Plan Review Details - Permit 04061022
Plan Review Stops For Permit 04061022
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-04-06 Cont ID  
Sent By jwitmer Date 2006-04-06 Time 08:58 Rev Time 1.11
Received By jwitmer Date 2006-04-06 Time 08:58 Sent To PC
Notes
2006-04-06 00:00:00REVISION # 6 2-15-06

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-01-30 Cont ID  
Sent By jwitmer Date 2006-01-30 Time 08:53 Rev Time 1.55
Received By jwitmer Date 2006-01-30 Time 07:30 Sent To  
Notes
2006-01-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04061022
 ADD: 605 N OLIVE AV
 CONT: CATALFUMO CONSTRUCTION
 TEL: (561)694-8818
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1) SHEET A-1.1 OFFICE 110 SEE 11-4.13.6
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 2) SHEET A-1.2 ROOMS 214 & 215
 SHEET -5.2 DETAIL# 1
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3)A 2.2 MISSING EXIT LIGHT IN HALLWAY
 BEFORE STAIR ENCLOSURE# 1.
  
 4) 1 SEET OF MEP IS MISSING THE ENGINEER
 RAISED SEAL & SIGNATURE.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-06-10 Cont ID  
Sent By jwitmer Date 2005-06-10 Time 08:03 Rev Time 2.22
Received By jwitmer Date 2005-06-10 Time 08:03 Sent To PC
Notes
2005-06-10 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 04061022
 ADDRESS: 605 N. OLIVE AV.
 CONT: CATALFUMO
 TELL # (561) 307-4836
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 BUILDING PROVISO:
 PLANS ARE MISSING THESE PRODUCT APPROVAL
 OR FLORIDA COVER SHEET OR DO NOT MEET
 THE WIND PRESSURES REQUIRED FOR THIS
 STRUCTURE. WINDOWS & DOORSWILL REQUIRE
 REVIEWED NOA'S BY THE BUCK INSPECTION
 (119).
 ROOFING APPROVALS BEFORE FIRST ROOF
 ASSEMBLIES INSPRCTION (112 ROOF METAL /
 TIN TAG)
  
 MISSING APPROVALS:
  
 A) DENS-GLASS GOLD SHEATHING- LOW
 PRESSURE
  
 B) JOHNS MANVILLE PVC OVER CONCRETE
 NO FL COVER SHEET/ NO SYSTEMS
 HIGHLIGHTED, SEE LIMITATIONS 7 & 9 FOR
 PRESSURES
  
 C) ROOF APPROVALS: ENGLERT SERIES 2000
 METAL PANEL OVER STEEL DECK LOW PRESURES
 GOOD FOR -62.5 REQUIRED -81.5. SYSTEM
 LIMITATION SEE # 1, FOR ENHANCED
 FASTENING.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-04-11 Cont ID  
Sent By jwitmer Date 2005-04-11 Time 07:40 Rev Time 1.11
Received By jwitmer Date 2005-04-11 Time 07:40 Sent To  
Notes
2005-04-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04061022
 ADD: 605 N OLIVE AV
 CONT:CATALFUMO
 TEL: (561)307-4836
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4TH REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)COMMENT #3 FROM THE PREVIOUS REVIEW:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR DOORS REPORT SUBMITTED FOR
 ALUMINIUM 35-H ONLY DOOR SCHEDULE
 INDICATES EXT. DOOR #121 WOOD DOOR
 DOOR # 123 HOLLOW METAL
 B) DECRATIVE STORM SHUTTERSMISSING FL
 COVERSHEET
 C) ROOFING ASSEMBLIES, MODIFIED
 BITUMEN SEE A-1.3 NO FL COVER SHEET,
  
 NO REPORT SUBMITTED
 D) ROOFING ASSEMBLIES 2000 SEERIES ROOF
  
 PANEL SYSTEM NO FL COVERSHEET
 E) PANEL WALL SYSTEMS: SOFFITS
 PRE-MANUFACTERED SOFFIT SYSTEM NO
 FL COVERSHEET NOR REPORT SEE A-4.5
  
 3) COMMENT # 3 FROM THE PREVIOUS
 REVIEW:PROVIDE MORE INFORMATION,
 THE ACCESSIBLE RAMP AND TOP LANDING.
 THERE SEEMS TO BE A DISCREPANCY, THE
 TOP OF THE RAMP IS AT ELEVATION 10.80
 DIRECTLY TO THE LEFT ABOUT 4'-0" AWAY
 THE ELEVATION IS 11.20?
 THERE WAS NO RESPONSE LETTER AND NO
 CHANGE TO THE PLANS, SEE 11-4.3.7 CROSS
 SLOPE FOR AN ACCESSIBLE ROUTE TO BE NOT
 MORE THAN 1/50. THE ELEVATION CHANGE IN
 5'-0" IS APPROXIMATELY 2 1/2".
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-01-03 Cont ID  
Sent By jwitmer Date 2005-01-03 Time 10:12 Rev Time 2.00
Received By jwitmer Date 2005-01-03 Time 10:12 Sent To  
Notes
2005-01-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04061022
 ADD: 605 N OLIVE AV
 CONT:CATALFUMO
 TEL: (561)307-4836
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT# 6 FROM THE PREVIOUS REVIEW,
 FBC*102.2.7 ARCHITECTURAL TRIM, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL BE CONSTRUCTED OF APPROVED NON-
 COMBUSTIBLE MATERIALS OR FIRE RETARDANT
 TREATED WOOD.
 A) A-4.5 SEC. 1 FPR BRACKET
 B) A-4.5 SEC. 2 POLYMER FPR BRACKET
 PROVIDE DOCUMENTATION (TESTING TO ASTM
 E-84 OR ASTM E 136) THAT THESE PRODUCTS
  
 MEET THE REQUIREMENTS OF
 NON-COMBUSTIBLITY OR FIRE RETARDANT
 TREATED WOOD.
  
 COMMENT # 8 FROM THE PREVIOUS REVIEW:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR DOORS
 B) DECRATIVE STORM SHUTTERS
 C) TRUSS ANCHOR SYSTEMS
 D) ROOFING ASSEMBLIES, MODIFIED
 BITUMEN
 SEE A-1.3
 E) EFIS SYSTEMS SEE S-3 DETAIL # 7.
  
 3) COMMENT # 7 FROM THE PREVIOUS
 REVIEW:
 PROVIDE MORE INFORMATION,
 THE ACCESSIBLE RAMP AND TOP LANDING.
 THERE SEEMS TO BE A DISCREPANCY, THE
 TOP
 OF THE RAMP IS AT ELEVATION 10.80
 DIRECTLY TO THE LEFT ABOUT 4'-0" AWAY
 THE ELEVATION IS 11.20?
  
 4) THERE SEEMS TO BE A DISCREPANCY
 BETWEEN A-4.1, A-4.5 AND DETAIL 15 ON
 PAGE A-6.1 AND THE ROOFING PRODUCT
 APPROVALS AS TO WHERE THE INSULATION
 WILL BE, AS TO WHAT TYPE OF NAILABLE
 SHEATHING AND THE STANDING SEEM METAL
 ROOF.
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-08 Cont ID  
Sent By jwitmer Date 2004-11-08 Time 14:40 Rev Time 3.33
Received By jwitmer Date 2004-11-08 Time 14:35 Sent To  
Notes
2004-11-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04061022
 ADD:605 N OLIVE AV
 CONT: CATALFUMO
 TEL: (561)307-4836
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 2NDREVIEW
 ACTION:DENIED
  
  
 1)PROVIDE NOC RECORDED WITH THE
 CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT# 2 FROM THE PREVIOUS REVIEW:
 FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN
 QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE
 EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) COMMENT# 4 FROM PREVIOUS REVIEW,
 SHEET T-2 ACCESSIBILITY NOTES# 8, WHEN
 THERE IS NO EDGE TREATMENT THE MAXIMUM
 CHANGE IN GRADE IS 1/4"WHEN CHANGE IN
 GRADE IS BETWEEN 1/4" AND 1/2" A BEVEL
 MAY BE USED WITH THE SLOPE NO GREATER
 THAN 1:2 (11-4.5.2).DO NOT LEAVE THE
 QUESTION MARKS IN, FILL IN THE BLANKS!
  
 4) COMMENT#5 FROM PREVIOUS REVIEW,
 SHEET
 T-2 ACCESSIBILITY NOTES: #9 CORRECT
 HANDICAPPED PARKINGSPACE TO 12'-0"
 11-4.6.3.
  
 5) COMMENT #6 FROM PREVIOUS REVIEW,
 SHEET T-2 ACCESSIBILITY ROUTE IF PART OF
 A MEANS OF EGRESS, 44" REQUIRED, ALSO
 SEE (11-4.6.2(1) ALL PARKING SPACES MUST
 BE LOCATED ON AN ACCESSIBLE ROUTE, NO
 LESS THAN 44".
  
 6) COMMENT# 8 FROM PREVIOUS REVIEW,
 FBC* F102.2.7ARCHITECTURAL TRIM, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL BE CONSTRUCTED OF APPROVED
 NON-COMBUSTIBLE MATERIALS OR FIRE
 RETARDANT TREATED WOOD.ANNOTATE THE
 PLANS TO DEMONSTRATE COMPLIANCE.
 A)A-4.5 .SEC.1 FAUX PECKY CYPRESS
 B)A-4.5SEC.2 FIBER REINFORCED
 POLYMER FPR BRACKETS
 C)CEDAR FACIA
 PROVIDE DOCUMENTATION THAT THESE
 PRODUCTS WILL MEET THE REQUIREMENTS OF
 NON-COMBUSTIBILITY OR FIRE RETARDANT
 TREATED WOOD.
  
 7) COMMENT# 10 RAMPS
 A-1.1/A-3.1HANDRAILS, 11-4.8.5 IF A
 RAMP
 HAS A RISE GREATER THAN 6" OR A
 HORIZONTAL PROJECTION GREATER THAN 72",
  
 OF STRAIGHT AND LEVEL CLEARENCE
 HANDRAILSSHALL BE REQUIRED.
  
  
  
 8) COMMENT# 14 FROM THE PREVIOUS REVIEW:
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) EXTERIOR DOORS
 C) MULLIONS
 D) STORM SHUTTERS
 E) ROOFING ASSEMBLIES
 F) TRUSS ANCHORS
 G) EFIS SYSTEMS
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) COMMENT# 21 FROM THE PREVIOUS
 REVIEW:
 SHEET A-6.1 ROOFING DETAILS AND SHEET
 S-3 INDICATE THE METAL STANDING SEAM
 ROOFING ATTACHED DIRECTLY TO THE METAL
 DECK, PROVIDE TESTING REPORT WITH THIS
 TYPE OF TESTING. RESPONCE THE ROOFING IS
 ACTUALLY FASTENED TO THE COMPOSTION
 BOARD INSULATION. PROVIDE PRODUCT
 TESTING!
  
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-22 Cont ID  
Sent By jwitmer Date 2004-07-19 Time 14:54 Rev Time 4.00
Received By lmartine Date 2004-07-19 Time 14:54 Sent To Z
Notes
2004-07-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04061022
 ADD: 605 N OLIVE AVE
 CONT: CATALFUMO
 TEL: (561)307-4836
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4) SHEET T-2 ACCESSIBILITY NOTES:
 #8 WHEN THERE IS NO EDGE TREATMENT THE
 MAXIMUM CHANGE IN GRADE IS 1/4". WHEN
 CHANGE IN GRADE BETWEEN 1/4" AND 1/2"
 A BEVEL MAY BE USED WITH THE SLOPE NO
 GREATER THAN 1:2(11-4.5.2)
  
 5) SHEET T-2 ACCESSIBILITY NOTES:
 #9 CORRECT WIDTH TO BE 12'-0" (11-4.6.3)
  
 6) SHEET T-2 ACCESSIBILTY NOTES:
 #4 ACCESSIBLE ROUTE IF PART OF A MEANS
 OF EGRESS, 44" ALSO SEE (11-4.6.2(1)
 ALL PARKING SPACES MUST BE LOCATED ON AN
 ACCESSIBILE ROUTE NO LESS THAN 44".
  
 7) CORRET SHEET A-0.1 HURRICANE CRITERIA
 THE CITY OF WEST PALM BEACH IS NOT LOCA-
 TED IN A HIGH VELOCITY HURRICANE ZONE.
  
 8) F102.2.7 FIRE DISTRICT, STRUCTURE IS
 LOCATED IN A FIRE DISTRICT.ARCHITECTURAL
 TRIM ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT SHALL BE CONSTRUCTED OF APPROV-
 ED NONCOMBUSTIBLE MATERIALS OR FIRE
 RETARDANT TREATED WOOD.
 SEE SHEET A-4.1 SECTION 2, FACTORY
 HARD COATED FOAM "PECKY CYPRESS BEAMS".
 SEE SHEET A-4.5 SECTIONS 1,2& 3 THE
 FAUX PECKY CYPRESS BRACKETS.
  
 9) SEE SHEET A-1.1/A-3.1 ATM RAMP IS
 MISSING THE REQUIRED 5'-0" TOP LANDING.
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
  
 10)11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 11) THIS SAME DETAIL, COLUMN AND BASE,
 IS A MEANS OF EGRESS FOR THE ATM,
 11-4.3.3. IF A PERSON IN A WHEELCHAIR
 MUST MAKE A TURN AROUND AN OBSTRUCTION,
 THE MINIMUM CLEAR WIDTH OF THE ACCESS-
 IBLE ROUTE SHALL BE AS SHOWN IN
 FIGURE 7(A) AND (B).
  
 12)S-3 DETAIL# 5, INDICATES THE USE
 PLYWOOD SHEATHING, "FIRE DISTRICT" NO
 TYPE VI CONSTRUCTION ALLOWED. PLANS
 INDICATE TYPE V BUILDING.
  
 13) A-01 BUILDING DATA INDICATES THIS
 BUILDING WILL BE BOTH "1 HR PROTECTED"
 AND "FIRE SPRINKLERED". NO INFORMATION
 HAS BEEN PROVIDED, PLEASE SUBMIT.
  
 14)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) EXTERIOR DOORS
 C) MULLIONS
 D) STORM SHUTTERS
 E) ROOFING ASSEMBLIES
 F) TRUSS ANCHORS
 G) EFIS SYSTEMS
  
 15) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 16) STURCTURAL PLANS DO NOT PROVIDE
 THE WINDOW NOR DOOR BUCK ATTACHMENT.
 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 17) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 18)1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 19) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 20) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 21) SHEET A-6.1 ROOFING DETAILS AND
 SHEET S-3 INDICATE THE METAL STANDING
 SEAM ROOFING ATTACHED DIRECTLY TO THE
 METAL DECK, PROVIDE THE PRODUCT TESTING
 REPORT WITH THIS TYPE OF TESTING.
  
 22) S-3 DOOR AND WINDOW SCHEDULE HAS
 NO IDENTIFYING MARKS?
  
 23) ARCHITECTURAL & STRUCURAL BOTH INDIC
 ATE THIS STRUCTURE IS DESIGNED AS A "C"
 EXPOSURE, THE PRODUCT TESTING REPORTS
 WILL REQUIRE THE HIGHER WIND PRESSURES
 AS INDICATED IN THE WINDOW AND DOOR
 SCHEDULE.
  
 24)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-06-08 Cont ID  
Sent By dpalmer Date 2006-06-08 Time 12:58 Rev Time 0.00
Received By dpalmer Date 2006-06-08 Time 10:44 Sent To PC
Notes
2006-06-08 00:00:00REVISION FOR ELECTRICAL, PLANS NOT
 REVIEWED BY FIRE REVIEW.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-03-27 Cont ID  
Sent By dpalmer Date 2006-03-27 Time 11:56 Rev Time 0.00
Received By dpalmer Date 2006-03-27 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-01-09 Cont ID  
Sent By dpalmer Date 2006-01-09 Time 11:03 Rev Time 0.00
Received By dpalmer Date 2006-01-09 Time 11:03 Sent To  
Notes
2006-01-09 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE SEE ONLY ONE SET IS
 SIGNED, DATED AND SEALED BY THE ENGINEER
 OF RECORD.
 PLEASE SEE FAC 61G15-23.002 WHICH
 REQUIRES ALL SETS TO BE SIGNED, DATED
 AND SEALED.
 PLEASE ALSO SEE THE SAME FLORIDA
 ADMINISTRATIVE CODE WHICH REQUIRES THE
 PRINTED NAME AND LICENSE # FOR SAID
 ENGINEER OF TITLE BLOCK.
  
