| Plan Review Stops For Permit 04060837 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-09-14 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-09-14 |
Time |
11:11 |
Rev Time |
0.66 |
| Received By |
alange |
Date |
2004-09-14 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2004-09-14 00:00:00 | DENIED | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-08-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-31 |
Time |
11:32 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2004-08-20 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2004-08-20 00:00:00 | DENIED | | | | | | 1.PRODUCT APPROVALS: | | | PRO-TECT HURICANE PANELS MISSING PAGES | | | FROM BOTH SETS. | | | LAWSON WINDOW ONE SET MISSING. | | | SUBMIT 2 SETS FOR STRAPS AND TIEDOWNS. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 3.LAWSON 24SH DOES NOT MEET EMERGENCY | | | ESCAPE RESCUE OPENING REQUIREMENTS. | | | PER FBC 1005.4 | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | ART LANGE | | | BUILDING PLAN REVIEW | | | TEL: (561)805-6672 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-07-09 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-20 |
Time |
12:13 |
Rev Time |
1.25 |
| Received By |
alange |
Date |
2004-07-09 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2004-07-09 00:00:00 | DENIED | | | | | | 1.PRODUCT APPROVALS MISSING FOR | | | ROOFING SHINGLES, ROOF TILE, AND | | | SHUTTERS.SUBMIT 2 COPIES. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATIONPLEASE SEE THE STATE WEBSITE | | | AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 3.LAWSON 24 DOES NOT MEET EMERGENCY | | | ESCAPE RESCUE OPENING REQUIREMENTS | | | PER FBC 1005.4. | | | | | | 4.INCLUDE A FRAMING PLAN SHOWING | | | STRAPS, HEADERS AND SIZES. | | | | | | 5.TITLE BLOCK MISSING ON SECOND PAGE. | | | FAC 61G15-23.002 | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-10 |
Time |
13:54 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-08-10 |
Time |
13:47 |
Sent To |
P |
|
| Notes |
| 2004-08-10 00:00:00 | ********* PROVISO/REVISION ************* | | | | | | 1)NOTE: PLEASE SEE PLANS NOW INDICATE | | | TWO PANELS? PLANS ARE STILL NOT SHOWING | | | METER/SERVICE LOCATION AS REQUESTED ON | | | FIRST REVIEW. | | | | | | 2)NOTE: PLEASE SEE RISER NOW INDICATES | | | AN EQUIPMENT GROUNDING CONDUCTOR FROM | | | METER TO MAIN. PLEASE SEE 250.24,250.6 | | | AN EQUIPMENT GRND IS ONLY INSTALLED | | | AFTER THE FIRST MEANS OF DISCONNECT. | | | | | | 3)NOTE: PLEASE SEE " ELECTRICAL NOTES" | | | REFEERENCES ARC-FAULT PROTECTION FOR | | | RECEPTS ONLY. WE ARE UNDER 2002 NEC , | | | 210.12 WHICH REQUIRES AFCI PROTECTION | | | FOR ALL "OUTLETS" IN BEDRMS. | | | | | | PLEASE SUBMIT CORRECTED REVISED PLANS | | | BEFORE ANY ROUGH ELECTRICAL INSPECTION | | | IS CALLED IN. IF PLANS COME BACK FOR ANY | | | CORRECTIONS NEEDED BEFORE PERMIT IS | | | ISSUED, PLEASE MAKE CORRECTIONS AT THAT | | | TIME. | | | THIS WILL BE A REVISION AND FEES WILL BE | | | DUE AFTER PERMIT IS ISSUED. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-06-22 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-03 |
Time |
11:34 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-06-22 |
Time |
17:07 |
Sent To |
P |
|
| Notes |
| 2004-06-22 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE SECOND SHEET MISSING | | | REQUIRED TITLE BLOCK. FAC 61G15-23.002 | | | | | | 2)NOTE: PLEASE SEE PANEL IS SHOWN AS A | | | 125A W/ 4/0'S LISTED AS SEC'S? PLEASE | | | SEE 310.15B6 4/0'S ARE RATED FOR A 250A | | | SERVICE. THESE ARE PERMITTED TO BE | | | INSTALLED BUT NOT REQUIRED TO THIS SIZE. | | | THIS IS ONLY A NOTE: IF SHOWN,THEN THEY | | | WILL BE REQUIRED. | | | | | | 3)NOTE: PLEASE SEE PLANS ARE NOT SHOWING | | | A/C UNITS, REQUIRED DISC'S, RECEPTS. | | | 440.11,210.63,210.70? | | | | | | 4)NOTE:PLEASE SEE MISSING FRONT AND REAR | | | RECEPTS. PER 210.52E | | | | | | 5)NOTE: PLEASE SEE RECEPTS IN BEDRM ARE | | | SHOWN AS AFI, HOWEVER WE AREUNDER THE | | | 2002 NEC WHICH REQUIRES PROTECTION FOR | | | ALL "OUTLETS" INCLUDING SD'S/LTS/FANS. | | | 210.12 | | | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 7)NOTE: PLEASE SHOW LOCATION OF METER | | | ON HOUSE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-08-31 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-31 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-31 |
Time |
11:32 |
Sent To |
B |
|
| Notes |
| 2004-08-31 00:00:00 | TO AL DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-08-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-20 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-20 |
Time |
12:13 |
Sent To |
B |
|
| Notes |
| 2004-08-20 00:00:00 | TO AL DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-08-03 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-08-19 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-03 |
Time |
11:34 |
Sent To |
E |
|
| Notes |
| 2004-08-03 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-06-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-06-21 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-06-21 |
Time |
12:38 |
Sent To |
E |
|
| Notes |
| 2004-06-21 00:00:00 | SENT TO E BOX/REMODEL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-06-17 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-06-21 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-17 |
Time |
14:46 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2004-07-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2004-07-01 |
Time |
19:38 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-07-07 |
Time |
11:17 |
Sent To |
B |
|
| Notes |
| 2004-07-07 00:00:00 | NO MECHANICAL INFORMATION SUBMITTED OR | | | CONTRACTOR INDICATED ON THE PERMIT | | | APPLICATION.FORM 600C SUBMITTED & | | | INDICATES CENTRAL AIR. | | | | | | PLEASE PROVIDE THE FOLLOWING WITH | | | MECHANICAL PERMIT APPLICATION: | | | - EQUIPMENT SCHEDULE | | | - LOCATION OF CONDENSER & AHU. | | | - DUCT/GRILLE SIZE, MATERIAL & LAYOUT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-08-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-08-14 |
Time |
13:21 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2004-08-14 |
Time |
13:21 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-07-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-10 |
Time |
13:54 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2004-07-01 |
Time |
19:38 |
Sent To |
M |
|
| Notes |
| 2004-07-01 00:00:00 | PAGE 2 PLUMBING RISER DIAGRAM. KITCHEN | | | SINKIS REQUIRED TO DISCHARGE DOWN | | | STREAM OF THE BATHROOM GROUP. SEC 909.1. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2004-08-19 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-08-19 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-08-19 |
Time |
14:31 |
Sent To |
I |
|
| Notes |
| 2004-08-19 00:00:00 | APPROVED RESUB MM |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-06-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-08-14 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-06-21 |
Time |
10:55 |
Sent To |
I |
|
| Notes |
| 2004-06-21 00:00:00 | NO WALLS TO BE REMOVED EXTERIOR MM |
|
|