Plan Review Details - Permit 04060944
Plan Review Stops For Permit 04060944
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-10-21 Cont ID  
Sent By alange Date 2004-10-21 Time 13:22 Rev Time 1.00
Received By alange Date 2004-10-21 Time 13:22 Sent To  
Notes
2004-10-21 00:00:00REVISION OF PAGES C1 AND C-2 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:34 Rev Time 0.50
Received By shill Date 2004-08-24 Time 14:49 Sent To  
Notes
2004-08-24 00:00:00REVISED A2 AND C2 DATED 8/23/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-08-02 Cont ID  
Sent By csiegber Date 2004-08-24 Time 09:40 Rev Time 1.50
Received By alange Date 2004-08-02 Time 09:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-02 Cont ID  
Sent By jleech Date 2004-07-31 Time 14:23 Rev Time 3.75
Received By alange Date 2004-07-02 Time 10:43 Sent To  
Notes
2004-07-02 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUATION HAS BEEN ADJUSTED TO
 $469,619.ADDITIONAL PERMIT FES ARE DUE
  
 3.SMOKE DETECTORS ARE REQUIRED IN BOTH
 MAIN HOUSE AND GUEST COTTAGE. SEE
 ELECTRICAL REVIEW NOTES.
  
 4.PRODUCT APPROVAL MISSING FOR
 PLYCRAFT GARAGE DOORS.SUBMIT 2 COPIES.
 ALSO PLYCRAFT NOT LISTED ON DCA
 PRODUCT APPROVAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5. SUBMIT SECOND FLOOR RAILING DETAIL.
 1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT
 WILLREJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 6.SHOW LOCATION AND SIZE OF ATTIC
 ACCESS COPLYING WITH FBC 2309.6.
  
 7.TRUSS PLANS NOT REQUIRED FOR REVIEW.
 PLEASE REMOVE FROM PLAN PACKAGE.
  
 8.PAGE A6 IS 16TH" SCALE. WPB
 AMMENDMENTS TO THE FBC SEC104.2.1.3
 MIN 1/8" SCALE REQUIRED.
  
 9.SUBMIT PRODUCT APPROVAL FOR SIMPSON
 STRAPS AND SHOW SCHEDULE ON PLAN.
  
 10.SECOND FLOOR DOOR ON GUEST COTTAGE
 TO STAIRS SHALL COMPLY WITH 1012.1.3#3
  
 11.PLEASE SUBMIT 2ND COPY OF SOIL
 REPORT.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
2004-06-22 00:00:00MUST PULL A SEPARATE PERMIT FOR POOL.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-11-07 Cont ID  
Sent By dpalmer Date 2007-11-07 Time 11:21 Rev Time 0.00
Received By dpalmer Date 2007-11-07 Time 10:28 Sent To PC
Notes
2007-11-07 11:21:28REVISION

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-10-29 Cont ID  
Sent By dpalmer Date 2007-10-29 Time 08:40 Rev Time 0.00
Received By dpalmer Date 2007-10-29 Time 08:39 Sent To PC
Notes
2007-10-29 08:44:05** DENIED REVISION**
  
 1) NOTE: PLEASE SEE THAT THE DESIGNER OF RECORD IS NOT
 THE SAME AS SUBMITTED ON THE REVISED ELECTRICALPLANS.
 PLEASE SUBMIT DOCUMENTION IF THE DESIGNER OF RECORD FOR
 ELECTRICAL IS CHANGING. PLEASE SEE THE FLORIDA
 ADMINISTRATIVE CODE 61G15 FOR HOW DESIGNERS OF RECORD
 ARE CHANGED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-15 Cont ID  
Sent By dpalmer Date 2007-09-15 Time 09:21 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 08:52 Sent To PC
Notes
2007-09-15 09:22:23 
 ** DENIEDREVISIONS**
  
 ** PLEASE SEE NOTES BELOW. ELECTRICAL RISER HAS NOW
 BEEN COMPLETELY REVISED.
  
 1) NOTE: PLEASE SEE RISER NOW INDICATES THE POOL PANEL
 AND THE CABANA PANEL BEING TAPPED FROM EACH OF THE TWO
 200AMP MAIN DISCONNECTS HOWEVER THE PANEL SCHEDULE FOR
 THE METER MAIN INDICATES ONE OF THESE PANELS FROM THAT
 PANEL.
 PLEASE SEE ORIGINAL RISER HAD BOTH OF THESE PANELS FROM
 THE METER MAIN.
 PLEASE SEE THE RISER CONDUCTORS/FEEDERS TO POOL PANEL
 ARE NOT THE SAME AS SCHEDULE.
 PLEASE SUBMIT PLANS SHOWING ALL LOCATIONS FOR EQUIPMENT
 AND PANELS. (UNABLE TO VERIFY TAPPED CONDUCTORS IF
 THESE PANELS ARE ACTUALLY BEING TAPPED FROM THESE
 MAINS)
 PLEASE SEE 240.21 FOR TAPPED CONDUCTOR RULES AS EACH OF
 THESE PANELS WOULD REQUIRE MAINS AND OVER CURRENT
 PROTECTION.
 240.21, 240.4, 310.16, 408.4 ETC
 FBC 104.1.2 (2001)
  
 2) NOTE: PLEASE SEE PREVIOUS REDLINED PLANS FROM JULY
 04 WHICH WAS NEVER CORRECTED OR REVISED.
 PLEASE SEE THE REVIEW REDLINES AT THAT TIME IS
 ATTACHED.
 THE MDP PANEL SCHEDULE WAS MISSING THE CABANA PANEL
 LISTED. 408.4
 THE UPSTAIRS CABANA BATH WAS MISSING.210.52D, 210.11C3
 PLEASE SEE THE LOAD CALCULATIONS WERE NEVER CORRECTED
 AS THE 1ST 10KW IS STILL BEING SHOWN AS A/C HEAT WHICH
 IS NOT CORRECT. PLEASE SEE 220.31
 ** PLEASE SUBMIT COMPLETE ELECTRICAL PLANS INCLUDING
 CABANA.
  
 3) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM AT
 THE MAIN HOUSE IS NO LONGER COMPLETE PER 250.32,
 250.50.
  
 4) NOTE: PLEASE SEE THE PANEL SCHEDULES ARE REQUIRED TO
 BE UPDATED PER 408.4. THE ITEMS AS SHOWN ARE THE SAME
 FROM THE 04 PLANS WHICH IS NOT CORRECT.
 PLEASE ALSO SEE THAT ALL ROOMS AND AREAS ON PANEL
 SCHEDULE ARE TO BE SPECIFIC.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM
 THE CODE COMMENTARY UNDER 408.4.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 104.1.2
  
 5) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE
 SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS
 SMOKE DETECTORS.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS AHJ HAS PERMITTED THE GENERAL USE OF THE SD FOR
 SMOKE DETECTORS AND WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 8-1.4.1.6.2 1999 AS PERMITTED.
  
 6) NOTE: PLEASE BE SURE THE ADOPTED CODES AT THE TIME
 OF PERMIT APPLICATION IS STATED ON PLANS.
 2001 FBC, 2002 NFPA-70 (NEC), 1999 NFPA-72
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-28 Cont ID  
Sent By dpalmer Date 2004-07-28 Time 18:29 Rev Time 0.50
Received By dpalmer Date 2004-07-28 Time 18:29 Sent To P
Notes
2004-07-28 00:00:00*** REDLINED ***
  
 CABANA NOT LABELED IN MDP SCHEDULE.
  
 RECEPT MISSING CABANA BATH RM. 2ND FLR
 210.11C3,210.52D
  
 LOAD CALCS, 1ST 10KW MISPRINT A/C/HEAT.
  
 REDLINED, STAMPED OK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-07-21 Time 16:08 Rev Time 1.50
Received By dpalmer Date 2004-06-23 Time 17:21 Sent To M
Notes
2004-06-23 00:00:00*********** UNSAT *****************
  
 ** PLEASE SEE PLANS ARE NOT COMPLETE AT
 THIS TIME FOR A COMPLETE REVIEW OF 2002
 NEC CODE COMPLIANCE.**
 THE FOLLOWING IS ONLY NOTES FOR WHAT IS
 SHOWN AT THIS TIME.
  
 1)NOTE: PLEASE SEE RISER DIAGRAM NEEDS
 TO BE COMPLETED.
 PLEASE SHOW WHAT IS FEEDING DETACHED
 BLDG.? PLEASE SEE MISSING CONDUCTORS
 FROM METER TO MAINS AND FROM PANEL 'B'
 TO PANEL 'C'.
  
 2)NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM PER 250.50
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE ALSO SEE DETACHED BLDG.
  
 5) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 6 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
 DETACHED BLDG.
  
 7)NOTE: PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 8)NOTE: PLEASE ALSO SEE PLANS MISSING
 SHOWING A/C UNITS AND DISC'S PER 440.11
 DETACHED BLDG MISSING SAME.
 210.70
  
 9)NOTE: PLEASE SEE MISSING CONTROL OF
 LTS AT DETACHED BLDG AND SECURITY LTS.
  
 10)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 11)NOTE: PLEASE SEE 225.31 FOR MEANS
 OF DISCONNECT AT DETACHED BLDGS.
  
 12)NOTE: PLEASE GROUNDING SYSTEM AT
 DEATCHED BLDG. PER 250.32
  
 13)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 14)NOTE: PLEASE ALSO SEE SOME AREAS ARE
 SHOWING A J-BOX WHERE A LT FIXTURE OF
 SOME SORT IS REQUIRED FOR EGRESS LIGHT-
 -ING. 210.70, LS 101 5-8
  
 15)NOTE:PLEASE SEE OCP SHOWN FOR 12KW
 RANGE/COOKTOP. SHOWN AT 40A??
  
 16)NOTE: PLEASE SEE MISSING RECEPTS
 IN CABANA BATHS. 210.52D,210.11C3
  
 17)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 SHOWING ALL MIN REQUIRED DEDICATED
 CIRCUITS, TEC PER NEC 2002
 PLEASE ALSO INDICATE AWG, AND OCP FOR
 BRANCH CIRCUITS.
  
 18)NOTE: PLEASE INCLUDE ALL LICENSE
 #'S ON TITLE BLOCK AS REQUIRED PER
 FS 481.219/ FAC 61G1-16.004
 THIS COMMENT IS FOR ARCH'S FIRM.
 THIS COMMENT IS FOR ALL TRADES AND SHEET
 -S WHEATHER PR NOT COMMENT IS MADE BY
 OTHER REVIEWERS.
  
 19)NOTE: PLEASE SEE LEGEND, SYMBOL SHOWN
 FOR J-BOX IS NOT DETAILED AS A "FAN BOX"
 , PLANS MENTION FAN/LT IN SOME LOCATIONS
 FOR THE SAME SYMBOL. PLEASE CORRELATE.
  
 PLEASE NOTE: DUE TO THE FACT OF PLANS
 NOT BEING COMPLETE AT THIS TIME, THERE
 MAY BE OTHER COMMENTS ON NEXT REVIEW.
 PLEASE ADDRESS THE ABOVE COMMENTS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 14:34 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 14:34 Sent To E
Notes
2007-11-06 14:35:11TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-26 Cont ID  
Sent By adarroug Date 2007-10-26 Time 08:39 Rev Time 0.00
Received By adarroug Date 2007-10-26 Time 08:39 Sent To E
Notes
2007-10-26 08:39:29TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 15:19 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 15:19 Sent To E
Notes
2007-09-13 15:19:56TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-17 Cont ID  
Sent By adarroug Date 2006-05-17 Time 14:28 Rev Time 0.00
Received By adarroug Date 2006-05-17 Time 14:28 Sent To P
Notes
2006-05-17 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:34 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:34 Sent To B
Notes
2004-10-05 00:00:00TO AL DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 09:40 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 09:40 Sent To B
Notes
2004-08-24 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 16:08 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 16:08 Sent To E
Notes
2004-07-21 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-02 Cont ID  
Sent By mmclean Date 2004-06-22 Time 15:13 Rev Time 0.00
Received By alange Date 2004-06-21 Time 09:47 Sent To  
Notes
2004-06-23 00:00:00TO SFD RACK/E
2004-06-21 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-07 Cont ID  
Sent By hmoser Date 2006-06-07 Time 15:33 Rev Time 0.00
Received By hmoser Date 2006-06-07 Time 15:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-25 Cont ID  
Sent By dpalmer Date 2004-06-23 Time 18:16 Rev Time 0.35
Received By pkrauss Date 2004-06-24 Time 14:41 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pschmitz Date 2006-05-22 Time 14:16 Sent To  
Notes
2006-05-22 00:00:00REVISION:
 2-2" ROOF DRAINS PRIMARY,AS REQUIRED.
 AND SECONDARY DRAINS, 2 SUPPERS DRAINS
 4" X 8"
 FBC 2004 SEC 1107 SECONDARY DRAINAGE
 REQUIRED.
 SEC 1107.2 SEPERATE SYSTEM REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-31 Cont ID  
Sent By jleech Date 2004-07-31 Time 14:23 Rev Time 0.33
Received By jleech Date 2004-07-31 Time 14:23 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-28 Cont ID  
Sent By dpalmer Date 2004-07-28 Time 18:29 Rev Time 0.50
Received By jleech Date 2004-06-28 Time 18:46 Sent To B
Notes
2004-06-28 00:00:00SEE ELECTRICAL PLAN REVIEW NOTE #18.

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-22 Cont ID  
Sent By mmclean Date 2004-06-22 Time 15:13 Rev Time 0.00
Received By mmclean Date 2004-06-22 Time 15:13 Sent To I
Notes
***NONE***