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL REVIEWER(S) WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOT: PLEASE VERIFY OCP FOR AHU'S, HEAT
 ETC TO BE SIZEDA MIN OF 125% PER
 424.3B
 PLEASE ADJUST.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-08-31 Cont ID  
Sent By dpalmer Date 2005-08-31 Time 21:58 Rev Time 0.25
Received By dpalmer Date 2005-08-31 Time 21:54 Sent To P
Notes
2005-08-31 00:00:00******** UNSAT *******
  
 1)NOTE: PLEASE SEE ANY REVISIONS TO
 ELECTRICAL UNDER INSTALLATIONS OF
 CONDUITS, MUST BE SUBMITTED SIGNED,DATED
 AND SEALED BY THE ELECTRICAL ENGINEER OF
 RECORD.
 PLEASE ALSO SEE ALL PLANS/ DRAWINGS MUST
 CONTAIN TITLE BLOCKS AS REQUIRED UNDER
 FAC 61G15-23.002.
 PLEASE SEE PLUMB REVIEW COMMENTS FOR
 PLAN SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-12-27 Cont ID  
Sent By dpalmer Date 2004-12-27 Time 13:06 Rev Time 0.50
Received By dpalmer Date 2004-12-27 Time 13:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-10-19 Cont ID  
Sent By dpalmer Date 2004-10-19 Time 16:57 Rev Time 1.25
Received By dpalmer Date 2004-10-19 Time 16:03 Sent To  
Notes
2004-10-19 00:00:00********** UNSAT 2ND REVIEW ************
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE#1 FROM PREVIOUS REVIEW.
 REPLY LETTER MENTIONS ADDED TO TITLE
 BLOCK, HOWEVER THIS COULD NOT BE LOCATED
 PLEASE SEE FAC 61G15-23.002.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWERS.
  
 2)NOTE: NOTE#2 FROM PREVIOUS REVIEW.
 LETTER MENTIONS REVISED/ADDED FIXTURE
 TYPE ON E8.1, YET THIS WAS NOT FOUND.
  
 3)NOTE: NOTE#5 FROM PREVIOUS REVIEW,
 PLEASE SEE 230.82 FOR EQUIPMENT PERMITT-
 -ED AHEAD OF MAIN. THIS IS NOT PERMITTED
 IN NEC.
 PLEASE ALSO SEE 230.72
  
 4)NOTE: NOTE#7 FROM PREVIOUS REVIEW.
 PLEASE SEE 310.16,240.4 ETC. SOME MOTOR
 ONLY LOADS (CU'S) ARE PERMITTED TO
 PROTECT AT THE NEXT SIZE UP.HOWEVER,
 AHU/HEAT ETC IS NOT, 424.3B ALONG W/
 ABOVE.
  
 PLEASE SEE COPY OF FS 553.80(2)(B) FOR
 NOTICE ONLY GIVEN AT THIS TIME.
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-25 Cont ID  
Sent By dpalmer Date 2004-06-25 Time 07:42 Rev Time 2.00
Received By dpalmer Date 2004-06-25 Time 06:25 Sent To  
Notes
2004-06-25 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002.
 PLEASE INCLUDE ALL INFORMATION ON TITLE
 BLOCK AS REQUIRED.
 NAME AND LICENSE # OF ENGINEER.
  
 2)NOTE: PLEASE SEE EXT LTS SHOWN AS X-1,
 YET THIS TYPE OF FIXTURE DOES NOT SEEM
 TO BE ON FIXTURE LEGEND?
  
 3)NOTE: PLEASE SEE NOTE ON RISER MENTION
 -S TO SEE DETAIL FOR GROUNDING ELECTRODE
 SYSTEM ON E7.1. PLEASE SEE 250.50 FOR
 REQUIRED COLD WATER, FOOTER STEEL ETC.
  
 4)NOTE: PLEASE PROVIDE CALCS/INFORMATION
 FOR WIND LOADING OF LT POLES/FIXTURES.
 MUST MEET FBC 140 MPH.
  
 5)NOTE: PLEASE SEE 230.82 FOR PERMITTED
 EQUIPMENT TO CONNECTED AHEAD OF THE
 MAIN.
 PLEASE ALSO SEE MORE INFORMATION IS REQ-
 -UIRED FOR ELEVATOR DISC. OCP ETC.
  
 6)NOTE: PLEASE SEE 620.22 FOR REQUIRED
 CIRCUITS.
 PLEASE SEE WE ALSO COULD NOT LOCATE
 REQUIRES LTS FOR ELEV.
  
 7)NOTE: PLEASE CORRELATE OCP AND AWG
 ON MDP PANEL SCHEDULE.
 APPEARS TO SHOW SOME SIZEDOVER
 RATING OF WIRE PER 310.16
 #12 W/ 70A OCP? #12 W/ 35A SOME COND/MOT
 -OR LOADS ARE PERMITTED TO HAVE SIZE
 ACCORDING TO NAMEPLATE.
  
 8)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISC. 250.24,250.6
  
 9)NOTE: PLEASE CLARIFY TYPE OF CONDUCTOR
 -S FOR FEEDERS ETC. THERE IS A NOTE
 THAT MENTIONS, AL/ CU BUT THE ONLY ITEM
 FOUND THAT INDICATE CU IS FOR BUS.
 PLEASE SEE LOCAL AMENDMENST, NO ALUM
 SMALLER THAN #2 310.2. 250.62
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-07-21 Cont ID  
Sent By rchokshi Date 2006-07-21 Time 13:19 Rev Time 0.00
Received By rchokshi Date 2006-07-21 Time 13:17 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-06-25 Cont ID  
Sent By mamini Date 2004-06-25 Time 14:46 Rev Time 0.00
Received By rchokshi Date 2004-06-25 Time 13:15 Sent To  
Notes
2006-07-21 00:00:00PASSED.CHECKED ALL NOTES BY AMINI. ALL
 NOTES ARE TAKEN CARE OF. 7-21-06. AS
 BUILT DRAWING OF MAY 2006 LOOKS OK TOO.
 7/21/06--CLICKED THIS STOP IN
 ERROR--RASIK
2004-06-25 00:00:00PASSED WITH PROVISOS:
 1. ALL OFF STREET PARKING STALLS MUST BE
 PAINTED WITH DOUBLE 4" WIDE STRIPES, PER
 CITY OF WEST PALM BEACH REQUIREMENTS.
 2. POLLUTION PREVENTION PLANS MUST BE
 INSTALLED IN THE FIELD PROIR TO ANY
 CONSTRUCTION ACTIVITIES.
 3. ANY WORK WITHIN PUBLIC R.O.W REQUIRES
 A SEPARATE PERMIT FROM PUBLIC UTILITIES
 AND ENGINEERING. 494-1086 WINDEL PALMER.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-04-11 Cont ID  
Sent By mwennerg Date 2006-04-11 Time 09:48 Rev Time 0.00
Received By mwennerg Date 2006-04-11 Time 09:48 Sent To  
Notes
2006-04-11 00:00:00REVISION DATED 2/15/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-01-11 Cont ID  
Sent By mwennerg Date 2006-01-11 Time 10:08 Rev Time 0.00
Received By mwennerg Date 2006-01-11 Time 10:08 Sent To  
Notes
2006-01-11 00:00:00REVISION DATED 12/01/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-01-05 Cont ID  
Sent By mcarsill Date 2005-01-05 Time 17:12 Rev Time 0.00
Received By mcarsill Date 2005-01-05 Time 17:11 Sent To  
Notes
2005-01-05 00:00:001. DOORS 212,218,AND 115 SHALL BE
 FIRE RATED. PLEASE REVISE DOOR
 SCHEDULE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-10-20 Cont ID  
Sent By mcarsill Date 2004-10-20 Time 16:27 Rev Time 0.00
Received By mcarsill Date 2004-10-20 Time 16:26 Sent To  
Notes
2004-10-20 00:00:001) ALL NEW STAIRS AND RAMPS REQUIRE
 HANDRAILS ON BOTH SIDES. THIS INCLUDES
 EXIT DISCHARGE LOCATIONS.
  
 2) REQUIRED FIRE ALARM SYSTEM SHALL
 BE UL LISTED FOR CENTRAL STATION
 SERVICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-23 Cont ID  
Sent By mcarsill Date 2004-06-23 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2004-06-23 Time 14:45 Sent To  
Notes
2004-06-23 00:00:001) ELECTRONIC SWITCHES, CHAIN AND LOCK
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 2) ARE ANY HANDRAILS PLANNED FOR
 STAIR TREADS AT THE EAST/NORTH ENTRY
 PORTICO.
  
 3) TACTILE SIGNAGE REQUIRED AT EXIT
 DOOR LOCATIONS.
  
 4) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF 6" HIGH NUMBERS
 ARE REQUIRED.
  
 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM INSTALLATION.
 CONNECTION TO CITY MAIN MUST BE APPROVED
 BY CITY UTILITIES PRIOR TO SUBMITTING
 PLANS.
  
 7) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. THE FIRE ALARM
 SYSTEM SHALL BE MONITORED BY A LICENSED
 UL COMPANY APPROVED FOR CENTRAL STATION
 SERVICE.
  
 8) NO COMBUSTIBLES ALLOWED IN THE
 RETURN AIR PLENUM.
  
 9) ELEVATOR WARNING SIGNS REQUIRED AT
 ELEVATOR ENTRANCES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-05-27 Cont ID  
Sent By adarroug Date 2006-05-27 Time 15:19 Rev Time 0.00
Received By adarroug Date 2006-05-27 Time 15:19 Sent To E
Notes
2006-05-27 00:00:00TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 08:50 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 08:50 Sent To B
Notes
2006-05-26 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-03-27 Cont ID  
Sent By dpalmer Date 2006-03-27 Time 07:40 Rev Time 0.00
Received By dpalmer Date 2006-03-27 Time 07:40 Sent To  
Notes
2006-03-27 00:00:00TO COMM BOARD #17

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 11:37 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 11:37 Sent To  
Notes
2006-03-02 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 11:30 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 11:30 Sent To  
Notes
2006-01-05 00:00:00TO "COMM" BD#54
2005-12-10 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-29 Cont ID  
Sent By adarroug Date 2005-08-29 Time 16:48 Rev Time 0.00
Received By adarroug Date 2005-08-29 Time 16:48 Sent To E
Notes
2005-08-29 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 14:07 Rev Time 0.00
Received By shill Date 2005-06-08 Time 14:07 Sent To B
Notes
2005-06-08 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 14:23 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 14:23 Sent To  
Notes
2005-03-31 00:00:00TO "COMM" BD#62

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-07 Cont ID  
Sent By mjacobs Date 2005-01-07 Time 15:49 Rev Time 0.00
Received By mjacobs Date 2005-01-07 Time 15:48 Sent To  
Notes
2005-01-07 00:00:00TO "COMM BD#17/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-13 Cont ID  
Sent By mjacobs Date 2004-12-13 Time 08:29 Rev Time 0.00
Received By mjacobs Date 2004-12-13 Time 08:29 Sent To  
Notes
2004-12-13 00:00:00SENT TO "COMM BD#43/RESUB."

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-04 Cont ID  
Sent By kstevens Date 2004-08-04 Time 11:36 Rev Time 0.00
Received By csiegber Date 2004-06-22 Time 16:07 Sent To  
Notes
2004-06-22 00:00:00TO COMM BD#54

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2006-11-03 Cont ID  
Sent By pkrauss Date 2006-11-03 Time 11:56 Rev Time 0.00
Received By pkrauss Date 2006-11-03 Time 11:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-10-13 Cont ID  
Sent By hmoser Date 2006-10-13 Time 09:07 Rev Time 0.00
Received By hmoser Date 2006-10-13 Time 09:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2006-10-12 Cont ID  
Sent By pkrauss Date 2006-10-12 Time 15:10 Rev Time 0.00
Received By pkrauss Date 2006-10-12 Time 15:10 Sent To  
Notes
2006-10-12 15:12:00TEST & BALANCE REPORT

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-04-10 Cont ID  
Sent By pkrauss Date 2006-04-10 Time 09:26 Rev Time 0.00
Received By pkrauss Date 2006-04-10 Time 09:26 Sent To  
Notes
2006-04-10 00:00:00PROVISO:
 1.EXHAUST SHALL NOT BE DIRECTED ONTO
 WALKWAYS OR TERMINATE IN A MANNER THAT
 CREATE A NUISANCE PER 2001 FMC 401.5.2.
  
