Plan Review Details - Permit 04060853
Plan Review Stops For Permit 04060853
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-11-08 Cont ID  
Sent By alange Date 2004-11-08 Time 08:16 Rev Time 1.50
Received By alange Date 2004-11-08 Time 08:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-23 Cont ID  
Sent By alange Date 2004-08-23 Time 10:36 Rev Time 1.00
Received By alange Date 2004-08-23 Time 10:36 Sent To  
Notes
2004-08-23 00:00:00DENIED
 SUBMIT PRODUCT APPROVALS FOR EXTERIOR
 DOORS, WINDOWS AND IMPACT PROTECTION.
 ALSO FOR STRAPS AND TIE DOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 PERMIT FEES OF $161.60 ARE DUE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-13 Cont ID  
Sent By kstevens Date 2004-08-21 Time 07:43 Rev Time 1.00
Received By alange Date 2004-07-13 Time 14:28 Sent To  
Notes
2004-07-13 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.IS EXISTING BUILDING WOOD OR
 MASONARY.IF WOOD FRAMED SHOW FRAMING
 DETAILS WITH STRAPS USED AND SIZES OF
 HEADERS.ALSO SHOW HOW WOOD MASONARY
 CONTACT ISSUE WILL BE ADDRESSED.
  
 4.SUBMIT PRODUCT APPROVALS FOR
 EXTERIOR DOORS, WINDOWS AND IMPACT
 PROTECTION. TWO COPIES REQUIRED.
  
 5. WHAT TYPE OF SIDING IS USED?
  
 6.INSUFFICIENT INFORMATION PROVIDED
 FOR A COMPLETE REVIEW.
  
 7.BUILDING VALUATION IS TOO LOW.
 ADJUST VALUATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-11-17 Cont ID  
Sent By dpalmer Date 2004-11-17 Time 09:27 Rev Time 0.50
Received By dpalmer Date 2004-11-17 Time 09:27 Sent To B
Notes
2004-11-17 00:00:00REDLINED 210.70 FOR ROOM.
  
 SENT TO BLDG FOR PROCESSING.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-11-15 Cont ID  
Sent By dpalmer Date 2004-11-15 Time 13:52 Rev Time 0.50
Received By dpalmer Date 2004-11-15 Time 12:58 Sent To  
Notes
2004-11-15 00:00:00** UNSAT **
  
 1)NOTE: PLEASE SEE TITLE BLOCK,
 INFORMATION STILL NOT INCLUDED AS
 REQUIRED UNDER FS 471.023
 FAC 61G15-23.002
  
 2)NOTE: PLEASE SEE MISSING LOAD
 CALCUALTIONS FOR SERVICE. ONLY LOAD CALC
 SHOWN IS FOR NEW SUB-PANEL.
  
 3)NOTE: PLEASE HAVE PRINTED NAME AND
 SIGNATURE OF PERSON RESPONSIBLE FOR
 PLANS ON EACH SHEET.
 IF PANEL SCHEDULE/LOAD CALCS ARE DONE BY
 SOMEONE ELSE, PLEASE HAVE THAT PERSON DO
 THE SAME.
 FBC 104.2.1
  
 PLEASE NOTE*** NOC IS EXPIRED AND WILL
 NEW A NEW RECORDED NOC BEFORE PICKING UP
 PERMIT.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-10-06 Cont ID  
Sent By dpalmer Date 2004-10-06 Time 20:25 Rev Time 0.33
Received By dpalmer Date 2004-10-06 Time 20:25 Sent To P
Notes
2004-10-06 00:00:00********** UNSAT 3RD REVIEW *********
  
 **PLEASE SEE SOME NOTES FROM FIRST TWO
 REVIEWS STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 471.023 FOR REQUIRED MISSING INFORMAT
 -ION ON TITLE BLOCKS.
 PLEASE ALSO SEE FBC 104.2.1 FOR PERSON
 RESPONSIBLE FOR PLANS.
 NOTE#2 FROM PREVIOUS REVIEW.
  
 2)NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS
 REVIEW. PLEASE SUBMIT LOAD CALCULATIONS
 PER 2002 NEC 220.31B. 215.5
  
 3)NOTE: PLEASE SEE A NEW RISER DIAGRAM
 IS NOW BEING SUBMITTED FOR REVIEW.
 PLEASE CORRELATE RISER, PANEL SCHEDULE
 SPECS AND LEGEND TO THE LEFT OF RISER.
 ONE SHOWS PANEL "A" AS A 100A PANEL,
 OTHER 125A, ALSO 60A?
  
 4)NOTE: PLEASE SEE NOTE BELOW RISER
 MENTIONS THIS GARAGE IS ATTACHED, YET
 PLANS SHOW THIS BLDG AS DEATCHED ON
 BLDG AND ELECTRICAL PLANS??
 PLEASE SEE 250.32 FOR GROUNDING AT
 DETACHED BLDGS.
  
