Plan Review Details - Permit 04060707
Plan Review Stops For Permit 04060707
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-25 Cont ID  
Sent By rmcdouga Date 2005-03-25 Time 12:42 Rev Time 0.00
Received By rmcdouga Date 2005-03-25 Time 12:42 Sent To  
Notes
2005-03-25 00:00:003/25/05 CHANGED DESIGNERS OF RECORD FROM
 JEFFERY D. BRASSEUR, AR TO HARVEY E.
 KOEHNEN, PE. SEE LETTER IN FILE.
 SUBMITTED NEW SET OF PLANS SIGNED AND
 SEALED BY NEW ENGINEER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-02-23 Cont ID  
Sent By rmcdouga Date 2005-02-23 Time 10:48 Rev Time 0.00
Received By rmcdouga Date 2005-02-23 Time 10:48 Sent To  
Notes
2005-02-23 00:00:00BUILDING DENIED
  
 1) THE SIGNATURE OF THE ARCHITECT WILL
 HAVE TO BE NOTARIZED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-12-30 Cont ID  
Sent By rmcdouga Date 2004-12-30 Time 11:14 Rev Time 0.00
Received By rmcdouga Date 2004-12-30 Time 11:14 Sent To  
Notes
2004-12-30 00:00:00BUILDING DENIED
  
 1) REVISION FEES ARE REQUIRED FOR ALL 13
 PLAN SHEETS.
  
 2) DESIGNER OF RECORD WILL BE CHANGED
 FROM THE ARCHITECT TO THE ENGINEER.
  
 3) SHEET 4, SHEET 10 AND SHEET 11 HAVE
 BEEN REVISED AND ARE OK.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-09-01 Cont ID  
Sent By rmcdouga Date 2004-09-01 Time 14:24 Rev Time 0.00
Received By rmcdouga Date 2004-09-01 Time 14:24 Sent To  
Notes
2004-09-01 00:00:00PROVISO
  
 SUBMIT PRODUCT APPROVALS FOR DOUBLE
 ENTRY DOOR AND SWINGING DOOR AT GARAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-06 Cont ID  
Sent By pkrauss Date 2004-08-26 Time 15:26 Rev Time 4.00
Received By rmcdouga Date 2004-07-02 Time 16:36 Sent To  
Notes
2004-07-06 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE ENGINEER IS REQUIRED TO SIGN AND
 SEAL THE PLAN SHEETS ON WHICH HIS TITLE
 BLOCK APPEARS. SEE FS 471.
  
 3) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 4) FBC 2405.2 REQUIRES WINDOWS WITHIN 3'
 HORIZONTALLY OF A TUB OR SHOWER TO HAVE
 SAFETY GLASS. SEE WINDOWS IN MASTER BATH
  
 5) SPECIFY THE SIZE AND LOCATION OF THE
 ATTIC ACCESS ON THE SECOND FLOOR. SEE
 FBC 2309.6.
  
 6) REVISE NOTE 11 ON SHEET 2. CITY
 AMENDMENTS TO FBC TABLE 2306.1 REQUIRES
 8D RING-SHANK NAILS FOR ROOF SHEATHING
 IN ZONE 3 ON STRUCTURES WITH A MEAN ROOF
 HEIGHT OF 25'-35'.
  
 7) PROVIDE A DOOR BUCK DETAIL. NOTE 13
 ON SHEET 2 DOES NOT SPECIFY DOOR BUCKS.
  
 8) SPECIFY THAT THE GUARDRAIL ON SHEET 3
 MUST REJECT A 4" SPHERE PER FBC 1015.3.
  
 9) FBC 1007.5 REQUIRES STAIRWAYS TO HAVE
 A HANDRAIL NOT LESS THAN 34" NOR MORE
 THAN 38" ABOVE THE LEADING EDGE OF A
 TREAD. SEE FBC 1007.5.3 FOR GRASPABILITY
 REQUIREMENTS.
  
 10)SPECIFY THE REQUIRED DESIGN PRESSURES
 FOR THE WINDOWS ON SHEET 4.
  
 11)SPECIFY THE R-VALUE OF THE INSULATION
 AT THE BLOCK WALLS. MUST CORRESPOND WITH
 THE ENERGY CALCS.
  
 12) SPECIFY THE LOCATIONS AND MATERIALS
 USED FOR THE DRAFTSTOPPING AT THE FLOOR/
 CEILING ASSEMBLY DIVIDING THE AREA INTO
 AREAS OF 500 SQFT OR LESS PER FBC 2305.2
 AND 2305.2.6.
  
 13) SPECIFY THE BOTTOM CORD LIVE LOAD ON
 THE PLANS. SEE FBC TABLE 1604.1.
  
 14) SPECIFY THE CONNECTORS USED TO
 ATTACH THE BOTTOM CORD OF THE ROOF
 TRUSSES TO THE LEDGERS.
  
 15) SPECIFY THE CONNECTORS FOR ATTACHING
 THE FLOOR TRUSSES TO THE LEDGERS.
  
 16) SPECIFY THE FIREBLOCKING OF THE
 CONCEALED SPACES BETWEEN STRINGERS AT
 THE STAIRS AT THE TOP AND BOTTOM OF RUNS
 PER FBC 2305.1.4.
  
 17) SPECIFY THE FIREBLOCKING OF THE
 FURRED SPACE AT THE EXTERIOR WALLS WHERE
 THEY MEET CEILINGS ON THE WALL SECTIONS
 PER FBC 2305.1.4.
  
 18) SUBMIT DETAILS FOR FIREPLACE AND
 CHIMNEY. SPECIFICATIONS AND LISTING IF
 THEY ARE PREFAB. PROVIDE DETAILED
 DRAWINGS OF DIMENSIONS, MATERIALS,
 ATTACHMENTS, CONNECTORS, ETC. FOR FIRE-
 PLACE AND CHIMNEY. SPECIFY THE HEIGHT
 ABOVE ROOF FOR THE CHIMNEY AS PER FBC
 2804.
  
 19) FBC 1606.1.4 REQUIRES PROTECTION OF
 GLAZED OPENINGS. SUBMIT STORM PANEL
 PRODUCT APPROVAL, KEY PLAN AND INSTALLA-
 TION SCHEDULE OR PRODUCT APPROVALS FOR
 LARGE MISSLE IMPACT RESISTANT GLASS.
  
 20) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE SAMPLE
 WITH NOAS.
  
 21) SUBMIT STATE OR LOCAL PRODUCT
 APPROVALS FOR THE FOLLOWING:
 - ARCHED TOP WINDOWS (DESIGNER SHAPES)
 - ENTRY DOORS
 - SIDE SWING DOOR AT GARAGE
 - OVER HEAD GARAGE DOOR
 - STORM PANELS
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-06-15 Cont ID  
Sent By dpalmer Date 2005-06-15 Time 12:59 Rev Time 0.25
Received By dpalmer Date 2005-06-15 Time 12:59 Sent To  
Notes
2005-06-15 00:00:00************ UNSAT ***********
  
 1)NOTE: PLEASE SEE GEN IS REQUIRED TO BE
 SUBMITTED UNDER SEPARATE PERMIT.
 PLEASE INCLUDE ALL INFORMATION AS
 REQUIRED FOR GEN PERMIT SUBMITTAL.
  
 PLEASE ALSO NOTE PLANS FOR MAIN/ORIG
 WILL ALSO BE REQUIRED TO BE REVISED
 AFTER PERMIT FOR GEN HAS BEEN OBTAINED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-03-10 Cont ID  
Sent By dpalmer Date 2005-03-10 Time 17:17 Rev Time 0.25
Received By dpalmer Date 2005-03-10 Time 17:17 Sent To P
Notes
2005-03-10 00:00:00REDLINED 220.16
  
 REDLINED NO MORE THAN 8' OF UNPROTECTED
 CONDUCTORS INSIDE HOUSE. 230.70

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-02-14 Cont ID  
Sent By dpalmer Date 2005-02-14 Time 14:04 Rev Time 0.33
Received By dpalmer Date 2005-02-14 Time 13:39 Sent To P
Notes
2005-02-14 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SEE REDLINES FROM
 PREVIOUS REVIEWS.
  
 2)NOTE: PLEASE SEE OCP ON PANEL FOR
 WHIRLPOOL 30A ON #12.
  
 3)NOTE: PLEASE SEC'S TO BE SIZED PER
 310.15B6, 240.4. MIN 400 MCM
  
 4)NOTE: PLEASE SEE GUTTER SIZING PER 366
 SHOWS 3"?
  
 5)NOTE: PLEASE SEE FBC 104.2.1, WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS.
 REQUIRED FOR ALL
  
 6)NOTE: PLEASE ALSO SEE MISSING FOOTER
 STEEL REQUIRED AS PART OF THE GROUNDING
 ELECTRODE SYSTEM. 250.50
  
 7)NOTE: PLEASE SEE LETTER FROM ARCHITECT
 IS ALSO REQUIRED TO BE NOTORIZED.
  
 PLEASE SEE PLANS REQUIRE A REVISION FEE
 FOR REVISED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-12-22 Cont ID  
Sent By dpalmer Date 2004-12-22 Time 17:04 Rev Time 0.40
Received By dpalmer Date 2004-12-22 Time 17:04 Sent To P
Notes
2004-12-22 00:00:00*********** UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS FOR ELECTRICAL
 HAVE NOT CHANGED DESIGNER/ENGINEER/ARCH
 OF RECORD.
 PLEASE SEE PLANS HOWEVER DO HAVE CHANGES
 MADE AND CONTRACTOR OWES REV FEES.
 THIS FEE MAY BE ADJUSTED TO DUE OTHER
 REVIEWS AND POSSIBLE CHANGES TO OTHER
 SHEETS ALSO.
  
 2)NOTE: PLEASE SUBMIT A NOTORIZED LETTER
 FOR THE RELEASE OF PREVIOUS ARCH.
  
 3)NOTE: PLEASE SUBMIT COMPLETED PLANS
 FOR CODE COMPLIANCE. PLEASE SEE ORIG
 NOTES REDLINED ON PLANS. SOME OF THESE
 ITEMS HAVE BEEN CHANGED AND SOME HAVE
 NOT.
  
 PLEASE SEE OTHER COMMENTS FROM OTHER
 REVIEWS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-23 Cont ID  
Sent By dpalmer Date 2004-08-23 Time 09:26 Rev Time 0.50
Received By dpalmer Date 2004-08-23 Time 09:11 Sent To P
Notes
2004-08-23 00:00:00*** NOTES REDLINED. ***
  
 SOME ITEMS FOR LOAD AND OCP WERE RED-
 -LINED ON PANEL SCHEDULE.
  
 GUTTER SIZE TO METT NEC 366.
  
 GEC SHOWN TO SLAB, 250.50 REQUIRED TO
 FOOTER STEEL.
  
 A COUPLE OF RECEPTS MISSING FOR 2' OF
 WALL SPACE PER 210.52. REDLINED.
  
 SEC'S PER 310.15B6,240.4B

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-08-20 Time 16:21 Rev Time 1.50
Received By dpalmer Date 2004-06-23 Time 10:11 Sent To M
Notes
2004-06-23 00:00:00************* UNSAT ************
  
 1)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE ALSO SEE ADAPTABLE RMS W/ CLOSETS
 OR BATHS ATTACHED.
  
 2) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 3) NOTE: PLEASE SEE 210.52C1,2,3 FOR
 RECEPT SPACING IN KITCHENS.THERE ARE A
 COUPLE MISSING. WALL/ PENINSULAR.
  
 4 )NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER PER 220.30
 PLEASE SEE LOAD FOR SUB-PANEL MUST BE
 FIGURED AND THEN ADDED TO MAIN PANEL.
 PLEASE SEE OTHER NOTES PERTAINING TO MIN
 LOADS FOR LAUNDRY ETC.
  
 5)NOTE: PLEASE SEE 220.16B, ETC
 FOR LAUNDRY LOAD MIN.
  
 6)NOTE: PLEASE CORRELATE LOAD/OCP FOR
 PUMPS ON PANEL SCHEDULE.
  
 7)NOTE:PLEASE SEE LOAD SHOWN ON PANEL
 "B" SCHEDULE DOES NOT CORRELATE WITH
 LOAD SHOWN ON PANEL "A" FOR PANEL "B".
  
 8)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS PER 2002 NEC
 210.12. THIS IS FOR ALL ITEMS IN BEDRMS.
 SD'S , LTS, FANS, RECEPTS.
  
 9)NOTE: PLEASE INDICATE REQUIRED GFI
 PROTECTION FOR WHIRLPOOL TUB. 680
  
 10)NOTE: PLEASE SEE SIZE OF DISCONNECT
 AND OCP FOR CU-3, SHOWS 65A DISC AND 65A
 OCP. PLEASE SEE PANEL SCHEDULE.?
  
 11)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS ON RISER.
 PANEL 'A' TO PANEL 'B' AND A/C EQUIP.
 210.110,250.122
  
 12)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250.66
  
 13)NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE ATTACHMENT TO FOOTER STEEL
 AS REQUIRED UNDER 250.50.
  
 14)NOTE: PLEASE SEE MISSING SEC'S SIZE
 FROM METER TO MAIN PANEL.
 PLEASE ALSO LABEL SIZE OF METER CAN.
  
 15)NOTE:PLEASE VERIFY SIZE OF CONDUCTOR
 SHOWN FOR 30A COOKTOP. SHOWS #6 FOR THIS
 UNLESS SOME SORT OF ADAPTER IS USED,
 #6 WILL NOT FIT A 2P30A BRKR.
 PLEASE VERIFY.
  
 16)NOTE: PLEASE SEE 210.52 FOR REQUIRED
 RECEPT SPACING IN HOUSE. THERE ARE A
 NUMBER OF MISSING RECEPTS. PLEASE SEE
 ONE SET OF PLANS HAS MOST OF THEM
 REDLINED, BUT EXACT LOCATIONS ARE NOT
 SPECIFIED. PLEASE ALSO SEE LEISURE "RM"
 RAILING AREA IS CONSIDERED "WALL SPACE"
 AND WILL REQUIRE RECEPTS PER 210.52.
  
 17)NOTE: PLEASE SEE 210.52D, GFI RECEPT
 FOR BATHS ARE REQUIRED TO BE WITHIN
 3' OF THE EDGE OF SINK. PLEASE SEE
 "HER" BATH AREA.
  
 18)NOTE: PLEASE SEE FS 471, 481.FAC
 61G15-23
 PLEASE SEE PLANS THAT CONTAIN A TITLE
 BLOCK OF AN ARCH/ ENGINEERMUST BE
 SIGNED, DATED AND SEALED BY THAT
 ENGINEER/ OR ARCH.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD MAY BE REQUIRED FOR
 REFERENCE BY SOME PLAN REVIEWERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-06-08 Cont ID  
Sent By mjacobs Date 2005-06-08 Time 09:31 Rev Time 0.00
Received By mjacobs Date 2005-06-08 Time 09:31 Sent To E
Notes
2005-06-08 00:00:00TO 'DP' DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 13:35 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 13:35 Sent To E
Notes
2005-03-09 00:00:00TO "DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-02-08 Cont ID  
Sent By mjacobs Date 2005-02-08 Time 16:35 Rev Time 0.00
Received By mjacobs Date 2005-02-08 Time 16:35 Sent To E
Notes
2005-02-08 00:00:00TO "E" BOX/SUBMITTALS.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 10:19 Rev Time 0.00
Received By mjacobs Date 2004-12-14 Time 10:19 Sent To E
Notes
2004-12-14 00:00:00SENT TO "DP" DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 15:02 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 15:02 Sent To B
Notes
2004-11-12 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-08-20 Time 16:21 Rev Time 0.00
Received By csiegber Date 2004-08-20 Time 16:21 Sent To E
Notes
2004-08-20 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-16 Cont ID  
Sent By mmclean Date 2004-08-20 Time 14:52 Rev Time 0.00
Received By csiegber Date 2004-08-16 Time 16:53 Sent To Z
Notes
2004-08-16 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-02 Cont ID  
Sent By mmclean Date 2004-06-22 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2004-06-18 Time 15:42 Sent To  
Notes
2004-06-23 00:00:00TO SFD RACK/E
2004-06-18 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By prafter Date 2005-02-23 Time 09:21 Rev Time 0.50
Received By prafter Date 2005-02-23 Time 09:21 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-26 Cont ID  
Sent By pkrauss Date 2004-08-26 Time 15:25 Rev Time 0.30
Received By pkrauss Date 2004-08-26 Time 15:25 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By kstevens Date 2004-08-23 Time 15:38 Rev Time 0.35
Received By pkrauss Date 2004-06-24 Time 12:51 Sent To P
Notes
2004-06-24 00:00:00PROVISO:
 1.RETURN AIR JUMPER FROM BEDROOM #2
 SHALL BE A MINIMUM OF 12" PER THE
 REVISED 2001 FBC(M) 601.4 EXCEPTION #1.
  
 2.RETURN AIR REQUIRED FROM THE 1ST
 FLOOR DEN/TV ROOM.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-03-22 Cont ID  
Sent By jleech Date 2005-03-22 Time 17:24 Rev Time 0.50
Received By jleech Date 2005-03-22 Time 17:24 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-02-23 Cont ID  
Sent By kstevens Date 2005-02-23 Time 06:43 Rev Time 0.50
Received By kstevens Date 2005-02-23 Time 06:42 Sent To M
Notes
2005-02-23 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 A) COMMENTS FROM PREVIOUS REVIEW OF
 REVISIONS:
 1) SEE RED LINE CORRECTIONS ON ORIGINAL
 SHEET 13. PLEASE MAKE THESE CORRECTIONS
 AND SUBMIT AS A REVISION AS REQUIRED BY
 PROVISO.
 2) THERE ARE 2 SHEET 13 OF 13 IN EACH
 SET OF PLANS. PLEASE REMOVE EXTRA SHEETS
 FORM EACH SET OF PLANS. SECTION
 104.2.1.
 3) SUBMIT A NOTORIZED LETTER FOR THE
 RELEASE OF PREVIOUS ARCHITECT AND
 SHOWING NEW ENGINEER ACCEPTING
 RESPONSIBLITY FOR PLANS.
 **************NEW COMMENT************
 1B) FEES DUE FOR REVISION AND MUST BE
 PAID PRIOR TO NEXT REVIEW FOR THIS
 REVIEW.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-12-28 Cont ID  
Sent By kstevens Date 2004-12-28 Time 13:06 Rev Time 0.33
Received By kstevens Date 2004-12-28 Time 13:06 Sent To B1
Notes
2004-12-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) SEE RED LINE CORRECTIONS ON ORIGINAL
 SHEET 13. PLEASE MAKE THESE CORRECTIONS
 AND SUBMIT AS A REVISION AS REQUIRED BY
 PROVISO.
 2) THERE ARE 2 SHEET 13 OF 13 IN EACH
 SET OF PLANS. PLEASE REMOVE EXTRA SHEETS
 FORM EACH SET OF PLANS. SECTION
 104.2.1.
 3) SUBMIT A NOTORIZED LETTER FOR THE
 RELEASE OF PREVIOUS ARCHITECT AND
 SHOWING NEW ENGINEER ACCEPTING
 RESPONSIBLITY FOR PLANS.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-08-23 Cont ID  
Sent By kstevens Date 2004-08-23 Time 15:36 Rev Time 0.50
Received By kstevens Date 2004-08-23 Time 15:36 Sent To M
Notes
2004-08-23 00:00:00 
  
  
 PASSED/PROVISO
  
 REVISION REQUIRED - SANT. RISER DIAGRAM
 SHALL REFLECT THE INSTALLATION OF PIPE
 SEE RED LINE CORRECTION FOR LAUNDRY ROOM
 PIPING
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 O

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-28 Cont ID  
Sent By dpalmer Date 2004-08-23 Time 09:26 Rev Time 0.75
Received By jleech Date 2004-06-28 Time 18:21 Sent To B
Notes
2004-06-28 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW NOTE # 18.
 2.W/M AND L/T ARE REQUIRED TO DISCHARGE
 DOWN STREAM OF BATHROOM GROUP. 909.1.
 3.PLEASE SEE RISER DIAGRAM MARKED IN RED
 AND MAKE REQUIRED CHANGES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop REV REVISIONS
Rev No 1 Status N Date 2004-11-19 Cont ID  
Sent By rmcdouga Date 2004-11-19 Time 18:29 Rev Time 0.00
Received By rmcdouga Date 2004-11-19 Time 18:29 Sent To  
Notes
2004-11-19 00:00:00DENIED
  
 REVISED SHEETS ARE NOT SIGNED AND SEALED
 BY THE DESIGNER OF RECORD. THE ARCHITECT
 JEFFERY D. BRASSEUR SIGNED AND SEALED
 THE PLAN SHEETS THAT ARE ON
 FILE,THEREFORE HE IS REQUIRED TO SIGN
 AND SEAL ANY REVISIONS.

Review Stop Z ZONING
Rev No 3 Status P Date 2004-08-20 Cont ID  
Sent By mmclean Date 2004-08-20 Time 14:52 Rev Time 0.00
Received By mmclean Date 2004-08-20 Time 14:52 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2004-08-20 Cont ID  
Sent By mmclean Date 2004-08-20 Time 10:41 Rev Time 0.00
Received By mmclean Date 2004-08-20 Time 10:41 Sent To I
Notes
2004-08-20 00:00:00DENIED, OVER THE HOUSE HEIGHT REQ. OF
 30FT.NEED TO REDUCE HEIGHT.CALLED
 CONTRACTOR MM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-06-22 Cont ID  
Sent By csiegber Date 2004-08-16 Time 16:53 Rev Time 0.00
Received By mmclean Date 2004-06-22 Time 15:47 Sent To I
Notes
2004-06-22 00:00:00DENIED, OVER THE HEIGHT REQUIREMENT OF
 33FT.CALLED & LEFT MSG ON VOICE MAIL.