 2.PLAN SHEET M7.2 INDICATES AUXILIARY
 DRAIN PAN ONLY REQUIRED FOR UNITS
 LOCATED ABOVE THE CEILING.PER 2001 FMC
 307.2.3 & 307.2.4, AN AUXULAIRY DRAIN
 PAN IS REQUIRED.THE FLOAT SWITCH SHALL
 BE INSTALLED IN THE AUXILIARY DRAIN PAN.
 PLEASE REVISE PLAN TO REFLECT THE
 REQUIREMENT OF ONE OF THE THREE METHODS
 DESCRIBED IN THE AFOREMENTIONED CODE
 SECTIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-01-21 Cont ID  
Sent By pkrauss Date 2006-01-21 Time 09:04 Rev Time 0.00
Received By pkrauss Date 2006-01-21 Time 09:04 Sent To  
Notes
2006-01-21 00:00:00DENIED:
 PLEASE NOTE, ONLY ONE SET OF PLANS WERE
 SIGNED, SEALED AND DATED BY THE
 ENGINEER.TWO COMPLETE SETS ARE
 REQUIRED IN ACCORDANCE WITH 2001 FBC
 104.2.1.PLANS ARE OTHERWISE CODE
 COMPLIANT.
  
 PER FS 471.025 & FAC 61G15-23.002 (1) &
 (2), ENGINEER IS REQUIRED TO SIGN, SEAL,
 AND DATE PLANS, REPORTS AND
 SPECIFICATIONS SUBMITTED FOR PUBLIC
 RECORD.WHEN PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING FIRM SHALL
 INDICATE THE CERTIFICATE OF
 AUTHORIZATION ON THE PLANS.
  
 IF YOU HAVE ANY QUESTION, PLEASE CONTACT
 PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-01-06 Cont ID  
Sent By pkrauss Date 2005-01-06 Time 08:34 Rev Time 0.40
Received By pkrauss Date 2005-01-06 Time 08:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-10-26 Cont ID  
Sent By pkrauss Date 2004-10-26 Time 07:42 Rev Time 0.40
Received By pkrauss Date 2004-10-26 Time 07:25 Sent To  
Notes
2004-10-26 00:00:00DENIED:
 1.PLAN SHEETS M1.1, M7.2, ARE NOT
 SIGNED & DATED BY THE ENGINEER.PLAN
 SHEETS M1.2, M7.1, M8.1, M8.2, M9.1 ARE
 NOT SIGNED,SEALED & DATED AS REQUIRED BY
 FS 471.025 & FAC 61G15-23.001.
  
 2.PLEASE NOTE, PLAN SHEET A-1.2
 THE LEGEND INDICATES WALL TYPES ON SHEET
 A-0.2, THIS SHOULD READ A-7.1.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-29 Cont ID  
Sent By pkrauss Date 2004-06-29 Time 15:51 Rev Time 0.55
Received By pkrauss Date 2004-06-29 Time 15:51 Sent To  
Notes
2004-06-29 00:00:00DENIED:
 1.PLAN SHEET M1.1, FIRE DAMPERS
 REQUIRED ON DUCTS PENETRATING OR
 TERMINATING AT A RATED WALL PER 2001
 FBC(M) 607.1.2.DUCTS TERMINATING AT
 THE ELEV MACHINE RM, STORAGE RM, & ATM
 RM ARE REQUIRED TO HAVE FIRE DAMPERS.
  
 2.PLAN SHEET M7.2 DETAIL 1 NOTE 4,
 AUXILIARY DRAIN PAN SHALL HAVE OVERFLOW
 PROTECTION BY MEANS OF A FLOAT SWITCH OR
 AUXILIARY DRAIN LINE TERMINATING AT A
 CONSPICUOUS POINT PER 2001 FBC(M)
 307.2.3.PLEASE INDICATE WHICH METHOD
 WILL BE UTILIZED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 7 Status P Date 2006-04-19 Cont ID  
Sent By kstevens Date 2006-04-19 Time 14:43 Rev Time 0.00
Received By kstevens Date 2006-04-19 Time 14:43 Sent To  
Notes
2006-04-19 00:00:00AS-BUILTS *** NO CHANGES FROM PREVIOUS
 REVISION.

