Plan Review Details - Permit 04061180
Plan Review Stops For Permit 04061180
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-03-21 Cont ID  
Sent By alange Date 2005-03-21 Time 12:26 Rev Time 0.00
Received By alange Date 2005-03-21 Time 12:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-03-18 Cont ID  
Sent By alange Date 2005-03-18 Time 07:55 Rev Time 0.25
Received By alange Date 2005-03-18 Time 07:51 Sent To  
Notes
2005-03-18 00:00:00DENIED
  
  
 PLANS SUBMITTED FOR REVISION NOT SIGNED
 AND SEALED.TWO COPIES REQUIRED.
  
 ART LANGE
 BUILDING PLAN EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-11-30 Cont ID  
Sent By alange Date 2004-11-30 Time 11:06 Rev Time 0.75
Received By alange Date 2004-11-30 Time 11:06 Sent To  
Notes
2004-11-30 00:00:00STRUCTURAL REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-08-31 Cont ID  
Sent By alange Date 2004-08-31 Time 16:31 Rev Time 1.00
Received By alange Date 2004-08-31 Time 16:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-02 Cont ID  
Sent By pkrauss Date 2004-08-31 Time 15:26 Rev Time 0.75
Received By alange Date 2004-08-02 Time 13:39 Sent To  
Notes
2004-08-02 00:00:00DENIED
 SAME COMMENTS FROM PREVIOUS REVIEW.
  
 2.PLEASE SIGN OWNER/AGENT ON BOTH
 COPIES OF ENERGY CALCS.
  
 5.FBC1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 FBC 1015.3 OPENINGS.OPEN
 GUARDRAILS SHALL HAVE INTERMEDIATE
 RAILS OR ORNIMENTAL PATTERNS SUCH AS A
 4" DIAMETER SPHERE CAN NOT PASS THROUGH.
 A BOTTOM RAIL OR CURB SHALL BE PROVIDED
 THAT WILL REJECT THE PASSAGE OF A 2"
 DIAMETER SPHERE.SHOW DETAIL ON PLANS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-13 Cont ID  
Sent By dpalmer Date 2004-07-28 Time 19:25 Rev Time 1.75
Received By alange Date 2004-07-13 Time 13:09 Sent To  
Notes
2004-07-13 00:00:00DENIED
 1. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.PLEASE SIGN OWNER/AGEN ON ENERGY
 CALCS.
  
 3. ALL PLANS ARE TO BE SIGNED AND SEALED
  
 4.SHOW SIZE OF ATTIC ACCESS ON PLAN
 FBC. 2309.6
  
 5.1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-08-17 Cont ID  
Sent By dpalmer Date 2004-08-17 Time 09:12 Rev Time 0.33
Received By dpalmer Date 2004-08-17 Time 09:11 Sent To M
Notes
2004-08-17 00:00:00REDLINED 410.8

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-08-09 Time 15:31 Rev Time 0.33
Received By dpalmer Date 2004-07-28 Time 19:25 Sent To B
Notes
2004-07-28 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE FS 481.221, PLANS
 HAVE A "STAMP" FOR SIGNATURE WHICH IS
 REQUIRED TO BE AN ORIGINAL SIGNATURE.
 FAC 61G1-16.004
  
 2)NOTE: PLEASE CORRELATE PANELS AND
 RISER DIAGRAM. PANEL "B" IS SHOWN AS
 NEW AND YET RISER IS SHOWN AS EXSITING??
  
 3 )NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER PER 220.31B FOR AN EXISTING DWELLING
  
 4) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 6)NOTE: PLEASE SEE 410.8 FOR CLOSET LTS
 AND MIN CLEARENCE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-07-28 Time 11:45 Rev Time 1.00
Received By jleahy Date 2004-06-30 Time 10:15 Sent To P
Notes
2004-06-30 00:00:001)ONLY ONE SET SEALED
  
 2)ARC FASULTS TO BE NOTED ON DRAWINGS
  
 QUESTIONS CALL JAKE805-6740

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-04-07 Cont ID  
Sent By adarroug Date 2005-04-07 Time 13:36 Rev Time 0.00
Received By adarroug Date 2005-04-07 Time 13:36 Sent To M
Notes
2005-04-07 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-15 Cont ID  
Sent By adarroug Date 2005-03-15 Time 11:28 Rev Time 0.00
Received By adarroug Date 2005-03-15 Time 11:28 Sent To B
Notes
2005-03-15 00:00:00TO "AL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-11-15 Cont ID  
Sent By csiegber Date 2004-11-15 Time 08:42 Rev Time 0.00
Received By csiegber Date 2004-11-15 Time 08:42 Sent To B
Notes
2004-11-15 00:00:00TO AL DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-09 Cont ID  
Sent By csiegber Date 2004-08-09 Time 15:31 Rev Time 0.00
Received By csiegber Date 2004-08-09 Time 15:31 Sent To E
Notes
2004-08-09 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-07-28 Time 11:45 Rev Time 0.00
Received By csiegber Date 2004-07-28 Time 11:45 Sent To E
Notes
2004-07-28 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-28 Cont ID  
Sent By csiegber Date 2004-06-28 Time 08:54 Rev Time 0.00
Received By csiegber Date 2004-06-28 Time 08:54 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-24 Cont ID  
Sent By mmclean Date 2004-06-25 Time 13:05 Rev Time 0.00
Received By csiegber Date 2004-06-24 Time 14:56 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-04-12 Cont ID  
Sent By prafter Date 2005-04-12 Time 10:58 Rev Time 0.50
Received By prafter Date 2005-04-12 Time 10:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-08-31 Cont ID  
Sent By pkrauss Date 2004-08-31 Time 14:51 Rev Time 0.20
Received By pkrauss Date 2004-08-31 Time 14:51 Sent To B
Notes
2004-08-31 00:00:00PROVISO:
 PER CONVERSATION WITH ROBERT FROM VAN'S
 COMFORT TEMP, A REVISE SET OF MANUAL J
 CALCULATIONS TO BE PROVIDED PRIOR TO
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-08-25 Cont ID  
Sent By pkrauss Date 2004-08-25 Time 14:22 Rev Time 0.25
Received By pkrauss Date 2004-08-25 Time 14:18 Sent To B
Notes
2004-08-25 00:00:00DENIED:
 ENERGY CALCULATIONS INDICATE A MINIMUM
 OF 12 SEER.MANUAL J CALCULATIONS AND
 PROPOSAL BY VAN'S COMFORTEMP INDICATE
 A 10 SEER.MANUAL J & PLANS SHALL
 BE NO LESS THAN THAT INDICATED ON THE
 ENERGY CALCULATIONS.
  
 RETURN AIR REQUIRED FROM BEDROOM 3 AND
 4.SHOW COMPLIANCE WITH THE REVISED
 2001 FBC(M) 601.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-07-13 Cont ID  
Sent By dpalmer Date 2004-08-17 Time 09:12 Rev Time 0.35
Received By pkrauss Date 2004-07-13 Time 08:01 Sent To B
Notes
2004-07-13 00:00:00NO MECHANICAL PLANS SUBMITTED OR
 MECHANICAL CONTRACTOR INDICATED ON
 PERMIT APPLICATION.PLEASE PROVIDE THE
 FOLLOWING WITH MECHANICAL PERMIT
 APPLICATION:
 1.INDICATE DUCT AND GRILLE SIZE,
 MATERIAL AND LAYOUT.
  
 2.PLAN SHEET A5 INDICATES AHU IN THE
 ATTIC.PROVIDE DETAIL AS TO HOW THE
 AHU IS MOUNTED.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 4.PROVIDE LINE SET SIZES AS WELL AS
 THE CONDENSATE.
  
 PLEASE NOTE ENERGY CALCS SUBMITTED WITH
 BUILDING PERMIT.PLEASE PROVIDE MANUAL
 J CALCULATIONS IN ACCORDANCE WITH 2001
 FBC CHAPTER 13 SUB-CHAPTER 6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-07-10 Cont ID  
Sent By jleahy Date 2004-06-30 Time 10:15 Rev Time 0.33
Received By jleech Date 2004-07-10 Time 12:17 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-24 Time 14:56 Rev Time 0.00
Received By mmclean Date 2004-06-25 Time 13:05 Sent To I
Notes
***NONE***