Plan Review Details - Permit 04060669
Plan Review Stops For Permit 04060669
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-07-14 Cont ID  
Sent By pkrauss Date 2004-08-11 Time 07:11 Rev Time 0.75
Received By alange Date 2004-07-14 Time 12:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-06-17 Cont ID  
Sent By dpalmer Date 2004-06-17 Time 16:02 Rev Time 0.33
Received By dpalmer Date 2004-06-17 Time 16:02 Sent To  
Notes
2004-06-17 00:00:00REDLINED 210.8A6

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-06-18 Cont ID  
Sent By mcarsill Date 2004-06-18 Time 12:52 Rev Time 0.00
Received By mcarsill Date 2004-06-18 Time 12:51 Sent To  
Notes
2004-06-18 00:00:001) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) ENSURE THAT THE EXISTING ELECTRIC
 POWERED SMOKE DETECTOR IS IN WORKING
 ORDER.
  
 3) ENTRY DOOR TO UNIT MUST POSITIVELY
 LATCH WHEN CLOSED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-07-26 Time 16:52 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 16:52 Sent To  
Notes
2004-07-26 00:00:00TO COMM BD#41

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-11 Cont ID  
Sent By pkrauss Date 2004-08-11 Time 07:07 Rev Time 0.25
Received By pkrauss Date 2004-08-11 Time 07:01 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-07-08 Cont ID  
Sent By pkrauss Date 2004-07-08 Time 14:17 Rev Time 0.35
Received By pkrauss Date 2004-07-08 Time 14:17 Sent To  
Notes
2004-07-08 00:00:00PROVISO:
 PLAN SHEET 7 OF 3 DEMOLITION NOTE #3,
 REMOVE ALL A/C DUCTWORK EXCEPT THAT
 SHOWN ON PLAN.PLAN DOES NOT INDICATE
 ANY DUCTWORK.NO MECHANICAL WORK
 INDICATED.PLEASE PROVIDE THE FOLLOWING
 INFORMATION PRIOR TO INSPECTION:
 1.INDICATE A/C EQUIPMENT NEW OR
 EXISTING.
 2.PROVIDE DUCT & GRILLE, SIZE,
 MATERIAL AND LAYOUT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-08-07 Cont ID  
Sent By kstevens Date 2004-08-07 Time 17:23 Rev Time 0.33
Received By kstevens Date 2004-08-07 Time 17:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By kstevens Date 2004-06-24 Time 11:45 Rev Time 0.50
Received By kstevens Date 2004-06-24 Time 11:44 Sent To  
Notes
2004-06-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT 3 DEMO NOTES AT TOP OF SHEET #5
 STATES REMOVE EXISTING SHOWER ENCLOSURE.
 NO SHOWER ENCLOSURE IS SHOWN IN BATH #2.
 PLEASE CLARIFY. SECTION 104.2.1
 2) ALL CAPPED PLUMBING PIPES SHALL BE
 INSPECTED PRIOR TO COVERING. (ADD TO THE
 NOTES). SECTION 104.2.1
 3) SHT 4 PARTIAL SANITARY RISER DIAGRAM,
 THE NEW TUB IS SHOWN AS AN "S" TRAP AND
 NOT APPROVED INSTALLED AS SUCH. SECTION
 1002.3(5).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]