Plan Review Details - Permit 04060851
Plan Review Stops For Permit 04060851
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-08-16 Cont ID  
Sent By lsmith Date 2004-08-16 Time 11:25 Rev Time 0.75
Received By lsmith Date 2004-08-16 Time 11:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-01 Cont ID  
Sent By lsmith Date 2004-07-01 Time 08:43 Rev Time 1.00
Received By lsmith Date 2004-07-01 Time 08:42 Sent To  
Notes
2004-07-01 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. SECOND SET OF PLANS ARE INCOMPLETE.
 PAGES 3.0 & 3.1 ARE MISSING.
 2. SEPARATE PERMITS REQUIRED FOR
 PLUMBING, ELECTRICAL & MECHANICAL.
 3. SEE ELECTRICAL COMMENTS ON LICENSE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-23 Cont ID  
Sent By dpalmer Date 2004-08-23 Time 08:16 Rev Time 0.33
Received By dpalmer Date 2004-08-23 Time 08:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-21 Cont ID  
Sent By dpalmer Date 2004-06-21 Time 16:50 Rev Time 1.50
Received By dpalmer Date 2004-06-21 Time 16:50 Sent To  
Notes
2004-06-21 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE FS 471.023, FAC 61G15
 -23.002. PLEASE SEE A CERTIFICATE OF
 AUTHORIZATION # IS REQUIRED ON TITLE
 BLOCK FOR FIRM.
 PLEASE SEE THERE IS NO MATCHING RECORD
 WITH STATE AS HAVING A LICENSE #.
 PLEASE SEE WE ARE RATAINING ONE SET OF
 PLANS FOR FILE. COPIES ARE TO BE SENT TO
 THE FBPE'S/ DBPR.
  
 2)NOTE: PLEASE PROVIDE NOTE FOR SHUT
 DOWN OF HOOD PER NFPA-96 CHAPTER 9
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONE SET
 OF OLD SHOULD BE SUBMITTED FOR REFERENCE
 ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-09-01 Cont ID  
Sent By mcarsill Date 2004-09-01 Time 15:34 Rev Time 0.00
Received By mcarsill Date 2004-09-01 Time 15:33 Sent To  
Notes
2004-09-01 00:00:001) SEPARATE PLAN AND PERMIT
 REQUIRED FOR HOOD, DUCT AND SUPPRESSION
 SYSTEM.
  
 2) PLEASE PROVIDE PRODUCT APPROVALS
 FOR DUCTWRAP LISTED ON THE PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-18 Cont ID  
Sent By mcarsill Date 2004-06-18 Time 12:26 Rev Time 0.00
Received By mcarsill Date 2004-06-18 Time 12:26 Sent To  
Notes
2004-06-18 00:00:001) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 2) PLEASE PROVIDE MORE DETAILS ON LP
 GAS TANKS. WHAT SIZE, HOW CLOSE TO
 PROPERTY LINES, WHAT MECHANICAL
 PROTECTION IS PROVIDED, AND ARE THE
 TANKS PROPERLY LABELED.
  
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR HOOD, DUCT, AND FIRE SUPPRESSION
 SYSTEMS PLANNED FOR USE.
  
 4) WHAT SIZES ARE THE PORTABLE FIRE
 EXTINGUISHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-17 Cont ID  
Sent By mjacobs Date 2004-12-17 Time 10:33 Rev Time 0.00
Received By mjacobs Date 2004-12-17 Time 10:33 Sent To G
Notes
2004-12-17 00:00:00SENT TO "GAS" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-22 Cont ID  
Sent By csiegber Date 2004-09-22 Time 14:34 Rev Time 0.00
Received By csiegber Date 2004-09-22 Time 14:34 Sent To P
Notes
2004-09-22 00:00:00TO KS DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-13 Cont ID  
Sent By csiegber Date 2004-08-13 Time 12:46 Rev Time 0.00
Received By csiegber Date 2004-08-13 Time 12:46 Sent To  
Notes
2004-08-13 00:00:00TO COMM BD#25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-09 Cont ID  
Sent By csiegber Date 2004-08-13 Time 12:46 Rev Time 0.00
Received By csiegber Date 2004-06-18 Time 10:52 Sent To  
Notes
2004-06-18 00:00:00TO COMM BD#34

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-27 Cont ID  
Sent By pkrauss Date 2004-08-27 Time 15:15 Rev Time 0.55
Received By pkrauss Date 2004-08-27 Time 14:44 Sent To  
Notes
2004-11-18 00:00:00HOOD/GREASE DUCT PLANS SUBMITTED AND
 APPROVED WITH BUILDING PERMIT.
 ADDITIONAL PERMIT REQUIRED FOR FIRE
 SUPPRESSION.PLEASE PROVIDE PLANS WITH
 PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-06 Cont ID  
Sent By pkrauss Date 2004-07-06 Time 08:46 Rev Time 0.55
Received By pkrauss Date 2004-07-06 Time 08:42 Sent To  
Notes
2004-07-06 00:00:00DENIED:
 1.PLAN SHEET A3.0 INDICATES LP TANKS
 ARE EXISTING WHEREAS PLAN SHEET A3.1
 INDICATES LP TANKS BY THE UTILITY CO.
 PLEASE CLARIFY.
  
