Plan Review Details - Permit 04060867
Plan Review Stops For Permit 04060867
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-11-30 Cont ID  
Sent By shill Date 2005-11-30 Time 13:59 Rev Time 0.50
Received By shill Date 2005-11-30 Time 13:59 Sent To PC
Notes
2005-11-30 00:00:00REVISION - CHANGE WINDOWS

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-08-11 Cont ID  
Sent By shill Date 2005-08-11 Time 09:40 Rev Time 0.00
Received By shill Date 2005-08-11 Time 09:40 Sent To  
Notes
2005-08-11 00:00:00TRUSS ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-05-12 Cont ID  
Sent By shill Date 2005-05-12 Time 18:42 Rev Time 0.00
Received By shill Date 2005-05-12 Time 18:42 Sent To  
Notes
2005-05-12 00:00:00LETTER FROM SCHUMATE, PE REGARDING WALL
 3/25/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-04-04 Cont ID  
Sent By shill Date 2005-04-04 Time 14:57 Rev Time 0.00
Received By shill Date 2005-04-04 Time 14:57 Sent To  
Notes
2005-04-04 00:00:00HOLLOW CORE ENGINEERING, SEE 04060859

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-28 Cont ID  
Sent By shill Date 2005-03-28 Time 15:08 Rev Time 2.00
Received By shill Date 2005-03-21 Time 12:46 Sent To  
Notes
2005-03-28 00:00:00PROVISO
  
 AT RISK PERMIT, SEE LETTER
  
 THE DECLARATION OF COVENANTS AND
 RESTRICTIONS TO BE AMENDED AS AGREED
 WITH THE BUILDING OFFICIAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-03-07 Cont ID  
Sent By shill Date 2005-03-07 Time 08:56 Rev Time 2.00
Received By shill Date 2005-03-07 Time 08:56 Sent To PC
Notes
2005-03-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #10.A
 PLAN FOR THE EXISTING WALL CONSTRUCTION,
 CALCULATIONS AND A LETTER FROM THE
 WALL'S PREVIOUS ENGINEER WAS INCLUDED IN
 THE PACKAGE.EOR OR DOR IS TO REVIEW
 THIS ENGINEERING AND CERTIFY THAT THE
 EXISTING WALL CAN ACCOMODATE ALL LOADS
 IMPOSED BY THE PROPOSED CONSTRUCTION TO
 BE BUILT ON TOP OF THIS WALL.
  
 2.)THE SOILS REPORT GIVES A BEARING
 CAPACITY OF 2500PSF, WALL REQUIREMENT AS
 PER PLAN SUBMITTED IS 3000PSF.ADDRESS.
  
 3.)THE WALL AS BUILT WALL-05 IN
 STRUCTURAL NOTE 3 STATES THAT THE
 TOWNHOUSES ARE TO BE 4' MIN FROM THE
 WALL.THIS CONFLICTS WITH THE TOWNHOUSE
 DESIGN.
  
 4.)SEE SECTIONS C1 THROUGH C5,
 WALL-05.THE WALL ENCROACHES PROPERTY
 LINE.ADDRESS.
  
 5.)THE CALCS SUBMITTED ADDRESS WALL
 SECTIONS C1&C2, C4, C6, AND T11.
 PROVIDE CALCS FOR ALL SECTIONS OF THE
 WALL AFFECTED.
  
 6.)SEPARATE PERMIT REQUIRED FOR THE
 ROOF.THE MEAN ROOF HEIGHT EXCEED THE
 PRODUCT APPROVAL LIMITATION OF 33'.
  
 7.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED (OVER 90 DAYS WITHOUT COMMENCING
 WORK), FS713.13.
  
 8.)THE STRUCTURAL SHEETS REFER TO A
 NONEXISTENT BUILDING CODE, SEE BOTTOM
 RIGHT CORNER (FLORIDA STANDARD BUILDING
 CODE) AND MAY REFER TO THE INCORRECT
 WIND ZONE (130 RATHER THAN 140, SEE
 S2.3).REVISE AND SUBMIT REVISIONS FOR
 THE BUILDINGS ALREADY ISSUED.
  
 AFTER THE ABOVE ISSUES HAVE BEEN
 RESOLVED,THIS PERMIT WILL BE ISSUED WITH
 THE FOLLOWING PROVISOS:
  
 THIS IS AN AT-RISK PERMIT, SEE LETTER.
  
 THE DECLARATION OF COVENANTS AND
 RESTRICTIONS TO BE AMENDED AS AGREED
 WITH THE BUILDING OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-01-26 Cont ID  
Sent By shill Date 2005-01-26 Time 14:03 Rev Time 0.00
Received By shill Date 2005-03-07 Time 08:54 Sent To  
Notes
2005-01-26 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 COMMENTS APPLY TO 04060867, 04060868
 04060856, 04060855, 04060842, 04060786,
 04060869, 04060871, 04060873
  
 COMMENTS 1, 2, 4,5,7 AND 12 APPLY TO
 04060880, 04060882
  
 COMMENTS 1, 2, 4, 5, 6 AND 12 APPLY TO
 04060876, 04060877
  
 1.)SUBCONTRACTORS HAVE SIGNED ONTO
 THE
 PERMIT SUBSEQUENT TO PERMIT INTAKE.
 PLEASE COORDINATE ASSIGNING OF THE
 SUBCONTRACTORS AND SUB PERMIT
 NUMBERS WITH DEAN RUNNELS, 805-6681 TO
 AVOID DELAYS AT TIME OF ISSUANCE.NOTE
 THAT AT THIS TIME THE ROOF PERMIT
 CANNOT BE ISSUED BECAUSE THE PRODUCT
 APPROVALS SUBMITTED ARE NOT COMPLIANT
 WITH THE PLAN (LIMITATION OF 33'.
  
 2.)THE FOOTINGS AND PORCH CANNOT
 ENCROACH THE PROPERTY LINE.
  
 3.)THE EXISTING RETAINING WALL CANNOT
 BE USED AS THE EXTERIOR BEARING WALL AS
 PER BUILDING OFFICIAL.
  
 4.)2-A6, THE STAIR RAIL SERVES AS A
 GUARDRAIL AND IS REQUIRED TO BE A
 MINIMUM OF 36" FBC1015.
  
 5.)B-A7 HAS BEEN REPLACED BY AN 8 1/2
 X 14 DETAIL; PLEASE CROSS OFF THE
 NONCOMPLIANT DETAIL WHICH IS STILL ON
 THE PLAN.
  
 6.)REGARDING THE ENGINEER'S LETTER
 FOR
 THE ROOF SHINGLES, PURSUANT TO FAC9B-72
 A FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL IS REQUIRED.SUBMIT AN
 APPLICATION AS REQUESTED WITH
 APPROPRIATE ENGINEERING.SUBJECT TO
 APPROVAL BY ASSISTANT BUILDING
 OFFICIAL.THE LETTER PREPARED BY DAVID
 SHUMATE, PE DATED 12/16/04 STATING THE
 DESIGN PRESSURE OF THE SHINGLES AND THE
 DP OF THE JOB DOES NOT PROVIDE ENOUGH
 DATA FOR ISSUANCE OF LOCAL PRODUCT
 APPROVAL (CONFIRMED WITH BUILDING
 OFFICIAL).ALSO NOTE THAT THE LETTER
 REFERS TO A MEAN ROOF HEIGHT OF 34',
 BUT
 BUILDING 8 HAS A MEAN ROOF HEIGHT OF
 34'4"+.
  
 LOCAL PRODUCT APPROVAL CAN BE REVIEWED
 AND ISSUED SEPARATELY FROM THE
 RESUBMITTAL PROCESS.
  
 7.)3-A4 (NEW DETAIL )REFERS TO
 UBC1988
 WHICH IS NOT THE APPLICABLE BUILDING
 CODE.PROVIDE EITHER AN APPROVED
 ASSEMBLY LISTING OR CALCULATED FIRE
 RESISTANCE, FBC CHAPTER 7.
  