Review Stop P PLUMBING
Rev No 6 Status F Date 2006-02-10 Cont ID  
Sent By kstevens Date 2006-02-10 Time 14:35 Rev Time 0.00
Received By kstevens Date 2006-02-10 Time 14:35 Sent To  
Notes
2006-02-10 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. IF THE DESIGN PROFESSIONAL IS AN
 ENGINEER LEGALLY REGISTERED UNDER THE
 LAWS OF THIS STATE REGULATING THE
 PRACTICE OF ENGINEERING, THEN HE/SHE
 SHALL AFFIX HIS/HER OFFICIAL SEAL TO
 SAID DRAWINGS AS REQUIRED BY FLORIDA
 STATUTES. SECTION 104.2.2.
 2.A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS
 PROVIDED TO THE OWNER AND BEING FILED
 FOR PUBLIC RECORD. THE DATE THAT THE
 SIGNATURE AND SEAL IS AFFIXED AS
 PROVIDED HEREIN SHALL BE ENTERED ON SAID
 PLANS. 61G15-23.002(1) AND FS 471.025.
 3. ONLY ONE SET OF PLANS HAS BEEN
 SIGNED, SEALED & DATED. PLEASE BE SURE
 BOTH SETS MEET THE ABOVE REQUIREMENTS.
 THE SIGNED, SEALED & DATED SET HAS BEEN
 APPROVED AND IS INSERTED INTO THE FILE
 SET. PLEASE PROVIDE THE SECOND SET FOR
 FIELD APPROVED REVISIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-09-10 Cont ID  
Sent By kstevens Date 2005-09-10 Time 09:06 Rev Time 0.52
Received By kstevens Date 2005-09-10 Time 09:05 Sent To B
Notes
2005-09-10 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SANT. RISER DIAGRAM SHEETS. DRAWINGS
 SHALL BE DRAWN WITH SUFFICIENT CLARITY
 AND DETAIL TO INDICATE THE NATURE AND
 CHARACTER OF THE WORK. REVISIONS ARE NOT
 CLEAR TO THE WORK BEING DONE. SECTION
 104.2.1.
 2. SANT. RISER DIAGRAM SHEETS SIGNED AND
 SEALED BY AN ARCHITECT (NOT ARCHITECT OF
 RECORD) WITHOUT A REQUIRED TITLE BLOCK.
 FAC 61G1-16.004 & FS 481.2055.
 3. SHT A-03 A CLEANOUT IS REQUIRED NEAR
 THE JUNCTION OF THE BUILDING DRAIN AND
 THE BUILDING SEWER. SECTION 708.3.5.
 4. SHT A-03 SHOWS WATER LINE REVISION.
 IF WATER LINES ARE CHANGED, A REVISION
 IS REQUIRED FOR THE WATER RISER DIAGRAM.
 SECTION 104.3.1.1.
 5. SHT A-03 THE PRINTED NAME OF THE
 ARCHITECT IS REQUIRED IN THE TITLE
 BLOCK. FAC 61G1-16.004(6) & FS 481.2055
 6. SHT A-03 INDICATES A 2" SS LINE DOWN
 FROM THE SECOND FLOOR. IF THIS IS A
 REVISION THAN IT SHALL BE REFLECTED ON
 THE SANITARY RISER DIAGRAM. SECTION
 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-04-25 Cont ID  
Sent By kstevens Date 2005-04-25 Time 17:39 Rev Time 0.50
Received By kstevens Date 2005-04-25 Time 17:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-01-11 Cont ID  
Sent By kstevens Date 2005-01-11 Time 06:42 Rev Time 0.75
Received By kstevens Date 2005-01-10 Time 19:23 Sent To  
Notes
2005-01-11 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT IRR-1 FAC 61G1-16.004 TITLE BLOCK
 INFORMATION STILL NOT SHOWN:
 (2) FIRM LICENSE NUMBER.
 (5) SPACE FOR THE SIGNATURE AND DATED
 SEAL. (NO DATE ON SEAL YET). FS481.2055
 AND FS 481.219.
 2) SHT IRR-1 SEAL IMPRESSION DOES NOT
 SHOW ANY INFORMATION. PLEASE RESEAL TO
 IMPRESS INFORMATION REQUIRED BY FAC
 61G1-16.001/002 & FS 481.2055.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-04 Cont ID  
Sent By kstevens Date 2004-11-04 Time 12:41 Rev Time 2.25
Received By kstevens Date 2004-11-04 Time 12:41 Sent To  
Notes
2004-11-04 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTE
  