 2.INDICATE CAPACITY OF THE TANKS,
 DISTANCE FROM THE PROPERY LINE, BUILDING
 AND COMBUSTIBLES.SHOW COMPLIANCE WITH
 NFPA 58.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 4.ADDITIONAL PERMITS REQUIRED FOR THE
 HOODS, FIRE SUPPRESSION AND WALK-IN
 COOLERS.PLEASE PROVIDE PLANS AND
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 5.PLEASE SEE COMMENT #1 BY DEWEY
 PALMER, ELECTRICAL PLAN REVIEW.PROVIDE
 CERTIFICATE OF AUTHORIZATION # AS
 REQUIRED BY FS 471.023 & FAC 61G15.23.00
 .2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-12-22 Cont ID  
Sent By kstevens Date 2004-12-22 Time 18:05 Rev Time 1.25
Received By kstevens Date 2004-12-22 Time 18:05 Sent To  
Notes
2004-12-22 00:00:00REVISION FOR GAS OK - RED LINE
 CORRECTIONS - WILL RESUBMIT A CLEAN SET
 OF REVISIONS 12-27-4 AS I HAVE MADE
 MISTAKES WITH THESE. KSTEVENS

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-10-15 Cont ID  
Sent By kstevens Date 2004-10-15 Time 19:22 Rev Time 1.50
Received By kstevens Date 2004-10-15 Time 19:22 Sent To  
Notes
2004-10-15 00:00:00PASSED/PROVISO
  
 REVISION REQUIRED ON GAS RISER. SHOW
 CORRECTED GAS PIPE AND VALVE SIZE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-08-27 Cont ID  
Sent By csiegber Date 2004-09-22 Time 14:35 Rev Time 2.00
Received By kstevens Date 2004-08-27 Time 13:36 Sent To  
Notes
2004-08-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) FROM PREVIOUS REVIEW:
 2 SETS OF PLANS WITH DBPR STAMP AND WORK
 SHEET ARE REQUIRED FOR REVIEW. SECTION
 104.2.1. - ONLY ONE SET OF PLANS AND
 WORK SHEET SUBMITTED. - ALSO FROM PRE-
 VIOUS REVIEW: SHEETS ADDED TO PLANS WITH
 DBPR STAMP ON THEM SHALL BE SIGNED,
 SEALED, AND DATED BY THE ENGINEER OF
 RECORD AS REQUIRED BY SECTION 104.2.2.
 2) FROM PREVIOUS REVIEW: CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE FOR SIZ-
 ING OF GREASE INTECEPTOR. WASTE ORDIN.
 #2938-96. (561) 837-4074. NO RESPONSE
 NOTED.
 3) SHT A1.1 EQUIPMENT SCHEDULE:
 #23 (2) HAND SINKS, NO WATER SUPPLY OR
 DRAINAGE INDICATED ON SCHEDULE.
 #24 3 HOLE STEAM TABLE, NO DRAIN? PLEASE
 CLARIFY. SECTION 104.2.1
 THESE COMMENTS WERE NOT ADDRESSED.
 4) FROM PREVIOUS REVIEW: FOR GAS
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES. - NOT ALL
 PIPE SIZES SHOWN. ALSO SHUT OFF VALVES
 SHALL BE THE SAME SIZE AS THE PIPE SIZE
 REQUIRED FOR GAS APPLIANCE. - PIPES
 SHALL BE SIZED PER FBC-2001 FUEL GAS
 TABLE 402(26)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-09 Cont ID  
Sent By kstevens Date 2004-07-09 Time 13:58 Rev Time 2.50
Received By kstevens Date 2004-07-09 Time 13:57 Sent To  
Notes
2004-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A1.0 MEN & WOMEN TOILET ROOMS,
 SHOW CLEAR FLOOR SPACE FOR W/C'S PER FIG
 28. MINIMUM 48" WIDE CLEAR FLOOR SPACE.
 URINAL PARTITION SHOWN IN URINAL DETAIL
 CAN NOT BE IN CLEAR FLOOR SPACE FOR THE
 WATER CLOSET. SECTION 11-4.22.3
 2) 2 SETS OF PLANS WITH DBPR STAMP AND
 WORK SHEETS ARE REQUIRED FOR REVIEW.
 SECTION 104.2.1
 3) CONTACT RODNEY COMPO ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTECEP-
 TOR. WASTE ORD. #2938-96. (561) 837-4074
 4) SEE ATTACHED SHEET FOR UTILITY STAND-
 ARD FOR GREASE INTERCEPTORS.
 5) SHT A1.1 EQUIPMENT SCHEDULE:
 #19.9 REFRIDGERATION FOR #18? (MOP SINK)
 PLEASE CLAIRFY. SECTION 104.2.1
 #23 (2) HAND SINKS, NO WATER SUPPLYS OR
 DRAINAGE INDICATED ON SCHEDULE?
 #24 3 HOLE STEAM TABLE, NO DRAIN?
 PLEASE CLARIFY. SECTION 104.2.1
 6) SHT A3.0 GREASE RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE MOP SINK
 AND FLOOR SINK FOR THE ICE MAKER ARE NOT
 SHOWN ON RISER. SECTION 104.2.1
 7) SHT A3.0 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 SHALL BE LOCATED NEAR THE FIXTURES
 NOT IN THE CEILING. PDI-WH 201.
 8) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 9) THERMAL EXPANSION CONTROL IS REQUIRED
 FOR THE WATER HEATER. SECTION 607.3.2.
 10) THE FOLLOWING INFORMATION IS REQUIR-
 ED FOR GAS PERMIT. SEPARATE GAS PERMIT
 REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - NOT ALL MEASUREMENTS
 ARE SHOWN.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. - THE MAN-
 UAL VALVE IS SHOWN DOWNSTREAM OF THE
 EMERGENCY VALVE.
 11) ENG'S SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025 - REMOVE
 ALL REFERENCES TO METRO DESIGN GROUP
 FROM THE PLANS.
 12) SHEETS ADDED TO PLANS WITH DBPR
 STAMP ON THEM SHALL BE SIGNED AND SEALED
 BY THE ENGINEER OF RECORD AS REQUIRED
 BE SECTION 104.2.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy