Plan Review Details - Permit 04060776
Plan Review Stops For Permit 04060776
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-06-25 Cont ID  
Sent By jwitmer Date 2004-06-25 Time 16:15 Rev Time 0.55
Received By jwitmer Date 2004-06-25 Time 16:15 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-19 Cont ID  
Sent By dpalmer Date 2004-07-19 Time 09:25 Rev Time 0.50
Received By dpalmer Date 2004-07-19 Time 08:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-17 Cont ID  
Sent By mjacobs Date 2004-07-14 Time 09:08 Rev Time 1.00
Received By dpalmer Date 2004-06-17 Time 15:02 Sent To  
Notes
2004-06-17 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE ONLY ONE SHEET OF
 EACH E0.1 IS IN ONE SET AND ONLY ONE
 SHEET E2.1 IN OTHER SET.
 PLEASE SUBMIT TWO COMPLETE SETS.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATION
 FOR EXSITING PANEL SBA.215.5
  
 3)NOTE: PLEASE VERIFY MEANS OF DISC AT
 ATS, PER 230.76, 230.79
  
 4)NOTE: PLEASE SEE PANEL BOARD ON SEC
 SIDE OF TRANSFORMER IS SHOWN AS MLO,
 PLEASE SEE 408-16D, 240-21C1 ETC MCB
 REQUIRED.
  
 3NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42,210.19A,210.20A ETC
  
 4)NOTE: PLEASE INCLUDE LOCATION OF
 PANEL "H". IS THIS A HOUSE PANEL OR
 PANEL TO THIS SPACE.
 PLEASE ALSO SHOW SIZE OF EXSITING PANELS
 "D".
  
 5)NOTE: PLEASE SEE LICENSE # ON TITLE
 BLOCK IS NOT CORRECT. PLEASE SEE DBPR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-28 Cont ID  
Sent By dpalmer Date 2004-07-19 Time 09:26 Rev Time 0.00
Received By mcarsill Date 2004-07-28 Time 15:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-06-18 Cont ID  
Sent By mcarsill Date 2004-06-18 Time 12:39 Rev Time 0.00
Received By mcarsill Date 2004-06-18 Time 12:39 Sent To  
Notes
2004-06-18 00:00:001) SUBMIT COMPLETE SETS OF PLANS.
 PAGE(S) ARE MISSING FROM WHAT WAS
 SUBMITTED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-19 Time 09:35 Rev Time 0.00
Received By csiegber Date 2004-07-19 Time 09:35 Sent To  
Notes
2004-07-19 00:00:00TO COMM BD#19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-14 Cont ID  
Sent By mjacobs Date 2004-07-14 Time 09:08 Rev Time 0.00
Received By mjacobs Date 2004-07-14 Time 09:07 Sent To E
Notes
2004-07-14 00:00:00SENT TO "DP" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-25 Cont ID  
Sent By mjacobs Date 2004-06-16 Time 16:23 Rev Time 0.00
Received By jwitmer Date 2004-06-16 Time 16:22 Sent To PC
Notes
2004-06-16 00:00:00TO COMM BD #42