 5)NOTE: PLEASE SEE ROOM/PORCH WITH MISS-
 -ING EGRESS LTS. 210.70
 RECEPTS? 210.52
  
 6)NOTE: PLEASE SEE 210.52D,210.11C3 FOR
 REQUIRED CIRCUIT FOR BATH NOT SHOWN ON
 PANEL SCHEDULE.
  
 7)NOTE: PLEASE SEE ARC-FAULT PROTECTION
 WILL BE REQUIRED FOR CABANA/ADAPTABLE
 SLEEPING RM. FOR RECEPTS/LTS/SD.
 2002 NEC 210.12
  
 8)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL. THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME. HOWEVER ONE COPY OF
 EACH SET IS NOW BEING RETAINED FOR FILE
 AND POSSIBLE REVIEW BY THE FBPE'S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:36 Rev Time 0.50
Received By dpalmer Date 2004-08-17 Time 11:48 Sent To P
Notes
2004-08-17 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE SOME NOTES FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.
  
 2)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 471.023,025.
 PLEASE INCLUDE ALL REQUIRED INFORMATION
 ON TITLE BLOCKS AS REQUIRED PER ABOVE.
 PLEASE ALSO SEE PLANS ARE NOT SIGNED,
 DATED AND SEALED BY THE ENGINEER OF
 RECORD.
  
 3)NOTE: PLEASE SEE PANEL SCHEDULE NOW
 SUBMITTED ALONG W/ LOAD CALCS WHICH ARE
 BOTH SHOWN "BLANK". THE NOTE MENTIONS
 CONTRACTOR TO BE RESPONSIBLE FOR THIS,
 HOWEVER MIN REQUIREMENTS UNDER 2002 NEC
 IS REQUIRED AT THIS TIME.
 215.5/220.31B
  
 4)NOTE: PLEASE INCLUDE RISER DIAGRAM
 WHICH FEEDS DETACHED BLDG.
 PLANS DO NOT INDICATE HOW THIS BLDG IS
 FED/ GROUNDING /PANEL SCHEDULE ETC.
 225.31,250.32.
  
 5)NOTE: PLEASE SEE PLANS INDICATE AN
 EXISTING A/C CU, YET SHOWS A NEW AHU?
 PLEASE CLARIFY.
 PLANS/ APPLICATION MENTIONS CONVERTING
 AN EXSITING GARAGE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-08-11 Time 10:46 Rev Time 0.25
Received By dpalmer Date 2004-07-02 Time 11:37 Sent To P
Notes
2004-07-02 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCK AS REQUIRED UNDER
 FS 471.023, FAC 61G15-23.002
  
 2)NOTE: PLEASE SUBMIT ELECTRICAL PLANS
 FOR NEW CONVERSION.
 PLANS TO MEET 2002 NEC, NFPA-72, LS101
 FBC 104.2.1
  
 PLANS NOT COMPLETE AT THIS TIME FOR
 FULL REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-11-08 Cont ID  
Sent By csiegber Date 2004-11-08 Time 14:45 Rev Time 0.00
Received By csiegber Date 2004-11-08 Time 14:45 Sent To E
Notes
2004-11-08 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-11-04 Cont ID  
Sent By csiegber Date 2004-11-04 Time 14:46 Rev Time 0.00
Received By csiegber Date 2004-11-04 Time 14:46 Sent To B
Notes
2004-11-04 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-10-05 Cont ID  
Sent By mmclean Date 2004-11-02 Time 13:35 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:35 Sent To E
Notes
2004-10-05 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-08-11 Time 10:46 Rev Time 0.00
Received By csiegber Date 2004-08-11 Time 10:46 Sent To E
Notes
2004-08-11 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-06 Cont ID  
Sent By mmclean Date 2004-08-10 Time 15:06 Rev Time 0.00
Received By csiegber Date 2004-08-06 Time 11:48 Sent To Z
Notes
2004-08-06 00:00:00TO MM BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:38 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 16:38 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-30 Cont ID  
Sent By mmclean Date 2004-07-01 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-06-30 Time 13:40 Sent To Z
Notes
2004-06-30 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-18 Cont ID  
Sent By csiegber Date 2004-06-18 Time 16:27 Rev Time 0.00
Received By csiegber Date 2004-06-18 Time 16:27 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-02-08 Cont ID  
Sent By prafter Date 2005-02-08 Time 09:55 Rev Time 0.45
Received By prafter Date 2005-02-08 Time 09:55 Sent To E
Notes
2005-02-08 00:00:00FL. ENERGY REPORT NOT FOR CABANA.
 NO A/C PLAN OR EQUIPEMET INFORMATION
 FOR CABANA.
  