  
 1) SHT IRR-1 FAC 61G1-16.004 THE TITLE
 BLOCK MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL. (NO DATE ON SEAL)
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 FS 481.2055
 --FROM PREVIOUS REVIEW:
 5) SHTS A-1.1, A-1.2, & A-5.2 SINKS IN
 THE BREAK ROOMS, (119) & 223), AND
 CONFERENCE ROOMS, (108 & 219), SHALL
 COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. STILL NOT SHOWN ARE THE
 KNEE CLEARANCE 11-4.24.3, SINK DEPTH
 11-4.24.4, CLEAR FLOOR SPACE (FORWARD
 APPROACH) 11-4.24.5, AND EXPOSED PIPES
 AND SURFACES 11-4.24.6.
 --FROM PREVIOUS REVIEW:
 11) SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAINS SHOWING COMPLIANCE WITH
 SECTION 11-4.15 AND ALL SUBSECTIONS.
 NOT
 SHOWN IS THE CLEAR FLOOR SPACE
 11-4.15.5
 (ARCHITECTURAL SHEETS REFER TO THE
 PLUMBING SHEETS, AND THE PLUMBING SHEETS
 REFER TO THE ARCHITECTURAL SHEETS -
 PLEASE CLARIFY)
 ALSO SHOW COMPLIANCE WITH SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO
 HAVE DIFFICULTY BENDING OR STOOPING. -
 THE ACCESSIBLE DRINKING FOUNTAIN SHALL
 BE 36 HIGH TO SPOUT MAXIMUM AND THE
 OTHER DRINKING SPOUT CAN BE AT REGULAR
 HEIGHT.
 --FROM PREVIOUS REVIEW:
 12) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ANDRESS AND LICENSE NUMBER
 ON EACH SHEET. FAC 61G15-23.002(2) AND
 FS471.025
 --NEW COMMENT:
 1B) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B)
 WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION
 AND
 REMOVE AND REPLACE ANY PAGES AS
 NECESSARY. SUBMIT (1) SET OF OLD
 DRAWINGS WITH THE PLANS WHEN
 RESUBMITTING PLANS. A TRANSMITTAL
 LISTING THE ORGINAL REVIEW NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPACIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND,
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPTATED COOPERATION.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-10 Cont ID  
Sent By kstevens Date 2004-07-10 Time 09:29 Rev Time 2.25
Received By kstevens Date 2004-07-10 Time 09:29 Sent To  
Notes
2004-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT IRR-1 SEAL IMPRESSION DOES NOT
 SHOW ANY INFORMATION. PLEASE RESEAL TO
 IMPRESS INFORMATION REQUIRED BY FAC 61G1
 -16.001/002 & FS 481.2055.
 2) SHT A-1.3 SUBMIT CALCULATIONS FOR THE
 FLAT ROOF PER SECTIONS 1106 & 1107 AND
 ALL SUBSECTIONS. SHOW AREA OF ROOF WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AND ROOF AREAS THAT DRAIN ONTO
 THE ROOF FROM ABOVE SHOWN IN CALCULAT-
 IONS,
 3) SHT A-1.3 COPPER SCUPPER DETAIL, IN-
 DICATE THE SIZE OF THE PIPE CONNECTED TO
 THE SCUPPER. SHOW PIPE SIZE FOR THE
 DOWNSPOUT. SECTION 1104.2.1
 4) SUBMIT A DETAIL FOR SECONDARY ROOF
 DRAIN. SHOW ALL PIPE SIZES, TERMINATION
 POINT, HEIGHT ABOVE ROOF SURFACE ECT.
 5) SHTS A-1.1, A-1.2, & A-5.2 SINKS IN
 THE BREAK ROOMS, (119 & 223), AND CON-
 FERENCE ROOMS, (202 & 219), SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS
 SHOW HEIGHT 4.24.2, KNEE CLEARANCE 4.24.
 3, DEPTH 4.24.4, CLEAR FLOOR SPACE 4.24.
 5, EXPOSED PIPES AND SURFACES 4.24.6.
 6) SHT A-7.2 FINISHED WALLS IN TOILET
 ROOMS CALL FOR WALL PAPER. THE WALLS AND
 FLOORS OF ALL PUBLIC REST ROOMS SHALL BE
 LINED WITH NONABSORBENT MATERIAL TO A
 HEIGHT OF 4 FT. ABOVE THE FLOOR. SECTION
 1204.S (BLDG) - PLEASE CLARIFY.
 7) SHTS P1.1 & P2.1 (SANT. RISER) MINI-
 MUM 2" PIPE UNDERGROUND. SECTION 710.3
 8) SHT P1.1 KEYED NOTES: 18 THRU 24,
 CONDENSATE SHALL DISCHARGE SEPARATELY
 FROM THE BUILDING AND TIE INTO STORM, A
 CATCH BASIN, OR DRYWELL. A RELIEF VENT,
 (GOOSENECK) SHALL BE INSTALLED AS THE
 CONDENSATE EXITS THE BUILDING. SECTION
 90-125(5) CITY CODE.
 9) SHT P2.1 WATER RISER DIAGRAM & KEY
 NOTES #4, WATER HAMMER ARRESTORS REQUIR-
 ED BY SECTION 604.9 SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 & MANUF. INSTALLATION INSTRUCTIONS.
 10) SHTS P2.1 & P7.1 AS SHOWN ON THE
 WATER RISER DIAGRAM, THE WATER HEATER
 DETAIL, AND NOTE #2, THE VALVE ON THE
 DRAIN LINE FOR THE EMERGENCY DRAIN PAN
 FOR THE WATER HEATER IS NOT APPROVED.
 DELETE VALVE AND REFERENCE TO VALVE.
 11) SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAINS SHOWING COMPLIANCE WITH SECT-
 ION 11-4.15 AND ALL SUBSECTIONS. SHOW
 SPOUT HEIGHT 4.1.2, AND CLEARANCES/CLEAR
 FLOOR SPACE 4.15.5.
 12) ADDRESS ON THE TITLE BLOCK IS NOT
 CORRECT. SEE ATTACHED SHEET.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-01-12 Cont ID  
Sent By aaponte Date 2005-01-12 Time 17:12 Rev Time 0.00
Received By aaponte Date 2005-01-12 Time 17:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2004-11-02 Time 1:12 Rev Time 0.00
Received By aaponte Date 2004-11-02 Time 11:46 Sent To  
Notes
2004-11-02 00:00:001.SIDEWALK ON QUADRILLE BOULEVARD SHALL
 BE A MINIMUM OF 8 FEET WIDE.
 2. STREET TREES SHALL BE PLANTED ON 5TH
 STREET ACCORDING WITH ART IV SEC 94-107
 (G)(2)
 3. PLEASE PROVIDE INFORMATION TO CONFIRM
 COMPLIANCE WITH PARKING REQUIREMENTS ON
 ART IV SEC 94-107 (D)(1).

Review Stop Z ZONING
Rev No 1 Status F Date 2004-08-04 Cont ID  
Sent By lmartine Date 2004-07-22 Time 13:23 Rev Time 0.00
Received By aaponte Date 2004-08-04 Time 10:11 Sent To  
Notes
2004-08-04 00:00:00BALCONIES ARE GOING OVER THE PROPERTY
 LINE. PURSUE AIR RIGHTS EASEMENT FROM
 CITY OR REVISE.
 -ARTICLE IV SECTION 94-107 (B)(1)
 MAXIMUM PERMITTED SETBACK IS 5'.
 BUILDING IS SETBACK 6'2" ON
 QUADRILLE BLVD. PLEASE REVISE OR PURSUE
 DAC VARIANCE.
 -ART. IV SECTION 94-107 (B)(4)
 STREET WALLS ON STREET FRONTAGE SHALL
 NOT EXCEED 4' IN HEIGHT.
 - ART. IV SECTION 94-107 (B)(7)
 PLEASE CONFIRM THAT SIDEWALKS ARE MIN
 8' WIDE ON SITE PLAN, ADJUST BUILDING
 SETBACK ACCORDINGLY.
 -ART. IV SECTION 94-107(G)(2)
 THREE SHADE TREES MUST BE PLANTED ALONG
 OLIVE AVE. AND QUADRILLE BLVD.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved