Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-07-03 Cont ID  
Sent By jwitmer Date 2006-07-03 Time 14:34 Rev Time 0.55
Received By jwitmer Date 2006-07-03 Time 14:34 Sent To PC
Notes
2006-07-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04061027
 ADD: 525 S FLAGLER DR/ #3005
 CONT: WOOLEMS
 TEL: (561)835-0401
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 RESTAMP REVIEW
 ACTION: DENIED
 104.5.1
 EVERY PERMIT ISSUED SHALL BECOME INVALID
 UNLESS THE WORK
 AUTHORIZED BY SUCH PERMIT IS COMMENCED
 WITHIN 6 MONTHS AFTER ITS
 ISSUANCE, OR IF THE WORK AUTHORIZED BY
 SUCH PERMIT IS SUSPENDED OR
 ABANDONED FOR A PERIOD OF 6 MONTHS
 AFTER THE TIME THE WORK IS COMMENCED.
  
 NO ACTIVITY ON PERMIT, EXPIRED, WILL
 REQUIRE A NEW PERMIT UNDER THE 2004
 FLORIDA BUILDING CODE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-09-23 Cont ID  
Sent By jwitmer Date 2004-09-23 Time 09:21 Rev Time 1.00
Received By jwitmer Date 2004-09-23 Time 09:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-08-03 Cont ID  
Sent By jwitmer Date 2004-08-03 Time 13:39 Rev Time 0.75
Received By jwitmer Date 2004-08-03 Time 12:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-25 Cont ID  
Sent By jwitmer Date 2004-06-25 Time 16:35 Rev Time 0.55
Received By jwitmer Date 2006-07-03 Time 14:34 Sent To PC
Notes
2004-06-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04061027
 ADD: 529 S. FLAGLER DR# PENT1E/
 CABANA# 41
 CONT: API CONSTRUCTION
 TEL: (561)715-9025
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS IN BATHROOM
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-06-25 Cont ID  
Sent By dpalmer Date 2006-06-25 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2006-06-25 Time 14:23 Sent To PC
Notes
2006-06-25 00:00:00********* UNSAT 3RD TIME********
  
 1) NOTE: PLEASE SEE COMMENTS FROM ALL
 PREVIOUS REVIEW WHICH ARE ATTACHED.
 PLEASE SEE THAT PLANS ARE STILL BEING
 SUBMITTED WHICH ARE NOT ACCEPTABLE AS
 THE ORIGINAL DESIGN TEAM OF RECORD IS
 NOT THE SAME.
 PLEASE SEE NOW TITLE BLOCKS CONTAIN
 NAMES OF OTHER FIRMS WITH OUT THE
 CORRECT LICENSURE AS REQUIRED UNDER
 FAC61G1-16.004, FS 481.219
 PLEASE KNOW, ALL COMMENTS FROM REDLINED
 PLANS FROM "04" NEED TO BE ADDRESSED AND
 PLEASE CALL TO GO OVER COMMENTS IF THERE
 ARE ANY QUESTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-06-16 Cont ID  
Sent By dpalmer Date 2006-06-16 Time 07:12 Rev Time 0.00
Received By dpalmer Date 2006-06-16 Time 07:09 Sent To PC
Notes
2006-06-16 00:00:00********** UNSAT ************
  
  
 1) NOTE: PLEASE SEE PLANS SUBMITTED ARE
 NOT DONE BY THE DESIGNER OF RECORD.
 PLEASE SEE FS 481 AND 471 WHICH REQUIRES
 ALL REVISIONS TO RECORD PLANS TO BE DONE
 BY THE DESIGN PROFESSIONAL OF RECORD.
  
 ** PLANS ARE SUBMITTED ONCE AGAIN NOT
 DONE BY THE DESIGNER OF RECORD.
  
 2) NOTE: PLEASE SEE REVISED CORRECTIONS
 FOR NOTES WHICH WERE GIVEN IN 8/04 WHICH
 HAVE NEVER BEEN REVISED FOR CORRECTIONS
 AND SUBMITTED FOR REVIEW.
 PLEASE ADDRESS.
 PLEASE SEE THIS PROJECT IS UNDER THE
 2002 NEC.
 (210.12)
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-05-02 Cont ID  
Sent By dpalmer Date 2006-05-02 Time 18:04 Rev Time 0.00
Received By dpalmer Date 2006-05-02 Time 17:40 Sent To PC
Notes
2006-05-02 00:00:00*********** UNSAT **********
  
 1) NOTE: PLEASE SEE PLANS SUBMITTED ARE
 NOT DONE BY THE DESIGNER OF RECORD.
 PLEASE SEE FS 481 AND 471 WHICH REQUIRES
 ALL REVISIONS TO RECORD PLANS TO BE DONE
 BY THE DESIGN PROFESSIONAL OF RECORD.
  
 2) NOTE: PLEASE SEE REVISED CORRECTIONS
 FOR NOTES WHICH WERE GIVEN IN 8/04 WHICH
 HAVE NEVER BEEN REVISED FOR CORRECTIONS
 AND SUBMITTED FOR REVIEW.
 PLEASE ADDRESS.
  
 3) NOTE: PLEASE SEE SCOPE OF WORK NOW
 SHOWN ON PLANS IS NOT PART OF PERMIT.
 IF ADDITIONAL WORK IS BEING DONE, PLEASE
 REVISE SCOPE, REVISE VALUE AND ADJUST
 PER FBC 104.6.5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-08-31 Cont ID  
Sent By dpalmer Date 2004-08-31 Time 07:36 Rev Time 0.33
Received By dpalmer Date 2004-08-31 Time 07:29 Sent To  
Notes
2004-08-31 00:00:00********* NOTES REDLINED **************
  
 1)NOTE: PLEASE SEE AHU AND OVEN ARE
 SHOWN WITH A LOAD OF 6KW AND 1-POLE 15A
 BRKR AND AHU AT 5KW W/ 1-POLE 20A BRKR?
 THIS WAS NOTED ON PREVIOUS REVIEW.
  
 2)NOTE: PLEASE SEE 210.8A6 FOR REQUIRED
 GFI PROTECTION SERVING KITCHEN COUNTER-
 -SPACE.
  
 3)NOTE: NOTED, ALL NEW BRANCH CIRCUITS
 FEEDING EXISTING BEDRMS TO HAVE ARC-
 -FAULT PROTECTION. 2002 NEC 210.12

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-28 Cont ID  
Sent By dpalmer Date 2004-07-28 Time 09:56 Rev Time 0.75
Received By dpalmer Date 2004-07-28 Time 09:56 Sent To  
Notes
2004-07-28 00:00:00********* UNSAT **********************
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE.
 PLEASE CORRELATE LOADS ALONG WITH OCP.
 PLEASE SEE AHU, SHOWS 5KW W/50A OCP,
 9.5KW OVEN W/ 40A OCP ETC.
  
 2)NOTE: PLEASE SEE MISSING TWO SMALL
 APPLIANCE CIRCUITS REQUIRED. 210.11C1
  
 3)NOTE: PLEASE SEE RECEPTS ARE SHOWN ON
 DIMMERS. THIS IS NOT PERMITTED.
  
 4)NOTE: PLEASE SEE LOAD CALCULATION
 SUBMITTED SHOWS LOAD AT 288A'S ON A 200A
 PANEL. PLEASE SUBMIT LOAD CALCS PER NEC
 220.31
  
 5)NOTE: PLEASE SEE ANY NEW BRANCH CIR-
 -CUITS TO BEDRMS WILL REQUIRE ARC FAULT
 PROTECTION. 2002 NEC 210.12B. PLEASE
 SEE SD'S ??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-23 Cont ID  
Sent By dpalmer Date 2004-06-23 Time 07:36 Rev Time 0.50
Received By dpalmer Date 2004-06-23 Time 07:36 Sent To  
Notes
2004-06-23 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE TITLE BLOCK IS TO
 CONTAIN ALL INFORMATION AS SETFORTH IN
 FAC 61G1-16.004.FS 481.219
 PLEASE SEE FS'S REQUIRED "LEGAL SIGNAT-
 -URE" FOR ARCH/ FS 481.221. PLEASE
 PROVIDE A SIGNED, DATED AND SEALED
 LETTER STATING THIS IS YOUR LEGAL
 SIGNATURE. THIS LETTER MUST ALSO BE
 NOTARIZED.
 **WE HAVE HAD SOME ISSUES WITH FORGERIES
 AND NOW MAINTAIN A FILE FOR SIGNATURES
 OF ARCH'S AND ENGINEERS.
  
 2)NOTE: PLEASE SEE KITCHEN LAYOUT,ONE
 NOTE MENTIONS NEW OUTLET FOR DRYER WITH
 ARROW, YET THAT CIRCUIT # ON SCHEDULE
 INDICATES FRIG??
  
 3)NOTE: PLEASE 2-POLE CIRCUIT IN KITCHEN
 IS LABELED CIRCUIT 3,4. PLEASE VERIFY,
 COOKTOP/OVEN. THIS APPEARS TO BE ON
 THE SAME PHASE? (B)
  
 4)NOTE: PLEASE LABEL NEW CIRCUITS ALSO
 AND CORRELATE WITH PANEL SCHEDULE. PLANS
 SHOW EXISTING BUT NOT NEW?
  
 5)NOTE: PLEASE VERIFY NEW OR EXSITING
 SD'S REQUIRED UNDER NFPA-72.8-1.4.1.6.2
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 THAT MAY OR MAY NOT HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-29 Cont ID  
Sent By mcarsill Date 2004-07-29 Time 11:06 Rev Time 0.00
Received By mcarsill Date 2004-07-29 Time 11:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By mcarsill Date 2004-06-24 Time 09:55 Rev Time 0.00
Received By mcarsill Date 2004-06-24 Time 09:54 Sent To  
Notes
2004-06-24 00:00:001) ENSURE THAT EXISTING ELECTRIC
 POWERED SMOKE DETECTORS ARE IN PROPER
 WORKING ORDER. COULD NOT LOCATE ANY
 SMOKE DETECTORS ON PAGE E-2 ALTHOUGH
 IT IS PRESENT ON THE LEGEND.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE SPRINKLER REMODEL UNLESS
 THE WORK INVOLVES FIVE OR LESS
 SPRINKLER HEADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 14:04 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 14:04 Sent To E
Notes
2006-06-22 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 13:50 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 13:50 Sent To P
Notes
2006-06-22 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 09:14 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 09:14 Sent To B
Notes
2006-06-22 00:00:00TO "JWITMER" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 16:13 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 16:13 Sent To E
Notes
2006-06-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-27 Cont ID  
Sent By adarroug Date 2006-04-27 Time 16:15 Rev Time 0.00
Received By adarroug Date 2006-04-27 Time 16:15 Sent To E
Notes
2006-04-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-08-25 Time 16:04 Rev Time 0.00
Received By csiegber Date 2004-08-25 Time 16:04 Sent To  
Notes
2004-08-25 00:00:00TO COMM BD#2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 16:28 Sent To  
Notes
2004-07-22 00:00:00TO COMM BD#28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-10 Cont ID  
Sent By kstevens Date 2004-07-10 Time 12:47 Rev Time 0.00
Received By kstevens Date 2004-06-22 Time 15:48 Sent To  
Notes
2004-06-22 00:00:00TO COMM BD#26

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-06-30 Cont ID  
Sent By pkrauss Date 2004-06-30 Time 11:28 Rev Time 0.20
Received By pkrauss Date 2004-06-30 Time 11:28 Sent To  
Notes
2004-06-30 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
 PLEASE PROVIDE PLANS AND EQUIPMENT
 SCHEDULE WITH MECHANICAL PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-07-13 Cont ID  
Sent By jleech Date 2006-07-13 Time 13:52 Rev Time 0.00
Received By jleech Date 2006-07-13 Time 13:52 Sent To  
Notes
2006-07-13 00:00:00DENIED;
  
 SUBMITED REVISION IS NOT DRAWN BY THE
 ARCHITECURAL FERM OF RECORD.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-09-24 Cont ID  
Sent By kstevens Date 2004-09-24 Time 07:31 Rev Time 0.50
Received By kstevens Date 2004-09-23 Time 18:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-08-07 Cont ID  
Sent By kstevens Date 2004-08-07 Time 11:14 Rev Time 0.33
Received By kstevens Date 2004-08-07 Time 11:14 Sent To  
Notes
2004-08-07 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) FROM PREVIOUS REVIEW, A SANITARY AND
 WATER RISER DIAGRAM SHALL BE REQUIRED IN
 ISOMETRIC FORM. SHOW PIPE SIZES, POINT
 OF CONNECTION TO EXISTING FOR NEW WORK.
 SHOW PIPE SIZES, LOCATION OF REQUIRED
 WATER HAMMERS, AND CONNECTION TO EXIST-
 ING. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-10 Cont ID  
Sent By kstevens Date 2004-07-10 Time 07:17 Rev Time 1.00
Received By kstevens Date 2004-07-10 Time 07:17 Sent To  
Notes
2004-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A-1 INDICATES NEW TUB IN NEW LO-
 CATION IN MASTER BATH, NEW WATER CLOSET
 AND LAV IN NEW LOCATION IN POWDER ROOM,
 AND NEW SINK IN NEW LOCATION IN KITCHEN.
 SUBMIT SANITARY AND WATER RISER DIAGRAMS
 SHOWING ALL NEW WORK AND HOW IT CONNECTS
 TO EXISTING RISERS. SHOW ALL PIPE SIZES,
 AND WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9. SECTION 104.3.1.1.
 2) SHT A-1 INDICATES A FLOOR DRAIN USING
 THE EXISTING SHOWER DRAIN. SUBMIT A DE-
 TAIL SHOWING HOW THE DRAIN WILL BE IN-
 STALLED AND HOW THE DRAIN WILL BE SEALED
 TO PREVENT WATER FROM LEAKING TO FLOOR
 BELOW.
 3) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL DOCUMENTS TO BE
 FILED FOR PUBLIC RECORD. INITIALS ARE
 NOT ACCEPTABLE. PLEASE PROVIDE PROOF OF
 LEGAL SIGNATURE WITH DRIVERS LICENSE,
 VOTER REGISTRATION, OR ARCHITECTS STATE
 LICENSE WITH SIGNATURE. ALSO SUBMIT A
 SIGNED/SEALED/NOTORIZED LETTER FOR OUR
 FILES WITH LEGAL SIGNATURE. FAC 61G1-16.
 003 & FS 481.2055.
 4) FIRM LICENSE NUMBER REQUIRED ON TITLE
 BLOCK. FAC 61G1-16.004(2) & FS 481.2055.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]