| Plan Review Stops For Permit 04061022 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2006-04-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-04-06 |
Time |
08:58 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2006-04-06 |
Time |
08:58 |
Sent To |
PC |
|
| Notes |
| 2006-04-06 00:00:00 | REVISION # 6 2-15-06 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2006-01-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-01-30 |
Time |
08:53 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2006-01-30 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2006-01-30 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04061022 | | | ADD: 605 N OLIVE AV | | | CONT: CATALFUMO CONSTRUCTION | | | TEL: (561)694-8818 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION REVIEW | | | ACTION: DENIED | | | | | | 1) SHEET A-1.1 OFFICE 110 SEE 11-4.13.6 | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 2) SHEET A-1.2 ROOMS 214 & 215 | | | SHEET -5.2 DETAIL# 1 | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 3)A 2.2 MISSING EXIT LIGHT IN HALLWAY | | | BEFORE STAIR ENCLOSURE# 1. | | | | | | 4) 1 SEET OF MEP IS MISSING THE ENGINEER | | | RAISED SEAL & SIGNATURE. | | | PLANS, SPECIFICATIONS,REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2005-06-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-06-10 |
Time |
08:03 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2005-06-10 |
Time |
08:03 |
Sent To |
PC |
|
| Notes |
| 2005-06-10 00:00:00 | | | | *** ISSUED PERMIT*** | | | -PLAN REVIEW HISTORY- | | | | | | PERMIT# 04061022 | | | ADDRESS: 605 N. OLIVE AV. | | | CONT: CATALFUMO | | | TELL # (561) 307-4836 | | | | | | THE ATTACHED COMMENTS ARE PART OF THE | | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | | | BUILDING PROVISO: | | | PLANS ARE MISSING THESE PRODUCT APPROVAL | | | OR FLORIDA COVER SHEET OR DO NOT MEET | | | THE WIND PRESSURES REQUIRED FOR THIS | | | STRUCTURE. WINDOWS & DOORSWILL REQUIRE | | | REVIEWED NOA'S BY THE BUCK INSPECTION | | | (119). | | | ROOFING APPROVALS BEFORE FIRST ROOF | | | ASSEMBLIES INSPRCTION (112 ROOF METAL / | | | TIN TAG) | | | | | | MISSING APPROVALS: | | | | | | A) DENS-GLASS GOLD SHEATHING- LOW | | | PRESSURE | | | | | | B) JOHNS MANVILLE PVC OVER CONCRETE | | | NO FL COVER SHEET/ NO SYSTEMS | | | HIGHLIGHTED, SEE LIMITATIONS 7 & 9 FOR | | | PRESSURES | | | | | | C) ROOF APPROVALS: ENGLERT SERIES 2000 | | | METAL PANEL OVER STEEL DECK LOW PRESURES | | | GOOD FOR -62.5 REQUIRED -81.5. SYSTEM | | | LIMITATION SEE # 1, FOR ENHANCED | | | FASTENING. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2005-04-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-04-11 |
Time |
07:40 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2005-04-11 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2005-04-11 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04061022 | | | ADD: 605 N OLIVE AV | | | CONT:CATALFUMO | | | TEL: (561)307-4836 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 4TH REVIEW | | | ACTION: DENIED | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2)COMMENT #3 FROM THE PREVIOUS REVIEW: | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) EXTERIOR DOORS REPORT SUBMITTED FOR | | | ALUMINIUM 35-H ONLY DOOR SCHEDULE | | | INDICATES EXT. DOOR #121 WOOD DOOR | | | DOOR # 123 HOLLOW METAL | | | B) DECRATIVE STORM SHUTTERSMISSING FL | | | COVERSHEET | | | C) ROOFING ASSEMBLIES, MODIFIED | | | BITUMEN SEE A-1.3 NO FL COVER SHEET, | | | | | | NO REPORT SUBMITTED | | | D) ROOFING ASSEMBLIES 2000 SEERIES ROOF | | | | | | PANEL SYSTEM NO FL COVERSHEET | | | E) PANEL WALL SYSTEMS: SOFFITS | | | PRE-MANUFACTERED SOFFIT SYSTEM NO | | | FL COVERSHEET NOR REPORT SEE A-4.5 | | | | | | 3) COMMENT # 3 FROM THE PREVIOUS | | | REVIEW:PROVIDE MORE INFORMATION, | | | THE ACCESSIBLE RAMP AND TOP LANDING. | | | THERE SEEMS TO BE A DISCREPANCY, THE | | | TOP OF THE RAMP IS AT ELEVATION 10.80 | | | DIRECTLY TO THE LEFT ABOUT 4'-0" AWAY | | | THE ELEVATION IS 11.20? | | | THERE WAS NO RESPONSE LETTER AND NO | | | CHANGE TO THE PLANS, SEE 11-4.3.7 CROSS | | | SLOPE FOR AN ACCESSIBLE ROUTE TO BE NOT | | | MORE THAN 1/50. THE ELEVATION CHANGE IN | | | 5'-0" IS APPROXIMATELY 2 1/2". | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-01-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-01-03 |
Time |
10:12 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2005-01-03 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2005-01-03 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04061022 | | | ADD: 605 N OLIVE AV | | | CONT:CATALFUMO | | | TEL: (561)307-4836 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RDREVIEW | | | ACTION: DENIED | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT | | | NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR | | | SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE | | | FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) COMMENT# 6 FROM THE PREVIOUS REVIEW, | | | FBC*102.2.7 ARCHITECTURAL TRIM, ON | | | BUILDINGS LOCATED IN THE FIRE DISTRICT, | | | SHALL BE CONSTRUCTED OF APPROVED NON- | | | COMBUSTIBLE MATERIALS OR FIRE RETARDANT | | | TREATED WOOD. | | | A) A-4.5 SEC. 1 FPR BRACKET | | | B) A-4.5 SEC. 2 POLYMER FPR BRACKET | | | PROVIDE DOCUMENTATION (TESTING TO ASTM | | | E-84 OR ASTM E 136) THAT THESE PRODUCTS | | | | | | MEET THE REQUIREMENTS OF | | | NON-COMBUSTIBLITY OR FIRE RETARDANT | | | TREATED WOOD. | | | | | | COMMENT # 8 FROM THE PREVIOUS REVIEW: | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) EXTERIOR DOORS | | | B) DECRATIVE STORM SHUTTERS | | | C) TRUSS ANCHOR SYSTEMS | | | D) ROOFING ASSEMBLIES, MODIFIED | | | BITUMEN | | | SEE A-1.3 | | | E) EFIS SYSTEMS SEE S-3 DETAIL # 7. | | | | | | 3) COMMENT # 7 FROM THE PREVIOUS | | | REVIEW: | | | PROVIDE MORE INFORMATION, | | | THE ACCESSIBLE RAMP AND TOP LANDING. | | | THERE SEEMS TO BE A DISCREPANCY, THE | | | TOP | | | OF THE RAMP IS AT ELEVATION 10.80 | | | DIRECTLY TO THE LEFT ABOUT 4'-0" AWAY | | | THE ELEVATION IS 11.20? | | | | | | 4) THERE SEEMS TO BE A DISCREPANCY | | | BETWEEN A-4.1, A-4.5 AND DETAIL 15 ON | | | PAGE A-6.1 AND THE ROOFING PRODUCT | | | APPROVALS AS TO WHERE THE INSULATION | | | WILL BE, AS TO WHAT TYPE OF NAILABLE | | | SHEATHING AND THE STANDING SEEM METAL | | | ROOF. | | | | | | 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-11-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-11-08 |
Time |
14:40 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2004-11-08 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2004-11-08 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04061022 | | | ADD:605 N OLIVE AV | | | CONT: CATALFUMO | | | TEL: (561)307-4836 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | 2NDREVIEW | | | ACTION:DENIED | | | | | | | | | 1)PROVIDE NOC RECORDED WITH THE | | | CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) COMMENT# 2 FROM THE PREVIOUS REVIEW: | | | FL BLD CODE 1804.2.2 QUESTIONABLE | | | SOILS, WHERE THE BEARING CAPACITY IS | | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | | WHERE THE BEARING CAPACITY OF THE SOIL | | | IS NOT DEFINITLY KNOWN OR IS IN | | | QUESTION | | | THE BUILDING OFFICIAL MAY REQUIRE | | | EXPLOR | | | ATIONS, TEST OR OTHER ADEQUATE PROOF AS | | | TO THE PERMISSIBLE SAFE BEARING | | | CAPACITY. REQUIRED TEST AND RECOMMENDA- | | | TIONS SUBMITTED TO VERIFY BEARING CAPA- | | | CITY SHALL BE CERTIFIED BY A GEOTECH- | | | NICALREPORT FROM A DESIGN PROFESSIONAL | | | PROPERLY LICENSED IN THE STATE OF | | | FLORIDA. | | | | | | 3) COMMENT# 4 FROM PREVIOUS REVIEW, | | | SHEET T-2 ACCESSIBILITY NOTES# 8, WHEN | | | THERE IS NO EDGE TREATMENT THE MAXIMUM | | | CHANGE IN GRADE IS 1/4"WHEN CHANGE IN | | | GRADE IS BETWEEN 1/4" AND 1/2" A BEVEL | | | MAY BE USED WITH THE SLOPE NO GREATER | | | THAN 1:2 (11-4.5.2).DO NOT LEAVE THE | | | QUESTION MARKS IN, FILL IN THE BLANKS! | | | | | | 4) COMMENT#5 FROM PREVIOUS REVIEW, | | | SHEET | | | T-2 ACCESSIBILITY NOTES: #9 CORRECT | | | HANDICAPPED PARKINGSPACE TO 12'-0" | | | 11-4.6.3. | | | | | | 5) COMMENT #6 FROM PREVIOUS REVIEW, | | | SHEET T-2 ACCESSIBILITY ROUTE IF PART OF | | | A MEANS OF EGRESS, 44" REQUIRED, ALSO | | | SEE (11-4.6.2(1) ALL PARKING SPACES MUST | | | BE LOCATED ON AN ACCESSIBLE ROUTE, NO | | | LESS THAN 44". | | | | | | 6) COMMENT# 8 FROM PREVIOUS REVIEW, | | | FBC* F102.2.7ARCHITECTURAL TRIM, ON | | | BUILDINGS LOCATED IN THE FIRE DISTRICT, | | | SHALL BE CONSTRUCTED OF APPROVED | | | NON-COMBUSTIBLE MATERIALS OR FIRE | | | RETARDANT TREATED WOOD.ANNOTATE THE | | | PLANS TO DEMONSTRATE COMPLIANCE. | | | A)A-4.5 .SEC.1 FAUX PECKY CYPRESS | | | B)A-4.5SEC.2 FIBER REINFORCED | | | POLYMER FPR BRACKETS | | | C)CEDAR FACIA | | | PROVIDE DOCUMENTATION THAT THESE | | | PRODUCTS WILL MEET THE REQUIREMENTS OF | | | NON-COMBUSTIBILITY OR FIRE RETARDANT | | | TREATED WOOD. | | | | | | 7) COMMENT# 10 RAMPS | | | A-1.1/A-3.1HANDRAILS, 11-4.8.5 IF A | | | RAMP | | | HAS A RISE GREATER THAN 6" OR A | | | HORIZONTAL PROJECTION GREATER THAN 72", | | | | | | OF STRAIGHT AND LEVEL CLEARENCE | | | HANDRAILSSHALL BE REQUIRED. | | | | | | | | | | | | 8) COMMENT# 14 FROM THE PREVIOUS REVIEW: | | | FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS | | | B) EXTERIOR DOORS | | | C) MULLIONS | | | D) STORM SHUTTERS | | | E) ROOFING ASSEMBLIES | | | F) TRUSS ANCHORS | | | G) EFIS SYSTEMS | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 9) COMMENT# 21 FROM THE PREVIOUS | | | REVIEW: | | | SHEET A-6.1 ROOFING DETAILS AND SHEET | | | S-3 INDICATE THE METAL STANDING SEAM | | | ROOFING ATTACHED DIRECTLY TO THE METAL | | | DECK, PROVIDE TESTING REPORT WITH THIS | | | TYPE OF TESTING. RESPONCE THE ROOFING IS | | | ACTUALLY FASTENED TO THE COMPOSTION | | | BOARD INSULATION. PROVIDE PRODUCT | | | TESTING! | | | | | | | | | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-07-19 |
Time |
14:54 |
Rev Time |
4.00 |
| Received By |
lmartine |
Date |
2004-07-19 |
Time |
14:54 |
Sent To |
Z |
|
| Notes |
| 2004-07-19 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04061022 | | | ADD: 605 N OLIVE AVE | | | CONT: CATALFUMO | | | TEL: (561)307-4836 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) FL BLD CODE 1804.2.2 QUESTIONABLE | | | SOILS, WHERE THE BEARING CAPACITY IS | | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | | WHERE THE BEARING CAPACITY OF THE SOIL | | | IS NOT DEFINITLY KNOWN OR IS IN QUESTION | | | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR | | | ATIONS, TEST OR OTHER ADEQUATE PROOF AS | | | TO THE PERMISSIBLE SAFE BEARING | | | CAPACITY. REQUIRED TEST AND RECOMMENDA- | | | TIONS SUBMITTED TO VERIFY BEARING CAPA- | | | CITY SHALL BE CERTIFIED BY A GEOTECH- | | | NICALREPORT FROM A DESIGN PROFESSIONAL | | | PROPERLY LICENSED IN THE STATE OF | | | FLORIDA. | | | | | | 3)FBC 13-103.1.2 BEFORE A BUILDING | | | PERMIT CAN BE ISSUED, THE SUBMITTED | | | ENERGY CODE COMPLIANCE FORMS SHALL BE | | | SIGNED BY THE BUILDING OWNER, THE | | | OWNER'S ARCHETECT OR OTHER AUTHORIZED | | | AGENT LEGALLY DESIGNATED BY THE OWNER. | | | | | | 4) SHEET T-2 ACCESSIBILITY NOTES: | | | #8 WHEN THERE IS NO EDGE TREATMENT THE | | | MAXIMUM CHANGE IN GRADE IS 1/4". WHEN | | | CHANGE IN GRADE BETWEEN 1/4" AND 1/2" | | | A BEVEL MAY BE USED WITH THE SLOPE NO | | | GREATER THAN 1:2(11-4.5.2) | | | | | | 5) SHEET T-2 ACCESSIBILITY NOTES: | | | #9 CORRECT WIDTH TO BE 12'-0" (11-4.6.3) | | | | | | 6) SHEET T-2 ACCESSIBILTY NOTES: | | | #4 ACCESSIBLE ROUTE IF PART OF A MEANS | | | OF EGRESS, 44" ALSO SEE (11-4.6.2(1) | | | ALL PARKING SPACES MUST BE LOCATED ON AN | | | ACCESSIBILE ROUTE NO LESS THAN 44". | | | | | | 7) CORRET SHEET A-0.1 HURRICANE CRITERIA | | | THE CITY OF WEST PALM BEACH IS NOT LOCA- | | | TED IN A HIGH VELOCITY HURRICANE ZONE. | | | | | | 8) F102.2.7 FIRE DISTRICT, STRUCTURE IS | | | LOCATED IN A FIRE DISTRICT.ARCHITECTURAL | | | TRIM ON BUILDINGS LOCATED IN THE FIRE | | | DISTRICT SHALL BE CONSTRUCTED OF APPROV- | | | ED NONCOMBUSTIBLE MATERIALS OR FIRE | | | RETARDANT TREATED WOOD. | | | SEE SHEET A-4.1 SECTION 2, FACTORY | | | HARD COATED FOAM "PECKY CYPRESS BEAMS". | | | SEE SHEET A-4.5 SECTIONS 1,2& 3 THE | | | FAUX PECKY CYPRESS BRACKETS. | | | | | | 9) SEE SHEET A-1.1/A-3.1 ATM RAMP IS | | | MISSING THE REQUIRED 5'-0" TOP LANDING. | | | 11-4.8.4.(2) LANDINGS. ALL LANDINGS | | | ON RAMPS SHALL NOT BE LESS THAN 60" | | | CLEAR, & THE BOTTOM OF EACH RAMP SHALL | | | HAVE NOT LESS THAN 72" OF STRAIGHT & | | | LEVEL CLEARENCE. | | | | | | 10)11.4.8.5. HANDRAILS: IF A RAMP HAS | | | A RISE GREATER THAN 6" OR A HORIZONTAL | | | PROJECTION GREATER THAN 72", THEN IT | | | SHALL HAVE HANDRAILS ON BOTH SIDES. | | | | | | 11) THIS SAME DETAIL, COLUMN AND BASE, | | | IS A MEANS OF EGRESS FOR THE ATM, | | | 11-4.3.3. IF A PERSON IN A WHEELCHAIR | | | MUST MAKE A TURN AROUND AN OBSTRUCTION, | | | THE MINIMUM CLEAR WIDTH OF THE ACCESS- | | | IBLE ROUTE SHALL BE AS SHOWN IN | | | FIGURE 7(A) AND (B). | | | | | | 12)S-3 DETAIL# 5, INDICATES THE USE | | | PLYWOOD SHEATHING, "FIRE DISTRICT" NO | | | TYPE VI CONSTRUCTION ALLOWED. PLANS | | | INDICATE TYPE V BUILDING. | | | | | | 13) A-01 BUILDING DATA INDICATES THIS | | | BUILDING WILL BE BOTH "1 HR PROTECTED" | | | AND "FIRE SPRINKLERED". NO INFORMATION | | | HAS BEEN PROVIDED, PLEASE SUBMIT. | | | | | | 14)FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS | | | B) EXTERIOR DOORS | | | C) MULLIONS | | | D) STORM SHUTTERS | | | E) ROOFING ASSEMBLIES | | | F) TRUSS ANCHORS | | | G) EFIS SYSTEMS | | | | | | 15) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 16) STURCTURAL PLANS DO NOT PROVIDE | | | THE WINDOW NOR DOOR BUCK ATTACHMENT. | | | 1606.4.4 ANCHOR METHODS. PROVIDE | | | INFORMATION FOR INSTALLATION OF DOOR | | | AND WINDOW BUCKS. | | | | | | 17) 1707.4.4.1 ANCHOR REQUIREMENTS: | | | WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR | | | ED IN ACCORDANCE WITH THE PUBLISHED | | | MANUFACTURER'S RECOMMENDATIONS TO | | | ACHIEVE THEDESIGN PRESSURE SPECIFIED. | | | SUBSTITUTE ANCHORING SYSTEM USED FOR | | | THE SUBSTRATE NOT SPECIFIED BY THE | | | FENESTRATION MANUFACTURER SHALL PROVIDE | | | EQUAL OR GREATER ANCHORING AS DEMONSTRA- | | | TED BY ACCEPTED ENGINEERING PRACTICES. | | | | | | 18)1707.4.4.2 TAPERED BUCKS: | | | SHALL EXTEND BEYOND THE INTERIOR FACE | | | OF THE WINDOW OR DOOR FRAME SUCH THAT | | | FULL SUPPORT OF THE FRAME IS SUPPORTED. | | | | | | 19) 1707.4.5.1 MULLIONS OCCURRING | | | BETWEEN INDIVIDUAL WINDOW AND GLASS | | | DOOR ASSEMBLIES. TESTING REPORTS ARE | | | REQUIRED BY AN APPROVED TESTING | | | LABORATORY OR BE ENGINEERED. | | | | | | 20) 1707.4.5.2 MULLIONS SHALL BE DESIGN- | | | ED TO TRANSFER THE DESIGN PRESSURE LOADS | | | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES | | | TO THE ROUGH OPENING SUBTRATE. | | | | | | 21) SHEET A-6.1 ROOFING DETAILS AND | | | SHEET S-3 INDICATE THE METAL STANDING | | | SEAM ROOFING ATTACHED DIRECTLY TO THE | | | METAL DECK, PROVIDE THE PRODUCT TESTING | | | REPORT WITH THIS TYPE OF TESTING. | | | | | | 22) S-3 DOOR AND WINDOW SCHEDULE HAS | | | NO IDENTIFYING MARKS? | | | | | | 23) ARCHITECTURAL & STRUCURAL BOTH INDIC | | | ATE THIS STRUCTURE IS DESIGNED AS A "C" | | | EXPOSURE, THE PRODUCT TESTING REPORTS | | | WILL REQUIRE THE HIGHER WIND PRESSURES | | | AS INDICATED IN THE WINDOW AND DOOR | | | SCHEDULE. | | | | | | 24)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2006-06-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-08 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-08 |
Time |
10:44 |
Sent To |
PC |
|
| Notes |
| 2006-06-08 00:00:00 | REVISION FOR ELECTRICAL, PLANS NOT | | | REVIEWED BY FIRE REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2006-03-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-27 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-27 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2006-01-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-01-09 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-01-09 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2006-01-09 00:00:00 | ***** UNSAT ***** | | | | | | 1)NOTE: PLEASE SEE ONLY ONE SET IS | | | SIGNED, DATED AND SEALED BY THE ENGINEER | | | OF RECORD. | | | PLEASE SEE FAC 61G15-23.002 WHICH | | | REQUIRES ALL SETS TO BE SIGNED, DATED | | | AND SEALED. | | | PLEASE ALSO SEE THE SAME FLORIDA | | | ADMINISTRATIVE CODE WHICH REQUIRES THE | | | PRINTED NAME AND LICENSE # FOR SAID | | | ENGINEER OF TITLE BLOCK. | | | | | | ** PLEASE KNOW THIS IS REQUIRED FOR ALL | | | TRADES AND FOR ALL REVIEWER(S) WHETHER | | | OR NOT COMMENT IS MADE BY OTHER | | | REVIEWER(S). | | | | | | 2)NOT: PLEASE VERIFY OCP FOR AHU'S, HEAT | | | ETC TO BE SIZEDA MIN OF 125% PER | | | 424.3B | | | PLEASE ADJUST. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2005-08-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-31 |
Time |
21:58 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-08-31 |
Time |
21:54 |
Sent To |
P |
|
| Notes |
| 2005-08-31 00:00:00 | ******** UNSAT ******* | | | | | | 1)NOTE: PLEASE SEE ANY REVISIONS TO | | | ELECTRICAL UNDER INSTALLATIONS OF | | | CONDUITS, MUST BE SUBMITTED SIGNED,DATED | | | AND SEALED BY THE ELECTRICAL ENGINEER OF | | | RECORD. | | | PLEASE ALSO SEE ALL PLANS/ DRAWINGS MUST | | | CONTAIN TITLE BLOCKS AS REQUIRED UNDER | | | FAC 61G15-23.002. | | | PLEASE SEE PLUMB REVIEW COMMENTS FOR | | | PLAN SUBMITTED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-12-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-12-27 |
Time |
13:06 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-12-27 |
Time |
13:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-10-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-10-19 |
Time |
16:57 |
Rev Time |
1.25 |
| Received By |
dpalmer |
Date |
2004-10-19 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2004-10-19 00:00:00 | ********** UNSAT 2ND REVIEW ************ | | | | | | PLEASE SEE SOME NOTES FROM FIRST REVIEW | | | STILL NEED TO BE ADDRESSED. | | | | | | 1)NOTE: NOTE#1 FROM PREVIOUS REVIEW. | | | REPLY LETTER MENTIONS ADDED TO TITLE | | | BLOCK, HOWEVER THIS COULD NOT BE LOCATED | | | PLEASE SEE FAC 61G15-23.002. | | | THIS IS REQUIRED ON ALL SHEETS AND FOR | | | ALL TRADES WHEATHER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWERS. | | | | | | 2)NOTE: NOTE#2 FROM PREVIOUS REVIEW. | | | LETTER MENTIONS REVISED/ADDED FIXTURE | | | TYPE ON E8.1, YET THIS WAS NOT FOUND. | | | | | | 3)NOTE: NOTE#5 FROM PREVIOUS REVIEW, | | | PLEASE SEE 230.82 FOR EQUIPMENT PERMITT- | | | -ED AHEAD OF MAIN. THIS IS NOT PERMITTED | | | IN NEC. | | | PLEASE ALSO SEE 230.72 | | | | | | 4)NOTE: NOTE#7 FROM PREVIOUS REVIEW. | | | PLEASE SEE 310.16,240.4 ETC. SOME MOTOR | | | ONLY LOADS (CU'S) ARE PERMITTED TO | | | PROTECT AT THE NEXT SIZE UP.HOWEVER, | | | AHU/HEAT ETC IS NOT, 424.3B ALONG W/ | | | ABOVE. | | | | | | PLEASE SEE COPY OF FS 553.80(2)(B) FOR | | | NOTICE ONLY GIVEN AT THIS TIME. | | | | | | PLEASE SEE POSSIBLE NOTES FROM OTHER | | | REVIEWERS WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-06-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-25 |
Time |
07:42 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2004-06-25 |
Time |
06:25 |
Sent To |
|
|
| Notes |
| 2004-06-25 00:00:00 | *********** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE FAC 61G15-23.002. | | | PLEASE INCLUDE ALL INFORMATION ON TITLE | | | BLOCK AS REQUIRED. | | | NAME AND LICENSE # OF ENGINEER. | | | | | | 2)NOTE: PLEASE SEE EXT LTS SHOWN AS X-1, | | | YET THIS TYPE OF FIXTURE DOES NOT SEEM | | | TO BE ON FIXTURE LEGEND? | | | | | | 3)NOTE: PLEASE SEE NOTE ON RISER MENTION | | | -S TO SEE DETAIL FOR GROUNDING ELECTRODE | | | SYSTEM ON E7.1. PLEASE SEE 250.50 FOR | | | REQUIRED COLD WATER, FOOTER STEEL ETC. | | | | | | 4)NOTE: PLEASE PROVIDE CALCS/INFORMATION | | | FOR WIND LOADING OF LT POLES/FIXTURES. | | | MUST MEET FBC 140 MPH. | | | | | | 5)NOTE: PLEASE SEE 230.82 FOR PERMITTED | | | EQUIPMENT TO CONNECTED AHEAD OF THE | | | MAIN. | | | PLEASE ALSO SEE MORE INFORMATION IS REQ- | | | -UIRED FOR ELEVATOR DISC. OCP ETC. | | | | | | 6)NOTE: PLEASE SEE 620.22 FOR REQUIRED | | | CIRCUITS. | | | PLEASE SEE WE ALSO COULD NOT LOCATE | | | REQUIRES LTS FOR ELEV. | | | | | | 7)NOTE: PLEASE CORRELATE OCP AND AWG | | | ON MDP PANEL SCHEDULE. | | | APPEARS TO SHOW SOME SIZEDOVER | | | RATING OF WIRE PER 310.16 | | | #12 W/ 70A OCP? #12 W/ 35A SOME COND/MOT | | | -OR LOADS ARE PERMITTED TO HAVE SIZE | | | ACCORDING TO NAMEPLATE. | | | | | | 8)NOTE: PLEASE SEE EQUIPMENT GROUNDING | | | CONDUCTORS ARE ONLY INSTALLED AFTER THE | | | FIRST MEANS OF DISC. 250.24,250.6 | | | | | | 9)NOTE: PLEASE CLARIFY TYPE OF CONDUCTOR | | | -S FOR FEEDERS ETC. THERE IS A NOTE | | | THAT MENTIONS, AL/ CU BUT THE ONLY ITEM | | | FOUND THAT INDICATE CU IS FOR BUS. | | | PLEASE SEE LOCAL AMENDMENST, NO ALUM | | | SMALLER THAN #2 310.2. 250.62 | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | WHICH MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT ONLY NEW SHEETS INTO TWO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2006-07-21 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-07-21 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-07-21 |
Time |
13:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2004-06-25 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-06-25 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2004-06-25 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2006-07-21 00:00:00 | PASSED.CHECKED ALL NOTES BY AMINI. ALL | | | NOTES ARE TAKEN CARE OF. 7-21-06. AS | | | BUILT DRAWING OF MAY 2006 LOOKS OK TOO. | | | 7/21/06--CLICKED THIS STOP IN | | | ERROR--RASIK | | 2004-06-25 00:00:00 | PASSED WITH PROVISOS: | | | 1. ALL OFF STREET PARKING STALLS MUST BE | | | PAINTED WITH DOUBLE 4" WIDE STRIPES, PER | | | CITY OF WEST PALM BEACH REQUIREMENTS. | | | 2. POLLUTION PREVENTION PLANS MUST BE | | | INSTALLED IN THE FIELD PROIR TO ANY | | | CONSTRUCTION ACTIVITIES. | | | 3. ANY WORK WITHIN PUBLIC R.O.W REQUIRES | | | A SEPARATE PERMIT FROM PUBLIC UTILITIES | | | AND ENGINEERING. 494-1086 WINDEL PALMER. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2006-04-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-04-11 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-04-11 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2006-04-11 00:00:00 | REVISION DATED 2/15/06 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2006-01-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-01-11 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-01-11 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2006-01-11 00:00:00 | REVISION DATED 12/01/05 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-01-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-01-05 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-01-05 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2005-01-05 00:00:00 | 1. DOORS 212,218,AND 115 SHALL BE | | | FIRE RATED. PLEASE REVISE DOOR | | | SCHEDULE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | BUREAU OF FIRE PREVENTION |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-10-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-10-20 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-10-20 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2004-10-20 00:00:00 | 1) ALL NEW STAIRS AND RAMPS REQUIRE | | | HANDRAILS ON BOTH SIDES. THIS INCLUDES | | | EXIT DISCHARGE LOCATIONS. | | | | | | 2) REQUIRED FIRE ALARM SYSTEM SHALL | | | BE UL LISTED FOR CENTRAL STATION | | | SERVICE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-06-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-06-23 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-06-23 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2004-06-23 00:00:00 | 1) ELECTRONIC SWITCHES, CHAIN AND LOCK | | | REQUIRED ON FIRE LINE BACKFLOW DEVICE. | | | | | | 2) ARE ANY HANDRAILS PLANNED FOR | | | STAIR TREADS AT THE EAST/NORTH ENTRY | | | PORTICO. | | | | | | 3) TACTILE SIGNAGE REQUIRED AT EXIT | | | DOOR LOCATIONS. | | | | | | 4) BUILDING ADDRESS REQUIRED ON PROPER | | | ELEVATION. A MINIMUM OF 6" HIGH NUMBERS | | | ARE REQUIRED. | | | | | | 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR HANDRAILS AND | | | GUARDRAILS. | | | | | | 6) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM INSTALLATION. | | | CONNECTION TO CITY MAIN MUST BE APPROVED | | | BY CITY UTILITIES PRIOR TO SUBMITTING | | | PLANS. | | | | | | 7) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM. THE FIRE ALARM | | | SYSTEM SHALL BE MONITORED BY A LICENSED | | | UL COMPANY APPROVED FOR CENTRAL STATION | | | SERVICE. | | | | | | 8) NO COMBUSTIBLES ALLOWED IN THE | | | RETURN AIR PLENUM. | | | | | | 9) ELEVATOR WARNING SIGNS REQUIRED AT | | | ELEVATOR ENTRANCES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2006-05-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-27 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-27 |
Time |
15:19 |
Sent To |
E |
|
| Notes |
| 2006-05-27 00:00:00 | TO "E" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2006-05-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-26 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-26 |
Time |
08:50 |
Sent To |
B |
|
| Notes |
| 2006-05-26 00:00:00 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-03-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-27 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-27 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2006-03-27 00:00:00 | TO COMM BOARD #17 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-03-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-02 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-02 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2006-03-02 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-12-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-10 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-10 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2006-01-05 00:00:00 | TO "COMM" BD#54 | | 2005-12-10 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-29 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-29 |
Time |
16:48 |
Sent To |
E |
|
| Notes |
| 2005-08-29 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-06-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-08 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-08 |
Time |
14:07 |
Sent To |
B |
|
| Notes |
| 2005-06-08 00:00:00 | TO JW DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-03-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-31 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-31 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2005-03-31 00:00:00 | TO "COMM" BD#62 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-01-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-07 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-07 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2005-01-07 00:00:00 | TO "COMM BD#17/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-12-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-13 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-13 |
Time |
08:29 |
Sent To |
|
|
| Notes |
| 2004-12-13 00:00:00 | SENT TO "COMM BD#43/RESUB." |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-08-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-08-04 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-22 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2004-06-22 00:00:00 | TO COMM BD#54 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
P |
Date |
2006-11-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-11-03 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-11-03 |
Time |
11:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2006-10-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-10-13 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-10-13 |
Time |
09:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
N |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-12 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-12 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2006-10-12 15:12:00 | TEST & BALANCE REPORT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2006-04-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-04-10 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-04-10 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2006-04-10 00:00:00 | PROVISO: | | | 1.EXHAUST SHALL NOT BE DIRECTED ONTO | | | WALKWAYS OR TERMINATE IN A MANNER THAT | | | CREATE A NUISANCE PER 2001 FMC 401.5.2. | | | | | | 2.PLAN SHEET M7.2 INDICATES AUXILIARY | | | DRAIN PAN ONLY REQUIRED FOR UNITS | | | LOCATED ABOVE THE CEILING.PER 2001 FMC | | | 307.2.3 & 307.2.4, AN AUXULAIRY DRAIN | | | PAN IS REQUIRED.THE FLOAT SWITCH SHALL | | | BE INSTALLED IN THE AUXILIARY DRAIN PAN. | | | PLEASE REVISE PLAN TO REFLECT THE | | | REQUIREMENT OF ONE OF THE THREE METHODS | | | DESCRIBED IN THE AFOREMENTIONED CODE | | | SECTIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2006-01-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-01-21 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-01-21 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2006-01-21 00:00:00 | DENIED: | | | PLEASE NOTE, ONLY ONE SET OF PLANS WERE | | | SIGNED, SEALED AND DATED BY THE | | | ENGINEER.TWO COMPLETE SETS ARE | | | REQUIRED IN ACCORDANCE WITH 2001 FBC | | | 104.2.1.PLANS ARE OTHERWISE CODE | | | COMPLIANT. | | | | | | PER FS 471.025 & FAC 61G15-23.002 (1) & | | | (2), ENGINEER IS REQUIRED TO SIGN, SEAL, | | | AND DATE PLANS, REPORTS AND | | | SPECIFICATIONS SUBMITTED FOR PUBLIC | | | RECORD.WHEN PRACTICING THROUGH A DULY | | | AUTHORIZED ENGINEERING FIRM SHALL | | | INDICATE THE CERTIFICATE OF | | | AUTHORIZATION ON THE PLANS. | | | | | | IF YOU HAVE ANY QUESTION, PLEASE CONTACT | | | PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-01-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-01-06 |
Time |
08:34 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-01-06 |
Time |
08:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2004-10-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-10-26 |
Time |
07:42 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-10-26 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2004-10-26 00:00:00 | DENIED: | | | 1.PLAN SHEETS M1.1, M7.2, ARE NOT | | | SIGNED & DATED BY THE ENGINEER.PLAN | | | SHEETS M1.2, M7.1, M8.1, M8.2, M9.1 ARE | | | NOT SIGNED,SEALED & DATED AS REQUIRED BY | | | FS 471.025 & FAC 61G15-23.001. | | | | | | 2.PLEASE NOTE, PLAN SHEET A-1.2 | | | THE LEGEND INDICATES WALL TYPES ON SHEET | | | A-0.2, THIS SHOULD READ A-7.1. | | | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-06-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-06-29 |
Time |
15:51 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2004-06-29 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2004-06-29 00:00:00 | DENIED: | | | 1.PLAN SHEET M1.1, FIRE DAMPERS | | | REQUIRED ON DUCTS PENETRATING OR | | | TERMINATING AT A RATED WALL PER 2001 | | | FBC(M) 607.1.2.DUCTS TERMINATING AT | | | THE ELEV MACHINE RM, STORAGE RM, & ATM | | | RM ARE REQUIRED TO HAVE FIRE DAMPERS. | | | | | | 2.PLAN SHEET M7.2 DETAIL 1 NOTE 4, | | | AUXILIARY DRAIN PAN SHALL HAVE OVERFLOW | | | PROTECTION BY MEANS OF A FLOAT SWITCH OR | | | AUXILIARY DRAIN LINE TERMINATING AT A | | | CONSPICUOUS POINT PER 2001 FBC(M) | | | 307.2.3.PLEASE INDICATE WHICH METHOD | | | WILL BE UTILIZED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2006-04-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-04-19 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-04-19 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2006-04-19 00:00:00 | AS-BUILTS *** NO CHANGES FROM PREVIOUS | | | REVISION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2006-02-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-02-10 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-02-10 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2006-02-10 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. IF THE DESIGN PROFESSIONAL IS AN | | | ENGINEER LEGALLY REGISTERED UNDER THE | | | LAWS OF THIS STATE REGULATING THE | | | PRACTICE OF ENGINEERING, THEN HE/SHE | | | SHALL AFFIX HIS/HER OFFICIAL SEAL TO | | | SAID DRAWINGS AS REQUIRED BY FLORIDA | | | STATUTES. SECTION 104.2.2. | | | 2.A PROFESSIONAL ENGINEER SHALL SIGN | | | HIS NAME AND AFFIX HIS SEAL TO ALL PLANS | | | PROVIDED TO THE OWNER AND BEING FILED | | | FOR PUBLIC RECORD. THE DATE THAT THE | | | SIGNATURE AND SEAL IS AFFIXED AS | | | PROVIDED HEREIN SHALL BE ENTERED ON SAID | | | PLANS. 61G15-23.002(1) AND FS 471.025. | | | 3. ONLY ONE SET OF PLANS HAS BEEN | | | SIGNED, SEALED & DATED. PLEASE BE SURE | | | BOTH SETS MEET THE ABOVE REQUIREMENTS. | | | THE SIGNED, SEALED & DATED SET HAS BEEN | | | APPROVED AND IS INSERTED INTO THE FILE | | | SET. PLEASE PROVIDE THE SECOND SET FOR | | | FIELD APPROVED REVISIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2005-09-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-09-10 |
Time |
09:06 |
Rev Time |
0.52 |
| Received By |
kstevens |
Date |
2005-09-10 |
Time |
09:05 |
Sent To |
B |
|
| Notes |
| 2005-09-10 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SANT. RISER DIAGRAM SHEETS. DRAWINGS | | | SHALL BE DRAWN WITH SUFFICIENT CLARITY | | | AND DETAIL TO INDICATE THE NATURE AND | | | CHARACTER OF THE WORK. REVISIONS ARE NOT | | | CLEAR TO THE WORK BEING DONE. SECTION | | | 104.2.1. | | | 2. SANT. RISER DIAGRAM SHEETS SIGNED AND | | | SEALED BY AN ARCHITECT (NOT ARCHITECT OF | | | RECORD) WITHOUT A REQUIRED TITLE BLOCK. | | | FAC 61G1-16.004 & FS 481.2055. | | | 3. SHT A-03 A CLEANOUT IS REQUIRED NEAR | | | THE JUNCTION OF THE BUILDING DRAIN AND | | | THE BUILDING SEWER. SECTION 708.3.5. | | | 4. SHT A-03 SHOWS WATER LINE REVISION. | | | IF WATER LINES ARE CHANGED, A REVISION | | | IS REQUIRED FOR THE WATER RISER DIAGRAM. | | | SECTION 104.3.1.1. | | | 5. SHT A-03 THE PRINTED NAME OF THE | | | ARCHITECT IS REQUIRED IN THE TITLE | | | BLOCK. FAC 61G1-16.004(6) & FS 481.2055 | | | 6. SHT A-03 INDICATES A 2" SS LINE DOWN | | | FROM THE SECOND FLOOR. IF THIS IS A | | | REVISION THAN IT SHALL BE REFLECTED ON | | | THE SANITARY RISER DIAGRAM. SECTION | | | 104.3.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-04-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-25 |
Time |
17:39 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-04-25 |
Time |
17:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-01-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-01-11 |
Time |
06:42 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2005-01-10 |
Time |
19:23 |
Sent To |
|
|
| Notes |
| 2005-01-11 00:00:00 | DENIED | | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHT IRR-1 FAC 61G1-16.004 TITLE BLOCK | | | INFORMATION STILL NOT SHOWN: | | | (2) FIRM LICENSE NUMBER. | | | (5) SPACE FOR THE SIGNATURE AND DATED | | | SEAL. (NO DATE ON SEAL YET). FS481.2055 | | | AND FS 481.219. | | | 2) SHT IRR-1 SEAL IMPRESSION DOES NOT | | | SHOW ANY INFORMATION. PLEASE RESEAL TO | | | IMPRESS INFORMATION REQUIRED BY FAC | | | 61G1-16.001/002 & FS 481.2055. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-11-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-04 |
Time |
12:41 |
Rev Time |
2.25 |
| Received By |
kstevens |
Date |
2004-11-04 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2004-11-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTE | | | | | | | | | 1) SHT IRR-1 FAC 61G1-16.004 THE TITLE | | | BLOCK MUST, AT A MINIMUM, CONTAIN THE | | | FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE | | | NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED | | | SEAL. (NO DATE ON SEAL) | | | (6) A SPACE FOR THE PRINTED NAME OF THE | | | PERSON SEALING THE DOCUMENT. | | | FS 481.2055 | | | --FROM PREVIOUS REVIEW: | | | 5) SHTS A-1.1, A-1.2, & A-5.2 SINKS IN | | | THE BREAK ROOMS, (119) & 223), AND | | | CONFERENCE ROOMS, (108 & 219), SHALL | | | COMPLY WITH SECTION 11-4.24 AND ALL | | | SUBSECTIONS. STILL NOT SHOWN ARE THE | | | KNEE CLEARANCE 11-4.24.3, SINK DEPTH | | | 11-4.24.4, CLEAR FLOOR SPACE (FORWARD | | | APPROACH) 11-4.24.5, AND EXPOSED PIPES | | | AND SURFACES 11-4.24.6. | | | --FROM PREVIOUS REVIEW: | | | 11) SUBMIT A DETAIL FOR THE DRINKING | | | FOUNTAINS SHOWING COMPLIANCE WITH | | | SECTION 11-4.15 AND ALL SUBSECTIONS. | | | NOT | | | SHOWN IS THE CLEAR FLOOR SPACE | | | 11-4.15.5 | | | (ARCHITECTURAL SHEETS REFER TO THE | | | PLUMBING SHEETS, AND THE PLUMBING SHEETS | | | REFER TO THE ARCHITECTURAL SHEETS - | | | PLEASE CLARIFY) | | | ALSO SHOW COMPLIANCE WITH SECTION | | | 11-4.1.3(10)(A) PROVISIONS FOR THOSE | | | WHO | | | HAVE DIFFICULTY BENDING OR STOOPING. - | | | THE ACCESSIBLE DRINKING FOUNTAIN SHALL | | | BE 36 HIGH TO SPOUT MAXIMUM AND THE | | | OTHER DRINKING SPOUT CAN BE AT REGULAR | | | HEIGHT. | | | --FROM PREVIOUS REVIEW: | | | 12) ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME, ANDRESS AND LICENSE NUMBER | | | ON EACH SHEET. FAC 61G15-23.002(2) AND | | | FS471.025 | | | --NEW COMMENT: | | | 1B) SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL AND FS 553.80(2)(B) | | | WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION | | | AND | | | REMOVE AND REPLACE ANY PAGES AS | | | NECESSARY. SUBMIT (1) SET OF OLD | | | DRAWINGS WITH THE PLANS WHEN | | | RESUBMITTING PLANS. A TRANSMITTAL | | | LISTING THE ORGINAL REVIEW NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPACIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND, | | | WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK | | | YOU FOR YOUR ANTICIPTATED COOPERATION. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-07-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-07-10 |
Time |
09:29 |
Rev Time |
2.25 |
| Received By |
kstevens |
Date |
2004-07-10 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2004-07-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHT IRR-1 SEAL IMPRESSION DOES NOT | | | SHOW ANY INFORMATION. PLEASE RESEAL TO | | | IMPRESS INFORMATION REQUIRED BY FAC 61G1 | | | -16.001/002 & FS 481.2055. | | | 2) SHT A-1.3 SUBMIT CALCULATIONS FOR THE | | | FLAT ROOF PER SECTIONS 1106 & 1107 AND | | | ALL SUBSECTIONS. SHOW AREA OF ROOF WITH | | | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING | | | PARAPETS AND ROOF AREAS THAT DRAIN ONTO | | | THE ROOF FROM ABOVE SHOWN IN CALCULAT- | | | IONS, | | | 3) SHT A-1.3 COPPER SCUPPER DETAIL, IN- | | | DICATE THE SIZE OF THE PIPE CONNECTED TO | | | THE SCUPPER. SHOW PIPE SIZE FOR THE | | | DOWNSPOUT. SECTION 1104.2.1 | | | 4) SUBMIT A DETAIL FOR SECONDARY ROOF | | | DRAIN. SHOW ALL PIPE SIZES, TERMINATION | | | POINT, HEIGHT ABOVE ROOF SURFACE ECT. | | | 5) SHTS A-1.1, A-1.2, & A-5.2 SINKS IN | | | THE BREAK ROOMS, (119 & 223), AND CON- | | | FERENCE ROOMS, (202 & 219), SHALL COMPLY | | | WITH SECTION 11-4.24 AND ALL SUBSECTIONS | | | SHOW HEIGHT 4.24.2, KNEE CLEARANCE 4.24. | | | 3, DEPTH 4.24.4, CLEAR FLOOR SPACE 4.24. | | | 5, EXPOSED PIPES AND SURFACES 4.24.6. | | | 6) SHT A-7.2 FINISHED WALLS IN TOILET | | | ROOMS CALL FOR WALL PAPER. THE WALLS AND | | | FLOORS OF ALL PUBLIC REST ROOMS SHALL BE | | | LINED WITH NONABSORBENT MATERIAL TO A | | | HEIGHT OF 4 FT. ABOVE THE FLOOR. SECTION | | | 1204.S (BLDG) - PLEASE CLARIFY. | | | 7) SHTS P1.1 & P2.1 (SANT. RISER) MINI- | | | MUM 2" PIPE UNDERGROUND. SECTION 710.3 | | | 8) SHT P1.1 KEYED NOTES: 18 THRU 24, | | | CONDENSATE SHALL DISCHARGE SEPARATELY | | | FROM THE BUILDING AND TIE INTO STORM, A | | | CATCH BASIN, OR DRYWELL. A RELIEF VENT, | | | (GOOSENECK) SHALL BE INSTALLED AS THE | | | CONDENSATE EXITS THE BUILDING. SECTION | | | 90-125(5) CITY CODE. | | | 9) SHT P2.1 WATER RISER DIAGRAM & KEY | | | NOTES #4, WATER HAMMER ARRESTORS REQUIR- | | | ED BY SECTION 604.9 SHALL BE LOCATED | | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | | NOT IN THE CEILING AS SHOWN. PDI-WH 201 | | | & MANUF. INSTALLATION INSTRUCTIONS. | | | 10) SHTS P2.1 & P7.1 AS SHOWN ON THE | | | WATER RISER DIAGRAM, THE WATER HEATER | | | DETAIL, AND NOTE #2, THE VALVE ON THE | | | DRAIN LINE FOR THE EMERGENCY DRAIN PAN | | | FOR THE WATER HEATER IS NOT APPROVED. | | | DELETE VALVE AND REFERENCE TO VALVE. | | | 11) SUBMIT A DETAIL FOR THE DRINKING | | | FOUNTAINS SHOWING COMPLIANCE WITH SECT- | | | ION 11-4.15 AND ALL SUBSECTIONS. SHOW | | | SPOUT HEIGHT 4.1.2, AND CLEARANCES/CLEAR | | | FLOOR SPACE 4.15.5. | | | 12) ADDRESS ON THE TITLE BLOCK IS NOT | | | CORRECT. SEE ATTACHED SHEET. | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. IF PRACTICING THROUGH A DULY | | | AUTHORIZED ENGINEERING BUSINESS, ENGIN- | | | EERS, ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME AND LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. A TITLE BLOCK | | | WILL SATISFY THIS REQUIREMENT. FAC | | | 61G15-23.002(2) - FS 471.025 | | | *********WHEN RESUBMITTING PLANS******** | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2005-01-12 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2005-01-12 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2005-01-12 |
Time |
17:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2004-11-02 |
Time |
1:12 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2004-11-02 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2004-11-02 00:00:00 | 1.SIDEWALK ON QUADRILLE BOULEVARD SHALL | | | BE A MINIMUM OF 8 FEET WIDE. | | | 2. STREET TREES SHALL BE PLANTED ON 5TH | | | STREET ACCORDING WITH ART IV SEC 94-107 | | | (G)(2) | | | 3. PLEASE PROVIDE INFORMATION TO CONFIRM | | | COMPLIANCE WITH PARKING REQUIREMENTS ON | | | ART IV SEC 94-107 (D)(1). |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-08-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2004-07-22 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2004-08-04 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2004-08-04 00:00:00 | BALCONIES ARE GOING OVER THE PROPERTY | | | LINE. PURSUE AIR RIGHTS EASEMENT FROM | | | CITY OR REVISE. | | | -ARTICLE IV SECTION 94-107 (B)(1) | | | MAXIMUM PERMITTED SETBACK IS 5'. | | | BUILDING IS SETBACK 6'2" ON | | | QUADRILLE BLVD. PLEASE REVISE OR PURSUE | | | DAC VARIANCE. | | | -ART. IV SECTION 94-107 (B)(4) | | | STREET WALLS ON STREET FRONTAGE SHALL | | | NOT EXCEED 4' IN HEIGHT. | | | - ART. IV SECTION 94-107 (B)(7) | | | PLEASE CONFIRM THAT SIDEWALKS ARE MIN | | | 8' WIDE ON SITE PLAN, ADJUST BUILDING | | | SETBACK ACCORDINGLY. | | | -ART. IV SECTION 94-107(G)(2) | | | THREE SHADE TREES MUST BE PLANTED ALONG | | | OLIVE AVE. AND QUADRILLE BLVD. |
|
|