Plan Review Details - Permit 04060665
Plan Review Stops For Permit 04060665
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 14:34 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 14:34 Sent To M
Notes
2004-06-15 00:00:00TO M ON PK DESK

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-08-19 Cont ID  
Sent By pkrauss Date 2004-08-19 Time 09:33 Rev Time 0.30
Received By pkrauss Date 2004-08-19 Time 09:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-08-03 Cont ID  
Sent By pkrauss Date 2004-08-03 Time 12:27 Rev Time 0.15
Received By pkrauss Date 2004-08-03 Time 12:27 Sent To  
Notes
2004-08-03 00:00:00PER CONVERSATION WITH EMITT (GC), MANUAL
 J OR 600C ON REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-16 Cont ID  
Sent By pkrauss Date 2004-06-16 Time 12:02 Rev Time 0.45
Received By pkrauss Date 2004-06-16 Time 06:56 Sent To  
Notes
2004-06-16 00:00:00DENIED:
 1.PROVIDE A COMPLETED FORM 600C IN
 ACCORDANCE WITH 2001 FBC CHAPTER 13
 SUB-CHAPTER 6.
  
 2.PROVIDE PLAN FOR THE DUCT & GRILLE
 LAYOUT.
  
 3.PROVIDE EQUIPMENT SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.