 8.)THE REVISION TO PERMIT #01091727
 (THE EXISTING RETAINING WALL) CONTAINS
 A LETTER FROM JENKINS & CHARLAND DATED
 10/9/01 IN REGARDS TO THE REDESIGN OF
 THE RETAINING WALL TO BE USED ALSO AS
 THE EXTERIOR BEARING WALL OF THE
 TOWNHOUSES.PROVIDE THE ORIGINAL
 SEALED
 CALCULATIONS REFERRED TO IN THAT
 LETTER.
 ALL DELEGATED ENGINEERING IS TO BE
 REVIEWED BY EOR.
  
 9.)WEEPHOLES WERE PLACED IN THE
 EXISTING WALL AVOIDING THE TOWNHOUSE
 LOCATIONS, BUT THE TOWNHOUSES WERE
 REPLATTED, CHANGING THE TOWNHOUSE
 LOCATIONS.ADDRESS. SEE RFI WALL 0060
 11/9/01, RFI WALL-0001 7/27/2001 IN THE
 REVISION.
  
 10.) INCORPORATE THE ACTUAL EXISTING
 WALL CONSTRUCTION DETAIL INTO THE PLAN.
 THERE IS A REFERENCE TO THE FOUNDATION
 PLAN 1-A%, WHICH REFERS TO SECTIONS 1
 AND 2 S2.4, WHICH STATE "EXISTING - SEE
 PLAN."
  
 11.)THE EXISTING WALL CONSTRUCTION
 PLANS SHOW ELEVATION CHANGES.IT
 APPEARS THAT THERE MAY BE ELEVATION
 CHANGES IN THE MIDDLE OF THE PROPOSED
 TOWNHOUSE WALLS.HOW DO THE CONTROL
 JOINTS AND ELEVATION CHANGES OF THE
 WALL AFFECT THE TOWNHOUSE STRUCTURE?
  
 12.)A LETTER WAS SUBMITTED IN
 RESPONSE
 TO A PREVIOUS COMMENT IN REGARDS TO
 SHOWING THE ABILITY OF THE HOLLOW CORE
 TO CARRY THE LINE LOAD OF THE BLOCK
 WALLS.PLEASE HAVE THE RESPONSE LETTER
 DATED 12/20/04 PREPARED BY BRADLEY
 CASH, PE (PCSI) SUBMITTED IN ORIGINAL
 FORM, SIGNED AND SEALED FAC61G15-23.002
 INCLUDING PRINTED LICENSE NUMBER.ALSO
 PLEASE ADDRESS THE WEIGHT OF BEAMS, ETC.
 IN THE CALCS AS DISCUSSED WITH BRADLEY
 CASH, PE OF PCSI.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-12-13 Cont ID  
Sent By shill Date 2004-12-13 Time 17:07 Rev Time 2.00
Received By shill Date 2004-12-13 Time 17:07 Sent To PC
Notes
2004-12-13 00:00:00SEE 04060856

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-23 Cont ID  
Sent By shill Date 2004-07-23 Time 17:26 Rev Time 1.00
Received By shill Date 2004-07-23 Time 17:26 Sent To  
Notes
2004-07-23 00:00:00SEE 04060887

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-27 Cont ID  
Sent By dpalmer Date 2004-10-27 Time 13:26 Rev Time 0.25
Received By dpalmer Date 2004-10-27 Time 13:26 Sent To  
Notes
2004-10-27 00:00:00NOTED 2002 NEC

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By dpalmer Date 2004-06-24 Time 10:44 Rev Time 0.50
Received By dpalmer Date 2004-06-24 Time 10:44 Sent To  
Notes
2004-06-24 00:00:00*************** UNSAT ***************
 BLDG # 7
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANLE SCHEDULE.
  
 2)NOTE: PLEASE SEE NFPA-72 FOR SD
 INSTALLATION LOCATIONS.
 3'BATHS,LITS, 20' COOKING ETC. PLEASE
 ALSO SEE EXCEPTIONS.
  
 3)NOTE: PLEASE SEE MISPRINT FOR ARC
 FAULT PROETCTION. NEC 210.12 E-8
  
 4)NOTE: PLEASE SEE CLOSET LT/ FIXTURE
 TYPE AND DISTANCE FROM SHELVES PER 410.8
  
 5)NOTE: PLEASE INDICATE A/C CU DISC'S
 PER 440.11
  
 6)NOTE: PLEASE SEE FAC 61G15-23.002,
 FS 471.023
 PLEASE INCLUDE ALL LICENSE #'S ON TITLE
 BLOCK.
 PLEASE SEE ATTACHED COPY OF DBPR PRINT
 OUT OF WEB-SITE. FIRM AS SHOWN ON TITLE
 BLOCK IS SHOWN AS HAVING A "CLOSED"
 LICENSE #.
 PLEASE SEE ABOVE IS REQUIRED ON ALL
 SHEETS AND TITLE BLOCKS WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWERS.
  
 7)NOTE: PLEASE SEE OCP FOR AHU IS SHOWN
 LARGER THAN CU , YET LOAD CALCS SHOW
 CU LOAD? PLEASE CORRELATE WITH A/C PLANS
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2005-03-07 Cont ID  
Sent By shill Date 2005-03-07 Time 08:55 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By mcarsill Date 2004-06-24 Time 11:34 Rev Time 0.00
Received By mcarsill Date 2004-06-24 Time 11:34 Sent To  
Notes
2004-06-24 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESSES REQUIRED.
  
 3) PRESCRIPTIVE STRENGTH REQUIREMENTS
 SHALL BE SHOWN ON PLANS FOR ALL
 HANDRAILS AND GUARDRAILS.
  
 4) IS THE DOOR BETWEEN THE GARAGE AND
 THE STAIRS RATED. NO RATING SHOWN ON
 DOOR SCHEDULE.
  
 5) SMOKE DETECTORS SHALL BE PLACED A
 MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
  
 6) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. PAGE A.1 INDICATES THAT
 THE BUILDING WILL BE FIRE SPRINKLER
 PROTECTED.
  
 7) NO INFORMATION PROVIDED REGARDING
 MONITORING OF THE FIRE SPRINKLER SYSTEM.
  
 8) SITE PLAN DOES NOT DISPLAY ANY
 FIRE HYDRANTS.
  
 9) NO MENTION OF ANY FIRE EXTINGUISHERS.
  
 COURTESY REVIEW PERFORMED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-09-28 Cont ID  
Sent By adarroug Date 2005-09-28 Time 16:32 Rev Time 0.00
Received By adarroug Date 2005-09-28 Time 16:32 Sent To M
Notes
2005-09-28 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 08:58 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 08:58 Sent To B
Notes
2005-09-12 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-23 Cont ID  
Sent By adarroug Date 2005-06-23 Time 10:13 Rev Time 0.00
Received By adarroug Date 2005-06-23 Time 10:13 Sent To B
Notes
2005-06-23 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-21 Cont ID  
Sent By adarroug Date 2005-03-21 Time 09:16 Rev Time 0.00
Received By adarroug Date 2005-03-21 Time 09:16 Sent To B
Notes
2005-03-21 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 15:49 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 15:49 Sent To  
Notes
2005-02-28 00:00:00TO "COMM" BD#36/"COMM" RACK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 13:38 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 13:38 Sent To  
Notes
2005-01-06 00:00:00TO "COMM BD#19/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-14 Cont ID  
Sent By csiegber Date 2004-10-14 Time 10:23 Rev Time 0.00
Received By csiegber Date 2004-10-14 Time 10:23 Sent To  
Notes
2004-10-14 00:00:00TO COMM BD#21/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-23 Cont ID  
Sent By shill Date 2004-07-23 Time 17:26 Rev Time 0.00
Received By shill Date 2004-06-18 Time 11:42 Sent To  
Notes
2004-06-18 00:00:00TO COMM BD#24

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-10-18 Cont ID  
Sent By tgordon Date 2005-10-18 Time 16:44 Rev Time 0.30
Received By tgordon Date 2005-10-18 Time 16:44 Sent To  
Notes
2005-10-18 00:00:00MECH. REV. PLANS AND E. CAL. .

