ROOM AND AC VENTS
  
 ANY QUESTIONS CALL JAKE805-6740

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-26 Cont ID  
Sent By adarroug Date 2006-04-26 Time 12:18 Rev Time 0.00
Received By adarroug Date 2006-04-26 Time 12:18 Sent To E
Notes
2006-04-26 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-06 Cont ID  
Sent By adarroug Date 2006-01-06 Time 17:12 Rev Time 0.00
Received By adarroug Date 2006-01-06 Time 17:12 Sent To E
Notes
2006-01-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-19 Cont ID  
Sent By csiegber Date 2004-08-19 Time 10:43 Rev Time 0.00
Received By csiegber Date 2004-08-19 Time 10:43 Sent To E
Notes
2004-08-19 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 13:43 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 13:43 Sent To E
Notes
2004-08-03 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-15 Cont ID  
Sent By csiegber Date 2004-07-15 Time 16:02 Rev Time 0.00
Received By csiegber Date 2004-07-15 Time 16:02 Sent To E
Notes
2004-07-15 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-29 Cont ID  
Sent By csiegber Date 2004-06-29 Time 15:07 Rev Time 0.00
Received By csiegber Date 2004-06-29 Time 15:07 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-25 Cont ID  
Sent By mmclean Date 2004-06-29 Time 12:13 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 09:27 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-07-08 Cont ID  
Sent By jleahy Date 2004-06-30 Time 10:40 Rev Time 0.25
Received By pkrauss Date 2004-07-08 Time 07:27 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-01-24 Cont ID  
Sent By jleech Date 2006-01-24 Time 15:21 Rev Time 0.33
Received By jleech Date 2006-01-24 Time 15:21 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-07-10 Cont ID  
Sent By pkrauss Date 2004-07-08 Time 07:34 Rev Time 0.25
Received By jleech Date 2004-07-10 Time 12:52 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-29 Cont ID  
Sent By csiegber Date 2004-06-25 Time 09:27 Rev Time 0.00
Received By mmclean Date 2004-06-29 Time 12:13 Sent To I
Notes
***NONE***