| Plan Review Stops For Permit 04061070 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-08-02 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-08-02 |
Time |
10:33 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
2004-08-02 |
Time |
10:33 |
Sent To |
E |
|
| Notes |
| 2004-08-02 00:00:00 | BUIDING PLAN REVIEW: PROVISO | | | | | | 1. SUBMIT THE FLORIDA PRODUCT APPROVAL | | | FOR THE EXTERIOR DOOR #10 SHOWN ON | | | PLANS BEFORE INSTALLATION. | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANSEXAMINER | | | 805-6713 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-07-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-08-02 |
Time |
09:27 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
2004-07-19 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2004-07-19 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | | | | | | | | | SEE NOTES FROM FIRST REVIEW NOT ANSWERED | | | NEED FLORIDA PRODUCT APPROVALS FOR STORE | | | FRONT SYSTEM. | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-08 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-07-08 |
Time |
08:39 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
2004-07-08 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2004-07-08 00:00:00 | 1.PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATIONPLEASE SEE THE STATE WEBSITE | | | AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 2. NEED SEPARATE PERMIT FOR MOVING | | | RETURN AIR HANDLER. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-08-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-02 |
Time |
16:35 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-08-02 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2004-08-02 00:00:00 | **** NOTES REDLINED ** | | | | | | MISSING EQUIPMENT GRNDS. 250.122,250.110 | | | | | | CORRELATE PANELS NEW AND EXSITING, | | | | | | REDLINE ABOVE, DOES NOT NEED TO REVISE | | | PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-07-15 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-08-02 |
Time |
10:38 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2004-07-15 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2004-07-15 00:00:00 | ************** UNSAT ************** | | | | | | PLEASE SEE SOME NOTES FROM FIRST REVIEW | | | HAVE NOT YET BEEN ADDRESSED. | | | | | | 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE WITH THE SUBMITTED PANEL | | | SCHEDULE. | | | | | | 2)NOTE: PLEASE LIST/SHOW/INDICATE SIGN | | | CIRCUIT AS REQUIRED PER 600.5 | | | | | | 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW PER | | | 220.3,220.10,220.11,220.13 ETC. | | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | | AT 125% PER 215.3,230.42 | | | PLEASE SUBMIT LOAD CALCS FOR EXISTING | | | SERVICE. PLEASE SEE WHAT WAS SUBMITTED | | | FOR REFERENCE TO PREVIOUS PERMITS DOES | | | NOT INDICATE LOAD CALCS. | | | | | | 4)NOTE; PLEASE SEE RISER, STILL DOES NOT | | | INDICATE ANY CONDUIT TO NEW SUB-PANELS, | | | FEEDERS, EQUIPMENT GRNDS ETC. | | | 215.5,310.16,250.24,250.110,250.122 ETC | | | | | | 5)NOTE: PLEASE SEE LETTER FROM FPL FOR | | | AVAILABLE FAULT CURRENT IS NOW ATTACHED | | | BUT THERE IS NO INDICATION FOR RATING | | | OF MAINS. 110.9 | | | | | | 6)NOTE: PLEASE SEE SUB PANELS ARE NOTED | | | ON PLANS AS BEING 125A AND 150A? | | | PLEASE VERIFY AND CORRELATE. | | | | | | 7)NOTE: PLEASE SEE TITLE BLOCK IS REQ'D | | | TO HAVE THE PRINTED LICENSE # OF | | | ENGINEER. FAC 61G15-23.002. FS 471.025 | | | | | | PLEASE SEE ATTACHED COPY OF FS 553.80(2) | | | (B) WITH RESPECT TO DESIGN PROFESSIONAL, | | | THIS IS GIVEN AS A NOTICE FOR PLANS | | | FAILED FOR THE SECOND REVIEW WHICH HAVE | | | ONE OR MORE OF THE SAME CODE COMMETS. | | | THIS IS A NOTICE ONLY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-06-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-22 |
Time |
17:42 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-06-22 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2004-06-22 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE SHOW ALL MIN CIRCUITING | | | ON PLANS AND CORRELATE W/ PANEL SCHEDULE | | | -S TO BE SUBMITTED. | | | PLEASE ALSO SEE 700.12E FOR EM/EXT LTS. | | | PLEASE PROVIDE ALL CIRCUITING TO | | | SEPARATE TENANT SPACES. | | | | | | 2)NOTE: PLEASE SEE PLANS AND PERMIT | | | APPLICATION INDICATE TWO NEW SUB PANELS | | | BEING INSTALLED , YET NO INFORMATION IS | | | PROVIDED ON A RISER DIAGRAM ETC? | | | ADDTIONAL SERVICES ARE NOT PERMITTED, | | | MUST COME FROM EXSITING SERVICE. | | | MAY HAVE ADDTIONAL METERS. | | | | | | 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW PER | | | 220.3,220.10,220.11,220.13 ETC. | | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | | AT 125% PER 215.3,230.42 | | | PLEASE PROVIDE LOAD CALCS FOR EXSITING | | | SERVICE. | | | | | | 4)NOTE: PLEASE INDICATE REQUIRED CIRCUIT | | | PER 600.5 | | | | | | 5)NOTE: PLEASE PROVIDE USEAGE AND OR | | | NEW/ EXSITING SHOW WINDOW RECEPTS REQ'D | | | PER 210.62. | | | | | | 6)NOTE: PLEASE VERIFY A/C SYSTEMS AND | | | WHICH SYSTEM IS FEEDING WHICH AREA. | | | PLANS ONLY SHOW ONE AHU? | | | PLEASE SHOW ALL, AND DISC'S PER 440.11 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-07-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-07-14 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-07-14 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-06-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-06-24 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-06-24 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2004-06-24 00:00:00 | 1) PLANS DISPLAY A PROPOSED STORAGE | | | AREA UNDERNEATH EXIT STAIRS WITH NO | | | FIRE RATING. PLEASE REVIEW NFPA 101, | | | THE LIFE SAFETY CODE, SECTION 7.2.2.5.3, | | | 2000 EDITION. | | | | | | 2) NO EMERGENCY LIGHTING SHOWN IN | | | ONE OF THE SECOND FLOOR TENANT | | | SPACES. | | | | | | 3) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENT FOR NEW ALUMINUM RAILING. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-08-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-08-02 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2004-08-02 |
Time |
09:13 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-07-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-12 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-12 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2004-07-12 00:00:00 | TO COMM BD#52 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-06-22 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-06-22 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-06-22 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2004-06-22 00:00:00 | TO COMM BD INTERIOR PARTITION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2004-08-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-08-02 |
Time |
09:26 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-08-02 |
Time |
09:13 |
Sent To |
B |
|
| Notes |
| 2004-08-02 00:00:00 | RELOCATING AH-2 TO NEW SPACE.OUTSIDE | | | AIR IS EXISTING AND WILL NOT CHANGE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2004-07-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-07-16 |
Time |
10:43 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2004-07-16 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2004-07-16 00:00:00 | PLAN SHEET 3 OF 4 INDICATES NO | | | MECHANICAL WORK.ALL SPACES ARE | | | OCCUPIED WITH NO CHANGES TO THE | | | EXISTING O.A. OR HVAC SYTEM. | | | NO MECHANICAL CONTRACTOR INDICATED ON | | | PERMIT APPLICATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-07-06 |
Time |
10:36 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-07-06 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2004-07-06 00:00:00 | DENIED: | | | PERMIT APPLICATION INDICATES INTERIOR | | | PARTITION & 2 ELEC SUB-PANELS.PLEASE | | | CLARIFY.IS THIS AN INTERIOR BUILD | | | OUT?IS THIS SPACEOCCUPIED? | | | | | | 1. INDICATE EQUIPMENT SCHEDULE. NEW OR | | | EXISTING. | | | | | | 2. PROVIDE DUCT & GRILLE SIZE, MATERIAL, | | | AND LAYOUT FOR ALL NEW DUCTWORK. | | | INDICATE EXISTING DUCTWORK. | | | | | | 3. PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2001 FBC(M) 403.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2004-07-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-07-10 |
Time |
06:23 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2004-07-10 |
Time |
06:23 |
Sent To |
|
|
| Notes |
| 2004-07-10 00:00:00 | NO PLUMBING PLANS/WORK SUBMITTED |
|
|