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-12-01 Cont ID  
Sent By pkrauss Date 2004-12-01 Time 17:07 Rev Time 0.10
Received By pkrauss Date 2004-12-01 Time 17:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-11-30 Cont ID  
Sent By pkrauss Date 2004-11-30 Time 07:53 Rev Time 0.35
Received By pkrauss Date 2004-11-30 Time 07:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-11-30 Cont ID  
Sent By pkrauss Date 2004-11-30 Time 07:49 Rev Time 0.40
Received By pkrauss Date 2004-11-30 Time 07:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-19 Cont ID  
Sent By pkrauss Date 2004-07-19 Time 09:26 Rev Time 0.40
Received By pkrauss Date 2004-07-19 Time 09:25 Sent To  
Notes
2004-07-19 00:00:00DENIED:"BORDEAUX MODEL" UNIT 29 & 30
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 402.2, 402.2.1 OR 403.3.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 3.RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.PER THE
 REVISED 2001 FBC(M) 601.4 EXCEPTION #1;
 TRANSFER DUCTS SHALL BE A MINIMUM OF 1
 1/2 TIMES THE SQUARE INCHES OF THE
 SUPPLY AIR TO THAT SPACE.EXCEPTION #3;
 ALL AIR INTO THE MASTER SUITE IS TO BE
 INCLUDED.SEE THE ATTACHED SCHEDULE FOR
 PROPER SIZING.
  
 4.PLANS ARE TO BE SIGNED AND DATED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE HVAC SYSTEM IN ACCORDANCE WITH THE
 FLORIDA STATUTES AND THE FLORIDA
 ADMINISTRATIVE CODE.
  
 5.PLEASE CLARIFY RATING OF THE
 SEPARATION WALL BETWEEN THE GARAGE AND
 THE RESIDENCE.
  
 6.PER 2001 FBC 104.2.1, TWO COPIES OF
 PLANS AND SPECIFICATIONS ARE TO BE
 PROVIDED FOR EACH PERMIT APPLICATION.
 PLEASE PROVIDE ADDITIONAL PLANS FOR
 COMPLIANCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-01-31 Cont ID  
Sent By kstevens Date 2005-01-31 Time 15:29 Rev Time 0.56
Received By kstevens Date 2005-01-31 Time 15:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-12 Cont ID  
Sent By kstevens Date 2004-11-12 Time 17:35 Rev Time 0.25
Received By kstevens Date 2004-11-12 Time 17:35 Sent To  
Notes
2004-11-12 00:00:00DENIED
  
  
 SEE COMMENTS FROM PERMIT #04060868

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-17 Cont ID  
Sent By kstevens Date 2004-07-17 Time 14:35 Rev Time 0.33
Received By kstevens Date 2004-07-17 Time 14:35 Sent To  
Notes
2004-07-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P.4 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENT, THE TUB IN
 BATH 2 THIRD FLOOR IS NOT VENTED. THE
 TUB SHALL CONNECT TO BRANCH DRAIN DOWN-
 STREAM OF THE LAV. SECTION 901.2.1
 2)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-25 Cont ID  
Sent By eschneid Date 2004-10-25 Time 14:55 Rev Time 0.25
Received By eschneid Date 2004-10-25 Time 14:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-06-30 Cont ID  
Sent By mmclean Date 2004-06-30 Time 14:26 Rev Time 0.00
Received By mmclean Date 2004-06-30 Time 14:26 Sent To  
Notes
2004-06-30 00:00:00DENIED, NEED TO PROVIDE PLAT WITH 41
 LOTS WITH ENGINEERING PLANS (2 SETS).
 NEED TO PROVIDE LANDSCAPE PLANS. CALL
 ERIC SCHNEIDER, SENIOR PLANNER AT 659-
 8031 FOR ANY QUESTIONS.