 PAT RAFTER 2/8/05 561/805/6728.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-10-27 Cont ID  
Sent By pkrauss Date 2004-10-27 Time 12:49 Rev Time 0.30
Received By pkrauss Date 2004-10-27 Time 12:49 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-07-13 Cont ID  
Sent By kstevens Date 2004-10-21 Time 12:06 Rev Time 0.25
Received By pkrauss Date 2004-07-13 Time 09:19 Sent To B
Notes
2004-07-13 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED ON PERMIT APPLICATION.
 PLEASE PROVIDE PLANS, A COMPLETED FORM
 600C, AND INDICATE IF A/C WILL BE NEW
 OR EXISTING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-10-21 Cont ID  
Sent By kstevens Date 2004-10-21 Time 12:06 Rev Time 0.50
Received By kstevens Date 2004-10-21 Time 12:06 Sent To M
Notes
2004-10-21 00:00:00CABANA ONLY THIS PERMIT

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-08-21 Cont ID  
Sent By dpalmer Date 2004-10-06 Time 20:25 Rev Time 0.50
Received By kstevens Date 2004-08-21 Time 07:42 Sent To B
Notes
2004-08-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SANT. RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS.
 A) SHOW ALL PIPE SIZES
 B) WASH MACHINE SHALL BE LOCATED DOWN-
 STREAM OF THE KITCHEN ON THE RISER DIAG-
 RAM AS IT IS SHOWN ON THE FLOOR PLAN.
 C) THE CABANA IS LOCATED TO THE NORTH-
 WEST CORNER OF THE LOT AND THE RISER
 DIAGRAM SHOWS THE CABANA CONNECTING
 PRIOR TO BATH #2 AND GOING TO THE SOUTH.
 D) WASH MACHINE REQUIRES A 2' STANDPIPE
 AND A CLEANOUT 4' ABOVE THE FLOOR FOR
 ACCESS. SECTIONS 1002.1/808.4 & 708.10
 PLEASE SUBMIT A RISER THAT REFLECT THE
 FLOOR PLAN AND MEETS CODE REQUIREMENTS.
 2)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-10 Cont ID  
Sent By dpalmer Date 2004-08-17 Time 13:17 Rev Time 0.33
Received By jleech Date 2004-07-10 Time 13:25 Sent To M
Notes
2004-07-10 00:00:00DENIED;
 1.SEE NOTE 1 ELECTRICAL PLAN REVIEW
 NOTES.
 2.TWO WAY CLEANOUT REQUIRED WITHIN 3'
 OF BUILDING.
 3.NOTE 3 AIR CHAMBERS NOT PERMITED BY
 CODE. SHOCK ARRESTORS TO BE USED PER
 SEC. 604.9
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2004-11-02 Cont ID  
Sent By mmclean Date 2004-11-02 Time 13:34 Rev Time 0.00
Received By mmclean Date 2004-11-02 Time 13:34 Sent To I
Notes
2004-11-02 00:00:00NO LIVING SPACE ALLOWED. ZONED SF7

Review Stop Z ZONING
Rev No 3 Status F Date 2004-08-10 Cont ID  
Sent By pkrauss Date 2004-10-27 Time 12:49 Rev Time 0.00
Received By mmclean Date 2004-08-10 Time 15:06 Sent To I
Notes
2004-08-10 00:00:00DENIED, NEED TO CHANGE FROM STANDARD
 SIZE REF & FREEZER TO UNDER THE COUNTER
 FREEZER & REFIDGERATOR.CALLED CONTR
 WILL PROVIDE NEW PLANS MM. PER ANGELLA
 JONES-VANN MM

Review Stop Z ZONING
Rev No 2 Status F Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-08-06 Time 11:48 Rev Time 0.00
Received By mmclean Date 2004-07-01 Time 16:30 Sent To I
Notes
2004-07-01 00:00:00DENIED, NEED TO CHANGE THE DESCRIPTION
 ON APPLICATION AND COMPUTER TO REFLECT
 THE DRAWINGS (CABANA).

Review Stop Z ZONING
Rev No 1 Status F Date 2004-06-21 Cont ID  
Sent By csiegber Date 2004-06-30 Time 13:41 Rev Time 0.00
Received By mmclean Date 2004-06-21 Time 11:44 Sent To  
Notes
2004-06-25 00:00:00RECEIVED MSG AND RETURNED CALL LEFT MSG
2004-06-22 00:00:00DENIED, CANNOT HAVE A GUEST SUITE AT
 LOCATION.ZONED SF7.NO KITCHEN OR
 LIVING SPACE IS ALLOWED.CALL CONTR
 FILE UNDER G FOR PICKE UP MM
2004-06-21 00:00:00DENIED, NEED TO PROVIDE TWO COPY OF
 SURVEY SHOWING THE WORK OF THE PROJECT.
 ZONED SF7 CANNOT HAVE AN ACCESSORY
 STRUCTURE, NO KITCHEN.CALLED CONTR
 FILE G FOR P/U MM